Base Can
A rugged, cylindrical steel enclosure embedded in the pavement that serves as the primary foundation for elevated AGL fixtures. It houses the isolating transformer, cable connections, and provides a stable, level mounting platform for the fixture's base plate, ensuring long‑term reliability under heavy aircraft loads and harsh environmental conditions.
Image disclaimer: For identification and illustration only. It may show a product by another manufacturer and may not depict the exact item described; it is not a statement of any product’s quality, approval or performance. Third-party image and trademark rights belong to their owners. See full notice.
What Is It?
A Base Can (also known as a transformer can, fixture base, or ground can) is a heavy‑duty cylindrical steel housing that is embedded in the pavement (concrete or asphalt) to provide a robust foundation for elevated AGL light fixtures. It serves as the primary structural and protective enclosure for the isolating transformer, cable terminations, and connector interfaces that power the fixture. Base cans are supplied in two distinct load classes that are not interchangeable: FAA Type L-867 is rated for occasional light vehicular traffic only and must never be installed where it could see aircraft wheel loads, while Type L-868 is load-bearing and rated for direct aircraft traffic. Selecting the wrong class for a given location — for example, an L-867 can where an aircraft excursion or routine taxi could load it — is a genuine safety defect, not just a spec mismatch.
Key characteristics of base cans include:
- Robust Construction: Made from high‑strength steel (typically hot‑dip galvanised or stainless) to withstand heavy aircraft loads, impact, and corrosion.
- Watertight Design: Sealed to prevent moisture ingress, with gasketed lids and cable entry points.
- Integrated Mounting: Includes a top flange or threaded holes for attaching the fixture's base plate, and internal brackets for securing the isolating transformer.
- Cable Management: Provides internal space for primary and secondary cable connections, with cable glands or conduits for entry and exit.
Base cans are designated L-867 (light-duty, for locations subject only to occasional light vehicular loads — not aircraft or heavy vehicle traffic) or L-868 (heavy-duty, rated for aircraft and heavy vehicular loads). Both types support elevated fixtures; the choice depends on the load the installation location will see, not on whether the fixture is elevated or inset — flush-mounted inset fixtures use their own in-pavement fixture housings (e.g. the L-850 series) rather than an L-867/L-868 base can. Base cans are typically installed during pavement construction or retrofitted into existing pavement, and are available in various diameters (typically 150mm to 300mm) and depths (200mm to 500mm) to accommodate different transformer sizes and cable configurations.
Purpose & Function
The parts of an elevated fixture most likely to actually fail — the isolating transformer and the cable terminations — are also the parts least able to tolerate water, dirt, or physical disturbance. The base can's purpose is to give those components a dedicated, protected space below the pavement surface, separated from both the aircraft loading experienced above and the surrounding soil and groundwater. It also fixes the fixture's exact position and height before the fixture is even installed, so the frangible pole or base plate that sits on top of it starts from a known, level, and correctly located reference point rather than relying on field adjustment. In effect, the base can turns "install a light fixture in a runway" into two separable jobs — a below-grade electrical and structural foundation, and an above-grade optical fixture — that can be built, sealed, and maintained independently of each other.
Where Is It Used?
Base cans are used wherever elevated AGL fixtures are installed on paved surfaces, including:
- Runway Edge Lighting: For elevated runway edge light fixtures, especially on curves, intersections, or where flush mounting is not feasible.
- Taxiway Edge Lighting: For elevated taxiway edge lights, particularly on curves and at intersections.
- Approach Lighting: For elevated approach light fixtures, barrettes, and flashing light units.
- Obstruction Lighting: For elevated obstruction lights on poles or structures.
- Airfield Signage: For elevated mandatory instruction signs and direction signs that require a stable foundation.
- Sensor Mounting: For anemometers, wind cones, and other instrumentation that requires a raised mounting.
The base can is designed to be installed flush with or slightly above the pavement surface, with a removable top cover that allows access to the transformer and connections for maintenance. The can's internal volume is sized to accommodate the isolating transformer, cable splices, and any necessary connectors, while maintaining adequate clearance for heat dissipation.
Installation & Location
The base can is set into a formed or cored foundation pit at the fixture's surveyed position, with its top rim set flush with or at the specified height above finished grade depending on whether the installation is elevated or inset. Backfill around the can is compacted in layers to prevent later settlement, which would otherwise leave the can proud of or sunk below grade; cable entry to the can is made through a sealed gland or knockout kept below any water table in the surrounding backfill where possible. Can position and level are checked against the pavement or shoulder survey before backfilling, since a can set at the wrong height is far more disruptive to correct once the surrounding pavement or turf is finished.
How Does It Work?
The base can functions as a combined structural foundation, protective enclosure, and cable management hub for the elevated fixture. Its design ensures that the fixture is securely mounted, electrically connected, and protected from the environment:
- Structural Support: The can is embedded in the pavement with a concrete or asphalt surround, providing a rigid, stable base that can withstand the dynamic loads from aircraft, snowploughs, and maintenance vehicles.
- Transformer Housing: The isolating transformer is mounted inside the can on a bracket or base plate, keeping it dry and protected from mechanical damage. The secondary cable runs from the transformer to the fixture, while the primary cable enters the can through a cable gland or conduit.
- Weatherproofing: A gasketed lid or cover plate seals the top of the can, preventing water, de‑icing fluids, and debris from entering. Cable entry points are also sealed with glands or compound to maintain a watertight seal.
- Accessibility: The top cover can be removed for maintenance, allowing technicians to access the transformer, cables, and connections without disturbing the pavement.
- Frangible Feature (if applicable): In some designs, the base can includes a frangible coupling or break‑away flange that allows the fixture to shear off on impact, minimising aircraft damage.
The installation process typically involves:
- Excavation: A hole is dug in the pavement to the required depth and diameter.
- Placement: The base can is positioned in the hole, levelled, and secured with a concrete or asphalt surround.
- Wiring: The primary cable is routed into the can, and the isolating transformer is connected. The secondary cable is routed from the transformer to the fixture location.
- Fixture Mounting: The fixture's base plate is bolted to the top flange of the can, and the fixture is installed.
- Sealing: The lid is installed and sealed to prevent water ingress.
The base can is designed to provide a service life of 20+ years, with regular inspection of the seal, cables, and transformer condition.
Installation sequence, from bare pavement to sealed, serviceable fixture base
1Excavation
Hole dug to the required depth and diameter
2Placement
Base can positioned, levelled, and secured with a concrete or asphalt surround
3Wiring
Primary cable routed in and connected to the isolating transformer; secondary cable routed on to the fixture location
4Fixture Mounting
Fixture's base plate bolted to the can's top flange
5Sealing
Lid installed and gasketed to prevent water ingress
20+ Year Service Life
Maintained by periodic inspection of the seal, cables, and transformer condition
System Architecture & Control Logic
The base can is the one point in the installation where the electrical and mechanical sides of the architecture physically meet. The series circuit cable arrives from the trench and terminates inside it, generally at the isolating transformer housed in the same can; at the same time, the can itself bolts down onto the anchor bolts and carries the structural load of whatever sits above it — a frangible coupling and elevated fixture, or an inset fixture seated directly in it. Because both the power connection and the mechanical foundation converge at this one component, a base can problem can present as either an electrical fault (a wet or failed transformer) or a mechanical one (a loose or corroded mounting), and diagnosing which requires opening the can rather than reading a single status from either the ALCMS or a structural inspection alone.
Electrical and mechanical architectures converge in one component — a fault here can be either kind, or both.
Physical Construction
A base can is fabricated from structural steel plate, rolled and welded into a cylindrical body, then hot-dip galvanised or specified in stainless steel for installations demanding higher corrosion resistance. The top of the can terminates in a welded flange or ring, machined or drilled with a bolt pattern matched to the fixture's base plate, so the fixture bolts directly onto the can once it is set into the pavement. A removable steel lid, gasketed with a neoprene or rubber seal and secured with bolts or quick-release clamps, closes the top opening around the fixture base, keeping the transformer and connector compartment inside protected from surface water while still allowing access for maintenance. Cable entries, typically two to four gland or conduit fittings, are welded or threaded into the can's side wall below grade, sized to accept the incoming and outgoing series circuit cables with a sealed, strain-relieved connection. The can's wall thickness and overall structural design are engineered to support the vertical load of the fixture above and the surrounding pavement load without deforming, while its buried depth and diameter are matched to the isolating transformer and connector hardware it houses.
Technical Parameters
| Parameter | Typical Value |
|---|---|
| Material | Structural steel (S235JR or S355JR), hot‑dip galvanised (min 85µm) or stainless steel (316L) |
| Diameter (internal) | 150mm to 300mm (6" to 12") |
| Depth | 200mm to 500mm (8" to 20") – varies by transformer size |
| Wall Thickness | 4mm to 8mm |
| Top Flange | Bolted ring with threaded holes for fixture base plate (M10 to M16) |
| Lid Type | Removable steel lid with neoprene gasket, secured with bolts or quick‑release clamps |
| Cable Entry | 2 to 4 cable glands (PG or metric) or conduit entries |
| Load Capacity (vertical) — L-867 | Light vehicular traffic only — not rated for aircraft wheel loads |
| Load Capacity (vertical) — L-868 | Load-bearing, ≥ 50 kN (depending on size), rated for direct aircraft traffic |
| IP Rating (with lid) | IP67 / IP68 (submersible) |
| Corrosion Resistance | ≥ 500 hours salt spray (galvanised); ≥ 1000 hours (stainless) |
| Operating Temperature | -40°C to +85°C |
| Standards | FAA AC 150/5345‑42, ICAO Annex 14, EN 10025, ASTM A123 |
Applicable Standards
FAA AC 150/5345‑42
Specification for Airport Light Bases, Transformer Housings, Junction Boxes, and Accessories (L-867/L-868 base cans)
ICAO Annex 14
Physical characteristics of AGL mounting structures and enclosures
EN 10025
Hot‑rolled products of structural steels (material specification)
ASTM A123
Standard specification for zinc (hot‑dip galvanised) coatings on iron and steel products
Installation Requirements
Excavation & Buried Depth
CivilExcavate to the can's specified buried depth and diameter, matched to the isolating transformer and connector hardware it will house, before backfilling around it.
Flush & Level Setting
CivilSet the top flange flush with the surrounding pavement and dead level, so the fixture's base plate seats true once bolted on.
Cable Entry Alignment
ElectricalAlign the can's cable gland or conduit entries with the incoming and outgoing duct runs before backfill, sized for a sealed, strain-relieved connection.
Load Path & Compaction
CivilCompact backfill evenly around the can so it supports the vertical load of the fixture above and the surrounding pavement load without deforming or settling.
Top Flange Bolt Pattern Match
MechanicalConfirm the flange's bolt pattern matches the fixture's base plate before setting the can, since this is fixed once the can is buried.
Lid Gasket & Closure
MechanicalConfirm the lid's neoprene gasket seats correctly and the bolts or quick-release clamps close fully, since this is what keeps the transformer and connector compartment protected from surface water.
Pre-Backfill Sign-off
DocumentationRecord can position, depth, and cable entry alignment as-built before final backfill, since these are not inspectable once the site is closed.
Testing & Commissioning
Dimensional & Bolt Pattern Verification
Pre-InstallationConfirm the can's diameter, depth, and top flange bolt pattern match the fixture's base plate before it is set into the pavement cut-out.
Watertightness/IP Rating Test
Pre-InstallationVerify the lid gasket seals correctly and the can meets its rated IP67/IP68 protection with a pressure or immersion check before backfill.
Cable Gland Sealing Check
InstallationConfirm each cable gland or conduit entry is correctly sealed and strain-relieved around the incoming and outgoing series circuit cables.
Load Capacity Verification
Pre-InstallationConfirm the can's rated vertical load capacity meets the design requirement for the fixture and pavement loading it will support.
Corrosion Coating Inspection
Pre-InstallationVerify galvanised or stainless finish is free of coating damage from handling or welding before the can is buried.
Grounding/Earth Continuity Check
InstallationConfirm the can body is bonded to the site earthing system with continuity within the acceptable resistance limit.
Documentation & Sign-off
Final AcceptanceRecord dimensional checks, seal verification, and earth continuity results against the installation location in the commissioning dossier.
Inspection & Maintenance
Lid Gasket Inspection
AnnualCheck the neoprene lid gasket for compression set or cracking, and confirm bolts or quick-release clamps still seat the lid tightly enough to hold the IP67/IP68 rating.
Internal Moisture / Debris Check
AnnualOpen the can and check for standing water, silt, or debris that may have entered through the lid seal or cable glands.
Cable Gland / Entry Inspection
AnnualInspect each cable gland or conduit entry for a secure seal, since this is the most common route for moisture ingress into the can.
Top Flange & Bolt Condition
AnnualCheck the top flange threaded holes and fixture mounting bolts for corrosion or thread damage that could compromise the fixture connection.
Corrosion Check
AnnualInspect galvanised or stainless can walls, inside and out, for coating breakdown or pitting, particularly near the base where moisture pools.
Insulation Resistance Test
AnnualMegger-test cable terminations inside the can to confirm insulation resistance remains above minimum, catching moisture ingress before it causes a series-circuit fault.
Drainage Check
AnnualConfirm any drainage provision at the base of the can is clear, and that surrounding soil or pavement grading directs water away from the unit.
Load Capacity / Structural Check
AnnualInspect for wall deformation or cracking that could reduce the can's rated ≥50 kN vertical load capacity, particularly on cans under trafficked pavement.
Common Field Issues
Water Ingress Through Lid Seal
The lid gasket can deteriorate over time, allowing water and de‑icing fluids to enter the can, causing corrosion of the transformer and cables. Regularly inspect and replace the gasket. Use a silicone‑based sealant on the lid bolts.
Corrosion of Can Interior
Condensation or water ingress can cause internal corrosion, compromising the structural integrity. Use stainless steel or galvanised cans, and consider installing a desiccant or moisture‑absorbing pack inside the can.
Damaged Cable Glands
Cable glands can be damaged during installation or by movement of the pavement, allowing water ingress. Use heavy‑duty glands and check them periodically for tightness and seal integrity.
Insufficient Depth for Transformer
If the base can is too shallow, the isolating transformer may not fit, or may be too close to the lid, causing overheating. Verify the transformer dimensions and select a can with adequate depth and ventilation.
Loose Fixture Bolts
Vibration from aircraft can loosen the fixture‑to‑can bolts, affecting alignment and safety. Use lock washers and thread‑locking compound, and schedule regular bolt torque checks.
Pavement Settlement Around Can
Settlement of the surrounding pavement can cause the can to tilt or sink, misaligning the fixture. Ensure proper compaction of the backfill and consider using a concrete collar to prevent settlement.
Rodent Infestation
Rodents can enter the can through cable entry points and damage insulation or chew cables. Use metal conduits, seal gaps with expanding foam, and consider installing rodent‑repellent materials.
Troubleshooting Guide
Fixture Dark, Water Found Inside Can on Excavation
Can Interior Shows Corrosion or Rust‑Through
Cable Gland Leaking or Cracked
Transformer Overheating or Fitment Too Tight
Fixture Loose or Misaligned Atop the Can
Can Tilted, Sunk, or Surrounding Pavement Cracked
Chewed Insulation or Signs of Rodent Entry
Failure Modes & Root Causes
Water Ingress Through Lid Seal
Corrosion of Can Interior
Damaged Cable Glands
Pavement Settlement Around the Can
Rodent Infestation
Insufficient Depth for Transformer
Safety & Operational Notes
Series Circuit Isolation
Electrical SafetyDe-energise and lock out the CCR feeding the circuit and verify zero energy at the isolating transformer and connectors before opening the base can lid.
Standing Water Shock Hazard
Electrical SafetyBase cans can accumulate groundwater; treat any water in the can as potentially energised until the circuit is confirmed isolated, and pump or drain before reaching in.
Lid & Housing Handling
Personnel SafetyUse proper lifting technique or lifting tools for the heavy steel lid and housing; a dropped lid or housing at an awkward angle is a crush and pinch-point hazard.
Airside Work Coordination
OperationalCoordinate with ATC/airside and raise a NOTAM where the fixture served by the base can will be dark, and never leave an open base can unattended on the movement area.
FOD Control
OperationalKeep tools, fasteners, and gaskets accounted for while the can is open, and secure or remove loose material before refitting the lid.
Insulation Test Before Re-Energisation
Electrical SafetyMegger test the circuit after any transformer or connector work inside the can before restoring power, since a residual fault can trip the CCR or damage healthy fixtures on the same loop.
Restore Seal & Load Rating
ComplianceConfirm the lid is correctly seated, gasketed, and rated for the traffic loading of its location before reopening the area, and verify the can hasn't shifted or settled out of level.
Airport Light Base Can
An airport light base can is the cylindrical housing set into the pavement or ground that supports an elevated or inset light and holds the transformer and connections beneath it. The right load class (L-867 or L-868) must be used for the location. After installation, check that the base can is level, correctly set to height, sealed, and that its cable entries are watertight, because a poorly set base can causes tilted lights and water ingress.
Engineering & Expert Notes
A Watertight Seal Only Works if the Gasket Is Actually Inspected
DurabilityBase can watertightness depends entirely on gasket condition at the lid and cable entries; a gasket that's compressed, cracked, or displaced defeats the can's protective function even though the can itself looks structurally fine. Include gasket condition in every scheduled inspection, not just when moisture ingress is already suspected.
Isolating Transformer Access Shouldn't Compromise the Seal
ElectricalFrequent transformer access for testing or replacement stresses the lid seal and cable gland seals over time; re-seat and verify seals properly after every access rather than assuming a quick re-close is sufficient.
Galvanised Cans Corrode From the Inside Out When Drainage Fails
CorrosionIf the can's drainage path is blocked or was never properly graded, water accumulates inside where galvanising is often thinnest at weld seams, corroding the can from the inside before any external sign appears. Verify internal drainage is clear during every service visit.
Verify Load Rating Matches Actual Pavement Traffic, Not Just Design Category
MechanicalA base can rated for the pavement's design traffic category can still be under-specified if actual traffic (de-icing vehicles, snow removal equipment) exceeds what was assumed at design time. Confirm the installed can's load rating against actual observed traffic, especially after any change in ground vehicle operations near the location.
Can Tilt Transfers Directly to Fixture Aim
AlignmentBecause the can is the foundation the entire fixture assembly sits on, even minor can tilt from installation error or ground movement propagates directly into fixture misalignment above it. Verify can level as part of any alignment troubleshooting, not just the visible fixture.
Confirm Zero Energy Before Opening, Even on a 'De-Energised' Circuit
SafetyIsolating transformers can retain induced or residual voltage briefly after de-energisation; verify zero energy with a meter at the can before handling internal connections, regardless of confirmation that the loop breaker is open.
Frequently Asked Questions
Short answers about the base can: what it is, how it works, specifications, standards, maintenance and common faults.
Q1What is a base can?
A base can (also called a transformer can, fixture base or ground can) is a heavy-duty cylindrical steel housing embedded in the pavement. It is the structural and protective enclosure for the isolating transformer, cable terminations and connector interfaces that power an elevated AGL fixture.
Q2What is the difference between L-867 and L-868 base cans?
They are two load classes that are not interchangeable. FAA Type L-867 is rated for occasional light vehicular traffic only and must never be installed where it could see aircraft wheel loads. Type L-868 is load-bearing and rated for direct aircraft traffic. Using the wrong class is a genuine safety defect.
Q3Where are base cans used?
They are used wherever elevated AGL fixtures are installed on paved surfaces: runway edge lighting (especially on curves and intersections), taxiway edge lighting, approach lighting and obstruction lighting.
Q4What sizes and materials are typical?
Internal diameter is typically 150 mm to 300 mm, depth 200 mm to 500 mm depending on transformer size, and wall thickness 4 mm to 8 mm. Material is structural steel (S235JR or S355JR) hot-dip galvanised to at least 85 µm, or 316L stainless steel.
Q5How is a base can sealed?
It has a removable steel lid with a neoprene gasket secured by bolts or quick-release clamps, and 2 to 4 cable glands or conduit entries. With the lid fitted, the typical rating is IP67 or IP68 (submersible).
Q6What load can a base can carry?
An L-868 can is load-bearing, typically at least 50 kN depending on size, and rated for direct aircraft traffic. An L-867 can is for light vehicular traffic only and is not rated for aircraft wheel loads.
Q7Which standards apply to base cans?
The main references are FAA AC 150/5345-42 (L-867 and L-868 base cans), ICAO Annex 14, EN 10025 for structural steel and ASTM A123 for hot-dip galvanised coatings. Always verify the current edition and your aerodrome's approved requirements.
Q8How often should a base can be inspected?
Typical annual checks cover the lid gasket, internal moisture and debris, cable glands and entries, top flange and bolts, corrosion, insulation resistance, drainage and load and structural condition. Your airport's approved maintenance programme takes precedence.
Q9Why is there water inside a base can?
The most common route is water ingress through a failed lid seal. Damaged cable glands and inadequate drainage also contribute, and water inside the can is a typical cause of a dark fixture. Inspect the gasket, glands and drainage path, and test insulation resistance.
Q10What are the common problems with base cans?
Common problems are water ingress through the lid seal, corrosion of the can interior, damaged cable glands, insufficient depth for the transformer, loose fixture bolts, pavement settlement around the can and rodent infestation.
Related Components
Go Beyond the Component. Understand the Complete AGL System.
You have explored the component. Now understand how it works within the complete Airfield Ground Lighting system.
Learn AGL from fundamentals to design, installation, testing, photometry, commissioning, maintenance and troubleshooting through structured technical training at Precision AGL Academy.
Build practical knowledge. Understand the circuit. Read the standards. Troubleshoot with confidence.
Your next step in AGL starts here.
Need expert guidance on base can selection and installation for your AGL project?
Precision AGL Academy provides advice on size selection, corrosion protection, sealing, and transformer mounting for reliable elevated fixture foundations.
Follow the Academy
Important Notice, Disclaimer & Limitation of Liability
Please read before relying on any content on this page.
- Purpose and intended users. This page on Base Can is an independent educational and informational reference for competent, suitably trained and authorised airfield ground lighting (AGL) and aerodrome electrical personnel. It is not professional engineering, legal or regulatory advice, and using it does not create any professional or client relationship.
- Safety. Work on series circuits, constant current regulators (CCRs), isolating transformers, cables, connectors and lighting equipment can be fatal. Always apply the aerodrome’s permit-to-work and isolation/LOTO procedures, prove dead, use correctly rated instruments and PPE, and follow the manufacturer’s instructions. Nothing here authorises work on live equipment or the bypassing of any safety device or interlock.
- Aviation operations. Nothing here authorises installation, modification, energisation, adjustment, return to service, a change of operating category (CAT I/II/III), a NOTAM or any aerodrome certification or approval decision. These rest with the aerodrome operator, the air navigation service provider and the competent regulator.
- Specifications, ratings and typical values. Descriptions, parameters, ratings, dimensions, photometric values, wattages, service lives, maintenance tasks and intervals, failure modes, certifications (for example CE, FCC, UL or IEC marks) and part or type designations are general, typical and indicative. They may not match any particular product, make, model or version, and they are not a datasheet, design, specification, selection, sizing, procurement or acceptance criterion. The manufacturer’s current documents, the approved design and the project specification prevail.
- Standards and regulations. References to ICAO, FAA, IEC, IEEE, ISO, BIS, DGCA and other standards are paraphrased summaries for orientation only. They may be incomplete or out of date, and standards are revised from time to time. Consult the current official editions. Following this content does not guarantee compliance with any law, standard or regulatory approval, and the regulator’s requirements always prevail.
- No warranty. Content is provided “as is” and “as available”, without warranty of any kind, express or implied, including accuracy, completeness, currency or fitness for a particular purpose. Real installations differ in design, equipment make and model, age and condition.
- Limitation of liability. To the fullest extent permitted by applicable law, Precision AGL Academy, Precision AGL Solutions and their owners, authors and contributors are not liable for any injury, death, loss, damage, downtime, penalty or regulatory consequence, whether direct or indirect, arising from the use of, reliance on, or inability to use this content. Nothing in this notice excludes or limits any liability that cannot lawfully be excluded or limited.
- Independence, brands and no endorsement. This is an independent publication. It is not affiliated with, sponsored by or endorsed by ICAO, the FAA, the IEC, DGCA, AAI, any airport, regulator, supplier or equipment manufacturer. Third-party names, product designations, standard designations and trademarks (including Megger®, Siemens, Eaton, Crouse-Hinds, ADB SAFEGATE, Fluke, ABB and Honeywell) belong to their respective owners and are used only for identification and description. Mention of a brand, product or supplier is not a recommendation, and we do not sell, supply or quote for any component described.
- Images and third-party content. Images and illustrations are shown to help identify the type of component. They may show products of various manufacturers, may not depict the exact item described, and are not a statement about any product’s quality, approval or performance. Copyright and trademarks in third-party images, logos and photographs belong to their respective owners and are not claimed as ours. If you are a rights holder and want an image removed, replaced or credited, email precisionaglsolutions@gmail.com with the page address and we will act promptly.
- Training and services. Mentions of training, courses, consultation, advice, selection, installation, calibration or other support, including the “Learn…Certify” pathway, describe learning stages and are not an offer, quotation, tender or promise of any result. Contacting us or our replying creates no engagement or duty of care; an engagement exists only under a written agreement. We are not a regulator or certification body, and completing any course or reading this content is not a certification, accreditation or authorisation to work on any aerodrome.
- Copyright, privacy and corrections. © 2026 Precision AGL Academy. All rights reserved. Text, structure, compilations and diagrams may be viewed for personal reference and internal training only; any other copying, republication or commercial use needs our written permission. If you email, telephone or message us, we use your details only to respond and handle your matter, in line with applicable Indian law including the Digital Personal Data Protection Act, 2023; please do not send confidential or security-sensitive information. To display this page your browser requests fonts, icons and images from third-party servers, which receive your IP address and browser details under their own policies. Content is reviewed periodically with no obligation to update. To report an error, safety concern or rights issue, write to precisionaglsolutions@gmail.com.