ALCMS Server
The central computing platform of the Airfield Lighting Control and Monitoring System (ALCMS). It aggregates data from field equipment, executes control logic, stores historical logs, manages alarm events, and provides a secure interface for operators to monitor and control all AGL assets from a single, unified dashboard.
Image disclaimer: For identification and illustration only. It may show a product by another manufacturer and may not depict the exact item described; it is not a statement of any product’s quality, approval or performance. Third-party image and trademark rights belong to their owners. See full notice.
What Is It?
The ALCMS Server (Airfield Lighting Control and Monitoring System Server) is the central computing and data management platform for the entire airfield ground lighting system. It is a high‑reliability industrial server that runs specialised software to communicate with field equipment—CCRs, remote I/O, PLCs, and smart fixtures—over various communication protocols (Ethernet, serial, fibre optic). The server provides a centralised point of control, monitoring, and data logging for all AGL assets across the airfield.
Key characteristics of the ALCMS server include:
- High Reliability: Designed for 24/7/365 operation in critical infrastructure environments, often with redundant power supplies, RAID storage, and hot‑swappable components.
- Industrial‑Grade Hardware: Built with industrial‑grade motherboards, processors, and memory that are tested for extended temperature ranges, vibration, and electromagnetic interference.
- Redundancy: Typically deployed in a primary‑backup or active‑active configuration to ensure uninterrupted operation in the event of a hardware failure.
- Secure Communication: Supports encrypted communication protocols (e.g., TLS, HTTPS) and role‑based access control (RBAC) to ensure that only authorised personnel can control or modify AGL settings.
Core functions of the ALCMS server include:
- Data Acquisition: Polling field equipment (CCRs, remote I/O, sensors) for status, current readings, alarm states, and fault conditions.
- Control Execution: Sending command signals to CCRs for brightness step changes, switching circuits on/off, and controlling stop bars and other field equipment.
- Alarm Management: Processing and prioritising alarms from field equipment, displaying them on operator workstations, and logging them for historical analysis.
- Logging and Reporting: Storing historical data on circuit status, current readings, alarm events, and operator actions for compliance, reporting, and trend analysis.
- User Interface: Serving the operator interface (HMI/SCADA) to workstations, presenting a visual representation of the airfield with real‑time status indicators.
The server is typically installed in a secure equipment room or control tower, connected to the airfield network via redundant fibre optic or Ethernet links. It is maintained by the airfield's IT and engineering teams, with regular backups, patches, and performance monitoring.
Purpose & Function
The ALCMS server exists as the single source of truth for the entire airfield lighting system's status, because without centralised data acquisition and control execution, every operator workstation, alarm panel, and remote HMI would need its own independent connection to hundreds of field devices — a fragile, inconsistent, and effectively unmanageable architecture. By consolidating polling, control commands, and historical logging into one authoritative platform, the server ensures every part of the AGL system sees the same, current picture of the field.
Its emphasis on redundancy and 24/7/365 reliability reflects what's actually at stake if it fails: since it's the platform that processes alarms, executes control commands, and serves the operator interface, a server outage doesn't just lose data — it can cut operators off from monitoring and controlling live runway and taxiway lighting, which is why hot-swappable components and active-active configurations are standard rather than optional for this role.
Where Is It Used?
The ALCMS server is used in all airfields that have a modern AGL control and monitoring system, including:
- International Airports: Managing large‑scale AGL systems with multiple runways, taxiways, and approach lighting systems, often with redundant servers and distributed I/O.
- Regional Airports: Providing centralised control and monitoring for smaller but still critical AGL systems, often with a single server and a limited number of workstations.
- Military Air Bases: Supporting mission‑critical AGL operations with enhanced security features and redundant configurations.
- Heliports: Controlling and monitoring heliport lighting systems, often with a smaller‑scale ALCMS server.
- Airfield Equipment Shelters: The server may be installed in an airfield equipment shelter near the CCR room, or in the control tower, depending on the architecture.
The server is the core component of the ALCMS architecture, which typically includes:
- Field Equipment: CCRs, remote I/O modules, PLCs, smart transformers, and sensors.
- Communication Network: Fibre optic backbone, Ethernet switches, and communication gateways.
- Operator Workstations: Desktop PCs or thin clients running the ALCMS operator interface.
- Peripheral Systems: Printers for alarm logging, external displays for status boards, and integration with other airport systems (e.g., ATC, ground handling).
The server is typically specified with high‑availability features, including dual power supplies, RAID 1 or RAID 10 storage, and redundant network interfaces. The software is designed to be fault‑tolerant, with automatic failover to a backup server in the event of a primary server failure.
Installation & Location
Servers are rack-mounted in the airport's main equipment room or a dedicated ALCMS server room with controlled access, conditioned power (UPS-backed), and adequate cooling for continuous operation, rather than in the operator-facing control room itself. Where the system is configured with redundant servers, the pair is split across separate racks or rooms on independent power feeds so a single electrical or physical fault cannot take down both; network cabling runs to the site's core switches on structured cabling rather than field cable, keeping the server room's cabling entirely separate from the field-device wiring that terminates at PLCs and Remote I/O out at the substations.
How Does It Work?
The ALCMS server functions as the central brain of the airfield lighting system, orchestrating all control, monitoring, and data management activities:
- Communication Engine: The server runs a communication engine that polls field equipment at configurable intervals (typically 1‑5 seconds). It uses protocols such as IEC 61850, MODBUS, DNP3, or proprietary protocols to communicate with CCRs, remote I/O, and smart fixtures. The engine handles time‑stamping, retries, and error handling to ensure reliable data exchange.
- Database Management: The server hosts a real‑time database that maintains the current state of all AGL equipment (on/off status, current level, alarm states). This database is continuously updated and serves as the source of truth for operator displays. Historical data is logged to a separate historian database for analysis and reporting.
- Alarm Processing: The server analyses incoming data for abnormal conditions, such as circuit faults, overcurrent, undercurrent, or communication loss. Alarms are categorised by severity (critical, major, minor) and displayed on operator workstations with clear visual and audible indicators. The server also logs all alarm events for later review.
- Command Execution: When an operator initiates a control action (e.g., changing brightness level, turning on a runway), the server validates the command (checking permissions, operational constraints), formats it into the appropriate protocol, and transmits it to the target field device. The server then confirms the successful execution and updates the operator interface.
- User Interface: The server hosts a web‑based or client‑server graphical user interface that is accessed by operator workstations. The interface provides a dynamic, geospatial representation of the airfield, with colour‑coded icons indicating the status of each circuit and fixture. Operators can click on any element to view detailed status, historical data, or to issue commands.
- Security Management: The server implements role‑based access control (RBAC), allowing different user levels (operator, supervisor, administrator) with different permissions. All user actions are logged for audit purposes. The server also supports encrypted communication (TLS/SSL) to protect against unauthorised access and eavesdropping.
The server is typically deployed in a client‑server architecture, with multiple workstations connecting to the server over the airfield network. In larger airports, a redundant server configuration is used, with a primary server and a hot‑standby backup server that automatically takes over in the event of a failure. The server also includes comprehensive diagnostics and self‑monitoring capabilities, alerting operators if the server itself experiences any issues.
System Architecture & Control Logic
The ALCMS server sits at the centre of the control hierarchy, one level above the field controllers and one level below the operator. Upstream, it exchanges real-time status and receives validated commands from PLCs, Remote I/O units, and CCRs, typically reaching them through an Ethernet switch and, where legacy or serial field devices are involved, a Communication Gateway or SCADA Interface performing protocol translation (Modbus, IEC 61850, OPC UA). Downstream, it serves one or more ALCMS Workstations (and Touchscreen HMIs at local panels), pushing map-based status updates and accepting operator commands after validating them against permissions and interlock conditions. Every status change and command is timestamped and written to the historian database, so the server is also the single point where the full operational picture and audit trail come together.
Field Layer
CCRs, PLCs & Remote I/O reporting circuit and fixture status
Network & Protocol Layer
Ethernet Switch, Communication Gateway / SCADA Interface (Modbus, OPC UA, IEC 61850)
ALCMS Server
Validates commands, formats field messages, writes historian records
Operator Layer
ALCMS Workstation(s) & Touchscreen HMIs — display, command entry, alarms
Redundancy & Automatic Failover
Primary Server Operating
Polls CCRs, remote I/O, and smart fixtures every 1–5 seconds
Continuous Self-Monitoring
Server diagnostics track its own hardware and communication health
Normal Operation Confirmed
Real-time database stays current for all operator displays
Primary Remains Source of Truth
Command execution and alarm processing continue as normal
Hardware or Communication Fault
Self-monitoring flags the primary as unavailable
Hot-Standby Backup Takes Over
Automatic switchover; operators alerted, control continues uninterrupted
Airfield Lighting Control Cannot Have a Single Point of Failure — Failover Is Automatic, Not Manual
Physical Construction
The server is built in a standard 19-inch rack-mount chassis, either 2U or 4U depending on storage and expansion needs, with a steel or aluminium enclosure designed for continuous airflow through front-to-rear cooling fans. Dual hot-swappable power supplies sit in the rear, each independently fed from the facility's redundant UPS circuits so either can fail without interrupting operation, and hot-swap drive bays at the front allow RAID array members to be replaced without powering down the server. Internal cabling and expansion cards (network interfaces, serial adapters, fibre SFP modules) are secured to the chassis rail system per rack-mount convention, and the unit is designed to sit in a temperature- and humidity-controlled equipment room or server rack rather than an outdoor cabinet. Front-panel status LEDs and a local console port allow basic diagnostics without needing to log in remotely, and the chassis is typically secured in the rack with a lockable front bezel to prevent unauthorised access to drive bays and power switches.
Technical Parameters
| Parameter | Typical Value |
|---|---|
| Form Factor | 2U or 4U rack‑mount server (19" rack) |
| Processor | Intel Xeon (dual‑socket), AMD EPYC, or industrial‑grade embedded processor |
| Memory (RAM) | 16GB to 128GB ECC RAM |
| Storage | RAID 1 (mirrored) or RAID 10 (mirrored + striped) SSDs or HDDs; 2TB to 20TB capacity |
| Operating System | Windows Server (with ALCMS software), Linux (Red Hat, Ubuntu), or real‑time OS (VxWorks, QNX) |
| Communication Ports | 2 x 1G Ethernet, 2 x 10G Ethernet (optional), RS‑232/422/485 serial ports (optional), fibre optic SFP slots |
| Protocols Supported | IEC 61850, MODBUS TCP/RTU, DNP3, SNMP, BACnet, OPC UA, proprietary AGL protocols |
| Power Supply | Redundant, hot‑swappable power supplies (2 x 500W to 1000W, 1+1 redundant) |
| Redundancy | Active‑standby (hot‑standby) or active‑active (load‑balanced) configurations |
| Data Storage | Real‑time database (in‑memory) plus historian database (disk‑based) |
| Operating Temperature | 0°C to 45°C (standard), -20°C to 60°C (industrial‑grade) |
| Humidity | 10% to 90% non‑condensing |
| Regulatory Compliance | FCC, CE, RoHS, IEC 61850, FAA AC 150/5345‑56 |
Electrical Requirements
| Requirement | Typical Value |
|---|---|
| Circuit Position | Standalone mains-powered server, control-room equipment; not part of the series lighting loop |
| Power Supply | Redundant, hot-swappable power supplies (2 x 500W to 1000W, 1+1 redundant) |
| Isolation | Powered independently of the AGL series circuit; communicates with CCRs via control/data interfaces only |
| Earthing | Rack/chassis bonded to control-room earth |
| Backup Power | UPS/generator backup typical for critical ALCMS installations |
| Fault Protection | Dual power supplies with automatic failover on loss of one input |
Applicable Standards
IEC 61850
Communication networks and systems for power utility automation (used for AGL control and monitoring)
FAA AC 150/5345‑56
Specification for L-890 Airport Lighting Control and Monitoring System (ALCMS)
ICAO Annex 14
Requirements for control and monitoring of AGL systems
NIST SP 800‑53
Security and privacy controls for information systems (cybersecurity for critical infrastructure)
Installation Requirements
Server Room Environment
CivilConfirm the server room or dedicated ALCMS space has conditioned power, adequate cooling, and controlled access before racks are installed, since continuous operation depends on a stable environment.
Rack Mounting & Redundant Placement
MechanicalMount servers in their racks and, where redundant, split the pair across separate racks or rooms on independent power feeds so a single physical fault cannot take down both.
UPS-Backed Power Feed
ElectricalConnect each server to its UPS-backed supply and confirm changeover to battery holds the unit up through a mains interruption before going live.
Structured Network Cabling
ElectricalRun structured cabling from the server to the site's core switches, kept entirely separate from the field-device wiring terminating at PLCs and Remote I/O out at the substations.
Redundancy & Failover Configuration
DocumentationConfigure and record the failover behaviour between redundant servers so a documented, tested procedure exists before the system is relied on operationally.
Pre-Commissioning Sign-off
DocumentationRecord rack position, power feed, and network cabling as-built, confirming the server room configuration matches the design before commissioning testing begins.
Testing & Commissioning
Hardware Burn-In & Health Check
Pre-CommissioningRun an extended hardware diagnostic and burn-in cycle before the server is accepted into service, catching early component failures.
Failover / Redundancy Test
CommissioningSimulate a primary server failure and confirm automatic failover to the redundant unit with no loss of control.
Field Device Communication Test
CommissioningConfirm the server establishes and holds communication with every CCR, PLC, and remote I/O point on the network.
UPS & Power Failure Simulation
CommissioningSimulate a mains power loss and confirm the server rides through on UPS power without data loss.
Database & Data Logging Verification
CommissioningConfirm event and status data is correctly logged and retrievable from the moment of first power-up.
Time Synchronisation Verification
CommissioningConfirm the server's clock source (NTP/GPS) is correctly synchronised before go-live.
Operator Workstation & Access Control Test
Final AcceptanceConfirm every operator workstation can log in, view, and control the system per its assigned permission level.
Documentation & As-Built Sign-off
Final AcceptanceRecord configuration, IP addressing, and test results in the commissioning dossier for handover.
Inspection & Maintenance
Hardware Health Check
MonthlyReview power supply, disk, memory, and fan diagnostics through server management tools, replacing degraded components before they trigger a failover event.
Failover / Redundancy Test
QuarterlyManually trigger an active-standby (or active-active) switchover to confirm the backup server takes control cleanly and without data loss.
Database Backup & Integrity Check
WeeklyVerify real-time and historian database backups complete successfully and run integrity checks to catch corruption before it affects historical records.
Security Patch & Antivirus Update
MonthlyApply vetted OS and application security patches, update antivirus definitions, and review access logs for unauthorised login attempts.
Time Synchronisation Verification
QuarterlyConfirm the server's NTP source and offset remain within tolerance so alarm and event timestamps stay consistent across all field devices.
UPS & Cooling Inspection
Semi-annualTest UPS battery runtime and load transfer, and check equipment room cooling and airflow to prevent thermal shutdowns.
Software & Firmware Review
QuarterlyCheck for ALCMS software and server firmware updates, testing on a staging system before rollout and maintaining a rollback snapshot.
Log & Storage Capacity Review
MonthlyAudit event and historian log growth against available disk capacity, archiving or purging aged data to prevent storage exhaustion.
Common Field Issues
Hardware Failure
Like all servers, the ALCMS server is subject to hardware failures—power supply failure, hard disk failure, or motherboard issues. Always deploy a redundant server configuration (active‑standby) and keep spare parts on hand. Implement regular hardware health checks and monitoring.
Network Connectivity Issues
If the server loses network connectivity to field equipment, it cannot control or monitor the AGL system. Use redundant network paths (dual‑homed servers) and monitor network health. Implement automatic failover to backup network interfaces.
Software Bugs and Updates
ALCMS software can contain bugs that affect performance or reliability. Ensure that the software is properly tested before deployment, and apply patches and updates in a controlled manner. Maintain a fallback version (snapshot or backup) to roll back if needed.
Database Corruption
The real‑time and historian databases can become corrupted due to power loss or software errors. Use a robust database management system (DBMS) with transaction logging, and perform regular backups. Consider using a database replication feature to maintain a copy on the backup server.
Cybersecurity Threats
The ALCMS server is a potential target for cyberattacks. Implement strong access controls, use encrypted communication, regularly update antivirus and security patches, and monitor for unusual activity. Conduct regular security audits and penetration tests.
Time Synchronisation Issues
If the server's clock is not synchronised with field equipment, time‑stamped events (alarms, logs) will be inconsistent. Use a Network Time Protocol (NTP) server to synchronise the system clock across all devices.
Inadequate Cooling and Power
Servers generate significant heat and require clean, stable power. Install the server in a temperature‑controlled equipment room with adequate ventilation and cooling. Use a UPS to protect against power surges and provide backup power during short outages.
Troubleshooting Guide
Active Server Fails Over to Standby Unexpectedly
Server Cannot Control or Monitor Field Equipment
System Behaves Unexpectedly After a Recent Software Update
Historical Data Missing, Corrupted, or Inconsistent
Alarm and Log Timestamps Don't Match Across Devices
Server Performance Degrading or Unexpected Shutdowns
Failure Modes & Root Causes
Redundant Server Failover
Field Network Path Failure
Software Update Regression
Database Corruption
Clock Synchronisation Fault
Environmental / Power Instability
Safety & Operational Notes
Isolate Both Redundant Power Supplies
Electrical SafetyThe server's redundant, hot-swappable power supplies are designed to keep it running through a single-input failure; before internal work, isolate and lock out both inputs independently and verify zero energy, since disconnecting only one leaves the unit live.
UPS-Backed Output May Stay Live
Electrical SafetyWhere the server's supply is UPS-backed, isolating the mains feed to the UPS does not necessarily de-energise the server; confirm the UPS output itself is isolated or the server is cleanly shut down before disconnecting power cabling.
ESD-Sensitive Electronics
OperationalUse anti-static precautions when handling internal boards, drives, or memory modules.
Data Integrity Before Shutdown
OperationalPerform an orderly shutdown of the ALCMS software and confirm any active database transactions or logs are safely committed before removing power, to avoid corrupting the airfield's historical lighting/fault records.
Access Control for Configuration Changes
ComplianceMake configuration or software changes only under an authorised change-control process, since the server is the central point of control for CCRs, remote I/O, and smart fixtures across the airfield.
Restore to Compliant State
ComplianceConfirm the server re-establishes communication with all connected field devices and that alarm/logging functions are operating correctly before closing out the work.
Engineering & Expert Notes
Test Failover on a Schedule, Not Just at Commissioning
ReliabilityA hot-standby server pair that failed over perfectly at commissioning can silently lose that capability months later if the standby's software drifts out of sync with the primary through unmirrored patches or config changes. Run a real, scheduled failover test rather than trusting a "standby healthy" status light, since the status check itself may not exercise the actual cutover logic.
Verify Backups Restore, Not Just Complete
Data IntegrityA backup job that reports success only confirms the write completed, not that the resulting file is a usable database. Periodically perform an actual restore-and-verify onto a test instance; a corrupted backup that's gone unnoticed for months is far worse than no backup, because it creates false confidence.
Time Sync Faults Look Like Data Faults
TroubleshootingWhen the server's time reference drifts, alarm sequences and event logs can appear to arrive out of order or duplicate, which technicians often misdiagnose as a field-device or database problem. Check NTP/time-sync health early in any troubleshooting sequence involving odd event ordering, before chasing the field layer.
Patch Management Needs a Rollback Plan, Not Just a Schedule
CybersecurityApplying security patches to a live ALCMS server without a tested rollback path risks trading a theoretical vulnerability for an actual outage if a patch conflicts with the control software. Always validate patches on a non-production instance first and keep a known-good snapshot ready before touching the production server.
Watch Log Growth as a Leading Indicator
Capacity PlanningSteadily rising event-log or database growth often signals a chattering field device (a fixture or CCR flapping between states) well before that device causes a visible operational problem. Trend storage consumption over time and investigate the source of any unexplained increase rather than simply expanding storage capacity.
Dual-Homed Doesn't Mean Automatically Redundant
NetworkingA server with two network interfaces only gains real redundancy if both paths actually terminate on physically independent switches and, ideally, separate power feeds; two NICs cabled into the same switch just moves the single point of failure one hop downstream. Verify the physical diversity of both paths during design review, not just the server's NIC count.
Frequently Asked Questions
Short answers about the ALCMS Server: what it is, how it works, typical specifications, standards, maintenance and common faults.
Q1What is an ALCMS Server?
The ALCMS Server (Airfield Lighting Control and Monitoring System Server) is the central computing and data management platform for the entire airfield ground lighting system. It is a high‑reliability industrial server that runs specialised software to communicate with field equipment—CCRs, remote I/O, PLCs, and smart fixtures—over various communication protocols (Ethernet, serial, fibre optic). The server provides a centralised point of control, monitoring, and data logging for all AGL assets across the airfield.
Q2What is the purpose of an ALCMS Server?
The ALCMS server exists as the single source of truth for the entire airfield lighting system's status, because without centralised data acquisition and control execution, every operator workstation, alarm panel, and remote HMI would need its own independent connection to hundreds of field devices — a fragile, inconsistent, and effectively unmanageable architecture. By consolidating polling, control commands, and historical logging into one authoritative platform, the server ensures every part of the AGL system sees the same, current picture of the field.
Q3Where is an ALCMS Server used and installed?
The ALCMS server is used in all airfields that have a modern AGL control and monitoring system, including: International Airports: Managing large‑scale AGL systems with multiple runways, taxiways, and approach lighting systems, often with redundant servers and distributed I/O. Regional Airports: Providing centralised control and monitoring for smaller but still critical AGL systems, often with a single server and a limited number of workstations. Military Air Bases: Supporting mission‑critical AGL operations with enhanced security features and redundant configurations.
Q4How does an ALCMS Server work?
The ALCMS server functions as the central brain of the airfield lighting system, orchestrating all control, monitoring, and data management activities: Communication Engine: The server runs a communication engine that polls field equipment at configurable intervals (typically 1‑5 seconds). It uses protocols such as IEC 61850, MODBUS, DNP3, or proprietary protocols to communicate with CCRs, remote I/O, and smart fixtures. The engine handles time‑stamping, retries, and error handling to ensure reliable data exchange.
Q5What are the typical technical parameters of an ALCMS Server?
Typical values are — Form Factor: 2U or 4U rack‑mount server (19" rack); Processor: Intel Xeon (dual‑socket), AMD EPYC, or industrial‑grade embedded processor; Memory (RAM): 16GB to 128GB ECC RAM; Storage: RAID 1 (mirrored) or RAID 10 (mirrored + striped) SSDs or HDDs; 2TB to 20TB capacity; Operating System: Windows Server (with ALCMS software), Linux (Red Hat, Ubuntu), or real‑time OS (VxWorks, QNX); Communication Ports: 2 x 1G Ethernet, 2 x 10G Ethernet (optional), RS‑232/422/485 serial ports (optional), fibre optic SFP slots; Protocols Supported: IEC 61850, MODBUS TCP/RTU, DNP3, SNMP, BACnet, OPC UA, proprietary AGL protocols.
Q6What are the electrical requirements for an ALCMS Server?
Typical requirements are — Circuit Position: Standalone mains-powered server, control-room equipment; not part of the series lighting loop; Power Supply: Redundant, hot-swappable power supplies (2 x 500W to 1000W, 1+1 redundant); Isolation: Powered independently of the AGL series circuit; communicates with CCRs via control/data interfaces only; Earthing: Rack/chassis bonded to control-room earth; Backup Power: UPS/generator backup typical for critical ALCMS installations; Fault Protection: Dual power supplies with automatic failover on loss of one input.
Q7Which standards apply to an ALCMS Server?
The main references are IEC 61850 — Communication networks and systems for power utility automation (used for AGL control and monitoring); FAA AC 150/5345‑56 — Specification for L-890 Airport Lighting Control and Monitoring System (ALCMS); ICAO Annex 14 — Requirements for control and monitoring of AGL systems; NIST SP 800‑53 — Security and privacy controls for information systems (cybersecurity for critical infrastructure). Always verify the current edition and your aerodrome's approved requirements.
Q8How often should an ALCMS Server be inspected and maintained?
Typical maintenance tasks and intervals are: Hardware Health Check (monthly); Failover / Redundancy Test (quarterly); Database Backup & Integrity Check (weekly); Security Patch & Antivirus Update (monthly); Time Synchronisation Verification (quarterly); UPS & Cooling Inspection (semi-annual); Software & Firmware Review (quarterly); Log & Storage Capacity Review (monthly). Your airport's approved maintenance programme takes precedence.
Q9How do I troubleshoot common ALCMS Server faults?
Common symptoms covered are: Active Server Fails Over to Standby Unexpectedly; Server Cannot Control or Monitor Field Equipment; System Behaves Unexpectedly After a Recent Software Update; Historical Data Missing, Corrupted, or Inconsistent; Alarm and Log Timestamps Don't Match Across Devices; Server Performance Degrading or Unexpected Shutdowns. For example, for "Active Server Fails Over to Standby Unexpectedly": Likely Cause: A hardware fault (power supply, disk, or motherboard) on the active server triggered the redundant active-standby configuration to fail over, or the failover was triggered by a network connectivity loss rather than a genuine hardware fault. Diagnostic Steps: Check the failed-over server's hardware health logs for the fault that triggered failover; verify network connectivity to field equipment was intact at the time of the event to rule out a network-triggered failover. Corrective Action: Replace the faulted hardware component using spares on hand; once repaired, restore it as standby rather than immediately failing back, to confirm stability first.
Related Components
Go Beyond the Component. Understand the Complete AGL System.
You have explored the component. Now understand how it works within the complete Airfield Ground Lighting system.
Learn AGL from fundamentals to design, installation, testing, photometry, commissioning, maintenance and troubleshooting through structured technical training at Precision AGL Academy.
Build practical knowledge. Understand the circuit. Read the standards. Troubleshoot with confidence.
Your next step in AGL starts here.
Need expert guidance on ALCMS server selection, configuration, or redundancy planning for your airfield?
Precision AGL Academy provides advice on server sizing, redundancy architectures, cybersecurity, and integration with existing AGL systems.
Follow the Academy
Important Notice, Disclaimer & Limitation of Liability
Please read before relying on any content on this page.
- Purpose and intended users. This page on ALCMS Server is an independent educational and informational reference for competent, suitably trained and authorised airfield ground lighting (AGL) and aerodrome electrical personnel. It is not professional engineering, legal or regulatory advice, and using it does not create any professional or client relationship.
- Safety. Work on series circuits, constant current regulators (CCRs), isolating transformers, cables, connectors and lighting equipment can be fatal. Always apply the aerodrome’s permit-to-work and isolation/LOTO procedures, prove dead, use correctly rated instruments and PPE, and follow the manufacturer’s instructions. Nothing here authorises work on live equipment or the bypassing of any safety device or interlock.
- Aviation operations. Nothing here authorises installation, modification, energisation, adjustment, return to service, a change of operating category (CAT I/II/III), a NOTAM or any aerodrome certification or approval decision. These rest with the aerodrome operator, the air navigation service provider and the competent regulator.
- Specifications, ratings and typical values. Descriptions, parameters, ratings, dimensions, photometric values, wattages, service lives, maintenance tasks and intervals, failure modes, certifications (for example CE, FCC, UL or IEC marks) and part or type designations are general, typical and indicative. They may not match any particular product, make, model or version, and they are not a datasheet, design, specification, selection, sizing, procurement or acceptance criterion. The manufacturer’s current documents, the approved design and the project specification prevail.
- Standards and regulations. References to ICAO, FAA, IEC, IEEE, ISO, BIS, DGCA and other standards are paraphrased summaries for orientation only. They may be incomplete or out of date, and standards are revised from time to time. Consult the current official editions. Following this content does not guarantee compliance with any law, standard or regulatory approval, and the regulator’s requirements always prevail.
- No warranty. Content is provided “as is” and “as available”, without warranty of any kind, express or implied, including accuracy, completeness, currency or fitness for a particular purpose. Real installations differ in design, equipment make and model, age and condition.
- Limitation of liability. To the fullest extent permitted by applicable law, Precision AGL Academy, Precision AGL Solutions and their owners, authors and contributors are not liable for any injury, death, loss, damage, downtime, penalty or regulatory consequence, whether direct or indirect, arising from the use of, reliance on, or inability to use this content. Nothing in this notice excludes or limits any liability that cannot lawfully be excluded or limited.
- Independence, brands and no endorsement. This is an independent publication. It is not affiliated with, sponsored by or endorsed by ICAO, the FAA, the IEC, DGCA, AAI, any airport, regulator, supplier or equipment manufacturer. Third-party names, product designations, standard designations and trademarks (including Megger®, Siemens, Eaton, Crouse-Hinds, ADB SAFEGATE, Fluke, ABB and Honeywell) belong to their respective owners and are used only for identification and description. Mention of a brand, product or supplier is not a recommendation, and we do not sell, supply or quote for any component described.
- Images and third-party content. Images and illustrations are shown to help identify the type of component. They may show products of various manufacturers, may not depict the exact item described, and are not a statement about any product’s quality, approval or performance. Copyright and trademarks in third-party images, logos and photographs belong to their respective owners and are not claimed as ours. If you are a rights holder and want an image removed, replaced or credited, email precisionaglsolutions@gmail.com with the page address and we will act promptly.
- Training and services. Mentions of training, courses, consultation, advice, selection, installation, calibration or other support, including the “Learn…Certify” pathway, describe learning stages and are not an offer, quotation, tender or promise of any result. Contacting us or our replying creates no engagement or duty of care; an engagement exists only under a written agreement. We are not a regulator or certification body, and completing any course or reading this content is not a certification, accreditation or authorisation to work on any aerodrome.
- Copyright, privacy and corrections. © 2026 Precision AGL Academy. All rights reserved. Text, structure, compilations and diagrams may be viewed for personal reference and internal training only; any other copying, republication or commercial use needs our written permission. If you email, telephone or message us, we use your details only to respond and handle your matter, in line with applicable Indian law including the Digital Personal Data Protection Act, 2023; please do not send confidential or security-sensitive information. To display this page your browser requests fonts, icons and images from third-party servers, which receive your IP address and browser details under their own policies. Content is reviewed periodically with no obligation to update. To report an error, safety concern or rights issue, write to precisionaglsolutions@gmail.com.