1Case Study Overview
During a routine night inspection, one runway edge light was found extinguished while all adjacent lights remained fully operational.
The Constant Current Regulator (CCR) was maintaining the selected current, and the primary series circuit showed normal electrical behavior.
Initial inspection suggested a failed LED fitting. However, replacement of the fixture did not restore operation.
The investigation ultimately identified an open circuit in the secondary winding circuit of the isolating transformer, preventing power from reaching the field fixture.
This case demonstrates the importance of separating primary-circuit diagnosis from secondary-circuit diagnosis in AGL systems.
2Learning Objectives
After completing this case study, the learner should be able to:
- Understand the function of the isolating transformer secondary circuit.
- Recognize symptoms of a secondary open-circuit fault.
- Differentiate transformer secondary faults from fixture failures.
- Perform systematic transformer secondary testing.
- Interpret continuity and resistance measurements.
- Investigate secondary cable and connector integrity.
- Verify transformer performance after replacement.
3System Background
An AGL isolating transformer electrically isolates the primary series circuit from the secondary fixture circuit.
A simplified arrangement is:
Primary Series Cable → Transformer Primary → Magnetic Coupling → Transformer Secondary → Secondary Leads → Light Fixture
A secondary open circuit may occur due to:
- Secondary winding failure.
- Broken secondary lead.
- Loose secondary termination.
- Corroded secondary connector.
- Internal transformer connection failure.
The primary circuit may remain fully operational while the individual light remains OFF.
4Problem Statement
The reported condition was:
- One runway edge light OFF.
- Adjacent lights ON.
- CCR operating normally.
- Primary circuit voltage normal.
- Fixture replacement unsuccessful.
- No visible cable damage.
Engineering QuestionIs the fault located in the light fixture, the transformer secondary circuit, or the transformer itself?
5Initial Observations
| CCR status |
Healthy |
| Selected current |
6.6 A |
| Primary circuit |
Normal |
| Affected light |
L71 OFF |
| Adjacent lights |
ON |
| Fixture replacement |
No improvement |
The failure of only one light strongly suggested a localized secondary-circuit problem.
6Initial Engineering Hypotheses
The maintenance team considered:
Hypothesis ALED fixture failure.
Hypothesis BSecondary cable open circuit.
Hypothesis CTransformer secondary winding open circuit.
Hypothesis DSecondary connector failure.
Hypothesis EPrimary transformer failure.
7Primary vs Secondary Faults
A useful diagnostic distinction is:
| Primary Fault |
May affect multiple lights |
| Secondary Fault |
Usually affects one light |
| Primary Fault |
CCR voltage often changes |
| Secondary Fault |
CCR often remains normal |
| Primary Fault |
Circuit current may change |
| Secondary Fault |
Circuit current usually remains normal |
| Primary Fault |
Section failure common |
| Secondary Fault |
Individual fixture failure common |
This observation directed the investigation toward the secondary side of the transformer.
8Test Equipment
The investigation used:
- True-RMS multimeter.
- Low-resistance continuity tester.
- Insulation resistance tester.
- Approved AGL transformer test equipment.
- Secondary cable test leads.
- Circuit drawings.
- Airport-approved PPE.
All testing was performed after approved circuit isolation.
9Investigation
Step 1: Verify Primary Circuit
Measurements confirmed:
| CCR current |
Normal |
| Primary continuity |
Normal |
| Adjacent transformers |
Operational |
The primary series circuit was healthy.
Step 2: Verify the Fixture
The LED fixture was tested separately. Results:
- Fixture continuity normal.
- Insulation normal.
- Bench operation satisfactory.
The fixture was not defective.
Step 3: Secondary Circuit Continuity
Continuity testing between the transformer secondary terminals and the fixture showed:
- Open circuit.
- Infinite resistance.
- No continuity.
This confirmed a secondary-circuit interruption.
Step 4: Secondary Lead Inspection
The secondary cable showed:
- No mechanical damage.
- Secure terminations.
- Acceptable insulation condition.
The secondary leads were healthy.
Step 5: Transformer Secondary Testing
The transformer was disconnected. Measurements:
| Primary winding |
Normal |
| Secondary winding |
Open circuit |
| Insulation resistance |
Acceptable |
| Core condition |
Normal |
The secondary winding showed infinite resistance, confirming an internal open circuit.
10Root Cause
Training-Case Finding
The isolating transformer developed an internal secondary winding open circuit caused by failure of the winding connection inside the transformer.
The primary winding remained functional, but the secondary circuit could not deliver power to the field fixture.
11Corrective Action
The maintenance team:
- Isolated the circuit.
- Removed the defective transformer.
- Inspected secondary connectors.
- Verified secondary cable integrity.
- Installed a new approved isolating transformer.
- Checked secondary continuity.
- Performed insulation resistance testing.
- Restored the circuit.
- Verified field-light operation.
- Recorded transformer replacement details.
12Post-Repair Verification
CCR operationNormal
Primary circuitNormal
Secondary continuityNormal
Light outputRestored
Transformer temperatureNormal
Maintenance documentationCompleted
The affected runway edge light returned to normal operation.
13Root-Cause Analysis
ProblemIndividual light OFF.
Secondary continuity testedOpen circuit.
Secondary cable testedHealthy.
Transformer testedSecondary winding open.
Root CauseInternal transformer secondary open circuit.
Corrective ActionReplace isolating transformer.
14Why This Case Was Important
A common maintenance error is replacing:
- LED fixtures.
- Connectors.
- Secondary cables.
before verifying transformer secondary continuity.
A secondary open circuit can perfectly mimic a failed light fitting.
15Engineering Lessons
01Separate primary and secondary diagnosis.
Always separate primary and secondary diagnosis.
02Single light failure rarely indicates a primary fault.
A single light failure rarely indicates a primary circuit fault.
03Test secondary continuity before fixture replacement.
Fixture replacement should not precede secondary continuity testing.
04Winding resistance measurement is valuable.
Transformer winding resistance measurement is a valuable diagnostic tool.
05Systematic testing prevents unnecessary replacement.
Systematic testing prevents unnecessary component replacement.
16Engineer's Decision Point
You observe: One runway edge light OFF. Adjacent lights ON. CCR operating normally. Fixture replacement unsuccessful. What should you investigate first?
A. Replace the CCR.
B. Replace the primary cable.
C. Test transformer secondary continuity.
D. Increase CCR current.
Correct answer: C. The failure pattern indicates a localized secondary-circuit problem. Secondary continuity testing is the appropriate next step.
17Knowledge Check
Q1. What was the primary fault?
Answer: Transformer secondary winding open circuit.
Q2. Did the primary circuit fail?
Answer: No.
Q3. Why did only one light remain OFF?
Answer: The fault was confined to the transformer secondary circuit.
Q4. What test confirmed the fault?
Answer: Secondary winding continuity and resistance testing.
Q5. What was the corrective action?
Answer: Replacement of the isolating transformer.
18Interview Questions
What is the function of an AGL isolating transformer?
How does a secondary open circuit affect the AGL system?
Why can the CCR remain normal during a secondary fault?
How would you test a transformer secondary winding?
What is the difference between a fixture failure and a transformer secondary failure?
Why is winding resistance measurement important?
How would you isolate the transformer from the field fixture?
What post-replacement tests should be performed?
What documentation should be recorded after transformer replacement?
How can transformer failures be reduced through preventive maintenance?
Quick Reference: Isolating Transformer Secondary Voltage
The isolating transformer secondary voltage is the voltage delivered to the lamp or LED module. It depends on the lamp load at the rated current. With the circuit energised and the right safety procedure followed, a normal reading means the transformer works and the fault is in the lamp or its wiring. No reading with a healthy primary points to an open secondary circuit, as in this case.
19Frequently Asked Questions
Quick answers about isolating transformer secondary open circuit, based on this case study.
Q1What is AGL-CS-016?
AGL-CS-016 is an engineering training case study on a single runway edge light failure caused by an open circuit in an isolating transformer secondary winding, which mimicked a failed fixture. It is an engineering simulation created for training, not a report of an actual airport incident.
Q2Why can a transformer fault look like a fixture failure?
One light was OFF while adjacent lights were ON and the CCR and primary circuit were normal, which is the usual pattern of a fixture failure. Replacing the fixture did not restore operation, revealing the fault was elsewhere.
Q3Why separate primary and secondary diagnosis?
The primary series circuit and the secondary circuit fail in different ways. Here the primary winding was functional, but the secondary could not deliver power to the fixture, so the two sides had to be tested separately.
Q4What was the root cause?
An internal secondary winding open circuit, caused by failure of the winding connection inside the isolating transformer. The primary winding remained functional.
Q5How is a transformer secondary open circuit confirmed?
Test transformer secondary continuity after approved circuit isolation. The team used a true-RMS multimeter, low-resistance continuity tester, insulation resistance tester, approved AGL transformer test equipment and secondary cable test leads.
Q6How was the circuit repaired?
The team isolated the circuit, removed the defective transformer, inspected secondary connectors and verified secondary cable integrity. They installed a new approved isolating transformer, checked secondary continuity, tested insulation resistance, restored the circuit and recorded the replacement details.
Q7How was the repair verified?
CCR operation, the primary circuit and secondary continuity were normal, light output was restored and transformer temperature was normal. Documentation was completed.
Q8What should you investigate first if one light is OFF, adjacent lights are ON and a fixture replacement failed?
Test transformer secondary continuity. Replacing the CCR or primary cable, or increasing CCR current, is not the right next step.
Engineering & Expert Notes
RS
By Rahul Sharma
Airfield Ground Lighting Specialist
Separate Primary and Secondary Tests
MethodTest each side independently so the result points to the winding rather than the cable or fixture.
Check Secondary Connections Before Opening the Case
TerminationsMost secondary faults are at the lead or connector. Confirm those before condemning the transformer.
Treat the Primary as Live Until Proved Isolated
SafetyThe primary circuit carries series current and voltage. Follow isolation and permit procedures before any disconnection.
Record Transformer Type and Rating at Replacement
RecordsThe replacement must match the original rating. Note it on the register to avoid mismatches later.
20Case Study Conclusion
Key Engineering Principle
A single AGL light failure should be investigated through systematic secondary-circuit testing before replacing field fixtures or primary-circuit components.
Verification of secondary continuity, winding resistance, connector integrity, and transformer isolation can accurately identify secondary open-circuit faults and prevent unnecessary maintenance actions.
In AGL engineering, a healthy primary circuit does not guarantee a healthy transformer secondary circuit, and the correct diagnosis often begins at the transformer terminals.
Go Deeper
Turn Case Studies Into Engineering Capability
A case study shows you how a problem is investigated. Precision AGL Academy helps you build the knowledge to understand why it happens, diagnose it systematically, and apply the right engineering approach.
Study real-world-style engineering scenarios, identify failure patterns, understand root causes, and develop a systematic approach to AGL troubleshooting.
Study the case. Understand the system. Build the skill.
Build Your Knowledge Across
Fundamentals
Electrical Systems
Fault Finding
Photometry
Installation
Testing
Commissioning
Maintenance
Explore More
More Case Studies in This Category