What is circuit termination?

Where a series lighting circuit starts and ends — both cable ends land at the CCR, so the loop has no far end.

SERIES LOOP · CIRCUIT TERMINATION AT THE CCR TERMINATE ONLY WHEN ISOLATED · LOCKED OUT · DEAD CCR OUT RTN T1 T2 T3 T4 1 LOOP LEAVES THE CCR AT ONE OUTPUT TERMINAL 2 AND RETURNS TO THE OTHER — BOTH ENDS TERMINATED 3 NO FAR END — THE LOOP CLOSES AT THE CCR BOTH ENDS TERMINATED LOOP CLOSED Current flows out, round and back LOOSE OR UNTERMINATED END OPEN CIRCUIT Lights out, and a hazard at the loose end SCHEMATIC · LOOP SHORTENED · NOT TO SCALE
series loop (primary cable)
terminated end (CCR output)
lamp lit
The Fact Series circuit design

Circuit termination is where a series lighting circuit starts and ends. Both ends of the primary cable are terminated at the CCR output terminals: the cable leaves one terminal, runs through every isolation transformer primary in series, and returns to the other. The loop has no far end.

A loose, damaged or unterminated end opens the loop, so every lamp goes out, and a poor connection can overheat. Terminations are made with the circuit isolated, locked out and proved dead, insulated, identified, and checked by continuity and insulation tests. This is different from cable termination, the physical work of connecting a cable end that happens at many points around the loop.

  1. Route. Run the primary cable out through the circuit and back to the CCR.
  2. Isolate. CCR off, locked out and tagged; confirm the circuit is dead.
  3. Terminate. Connect both cable ends at the CCR output terminals.
  4. Insulate & identify. Protect each connection and label the circuit and ends.
  5. Test. Continuity and insulation resistance on the closed loop.
  6. Record. Log the readings against the commissioning baseline.
Where Both cable ends at the CCR output terminals
Far end None; the loop returns to the CCR
If lost Open circuit; all lamps out; hazard at the loose end
Made when Circuit isolated, locked out and proved dead
Checked by Inspection, continuity and insulation tests
Reference ICAO Doc 9157 Pt 5; FAA AC 150/5340-30
Schematic — loop shortened for clarity. Isolation means the full sequence shown in Entry 10, Circuit Isolation, including earthing at the work point. Always follow your site’s isolation and permit-to-work procedure and the equipment manufacturer’s instructions; fault-finding methods and acceptable values are set by the applicable standard and the commissioning record.
Entry 16 · Circuit expansion Entry 18 · Film cutout operation

Frequently Asked Questions

Q1What is circuit termination in a series lighting circuit?

The points where the series loop starts and ends. The two ends of the primary cable are terminated at the CCR output terminals, and every isolation transformer primary is connected in series in the cable between them.

Q2Where does a series lighting circuit terminate?

At the CCR. A series loop has no far end: the cable leaves one CCR output terminal, runs through all the transformers and returns to the other output terminal, so the circuit is closed at the CCR.

Q3Why can't a circuit end at the last fixture?

Current needs a complete path. A cable that ends at the last fixture leaves the loop open, so no current flows and every lamp on the circuit goes out. The cable has to return to the CCR to close the loop.

Q4What happens if a termination is loose or fails?

The loop can open, giving an open circuit with all lights out, or the poor connection can overheat or arc at the terminal. A loose end on an energised circuit is also a shock hazard, so terminations must be secure, insulated and protected.

Q5How is a termination checked?

With the circuit isolated, locked out and proved dead, by inspecting the connection and its insulation, then testing continuity and insulation resistance of the loop and comparing the readings with the commissioning baseline.

Q6How is circuit termination different from cable termination?

Circuit termination is where the loop starts and ends at the CCR. Cable termination is the physical work of connecting a cable end to a connector, joint or terminal, which happens at many points around the loop, including at the CCR.

Precision AGL Academy

See It. Understand It. Then Learn How to Engineer It.

Recognising an AGL system visually is the first step. The next step is knowing how to design, install, test, commission and maintain them correctly.

Build Practical AGL Engineering Skills

Go deeper with structured training from Precision AGL Academy, covering:

AGL Fundamentals Design & Electrical Engineering Approach Lighting Photometry Installation & Commissioning Maintenance & Troubleshooting

Learn how each light, sign and circuit works as part of a complete airport lighting system, not just as an isolated diagram.

See. Understand. Apply. Engineer.