Cable Lug
A copper or aluminium termination device used to securely connect cable conductors to bus bars, transformers, earth bars, and other equipment in AGL power distribution systems. Available in crimp, solder, and bolted variants, it ensures low‑resistance, reliable electrical connections that withstand the harsh airfield environment.
Image disclaimer: For identification and illustration only. It may show a product by another manufacturer and may not depict the exact item described; it is not a statement of any product’s quality, approval or performance. Third-party image and trademark rights belong to their owners. See full notice.
What Is It?
A Cable Lug (also known as a cable terminal or termination lug) is a metallic connector used to terminate the end of a cable conductor, providing a secure interface for bolting, soldering, or crimping to a bus bar, terminal block, isolating transformer, earthing system, or other electrical equipment. In airfield ground lighting (AGL) systems, cable lugs are essential for creating reliable, low‑resistance connections in both primary and secondary circuits.
Cable lugs are typically manufactured from high‑conductivity copper (tinned or bare) or aluminium, and are designed to match the conductor size and termination method. They feature a barrel for cable insertion (which is crimped or soldered) and a flat tongue or pad with a hole for bolting to the equipment. They are available in a wide range of sizes, configurations, and plating options to suit the diverse requirements of AGL installations, including compatibility with copper, aluminium, and bi‑metallic connections.
Purpose & Function
A cable lug's purpose is to preserve the conductor's own low resistance all the way through the point where it ends and bolts to something else, a transition that would otherwise be the weakest link in the circuit. A crimped or soldered lug creates a gas-tight, high-surface-area joint between the stranded conductor and the terminal pad, so that current can cross the interface without concentrating heat at any single strand. Getting the metal pairing right, matching copper to copper or using a bi-metallic lug where copper meets aluminium, matters because a poorly matched termination corrodes over time through galvanic action, gradually raising resistance at exactly the point where a failure is hardest to spot during a routine visual inspection.
Where Is It Used?
Cable lugs are used throughout the airfield wherever cable terminations are required, including:
- CCR Output Terminals: Terminating primary cables at the output of Constant Current Regulators (CCRs) using heavy‑duty lugs.
- Isolating Transformer Connections: Connecting secondary cables from the transformer to the light fixture or sign.
- Earthing and Bonding: Terminating bare copper earth cables to earth pits, earth electrodes, and equipment grounding points.
- Distribution Panels: Terminating incoming and outgoing cables at terminal blocks and bus bars in junction boxes and distribution panels.
- Receptacle and Connector Wiring: Connecting wires inside L‑823 connectors and other primary/secondary connectors.
- Fixture Wiring: Internal wiring inside light fixtures, signs, and beacons, connecting the transformer secondary to the lamp or LED driver.
The lug is selected based on the cable size (conductor cross‑section), material (copper or aluminium), termination method (crimp, solder, or bolt), and the equipment interface (stud size, orientation, and plating). Proper selection and installation are critical for maintaining low contact resistance and preventing overheating or failure.
Installation & Location
The lug is installed at the point where a cable conductor terminates — a CCR output stud, transformer terminal, earth bar, or terminal block — with the conductor stripped to the length specified for the barrel and crimped (or soldered) using tooling and a die matched to the lug and conductor size, since an incorrect crimp is one of the more common causes of a high-resistance joint. The lug's tongue is then bolted to its terminal pad at the torque specified for the stud size and plating, with a flat washer and, where dissimilar metals meet, an anti-oxidant compound or bi-metallic barrier used to limit corrosion. Sufficient cable slack is left on the approach to the lug so the termination isn't placed under mechanical strain, and lugs used outdoors or below grade are generally covered with heat-shrink or a boot to keep moisture off the crimped joint. Positioning keeps the finished termination clear of adjacent live parts and accessible for the periodic resistance or thermal checks used to catch a degrading connection before it fails.
How Does It Work?
A cable lug provides a secure, low‑resistance electrical termination for a cable conductor. Its design and installation ensure a reliable connection that can carry the required current without excessive heating or voltage drop. The typical functional elements include:
- Cable Barrel: A cylindrical section that accepts the stripped conductor. The barrel is crimped (using a hex‑shaped or indenting crimp tool) or soldered to the conductor, creating a gas‑tight, low‑resistance joint. For aluminium conductors, the barrel may be filled with a corrosion‑inhibiting compound.
- Flat Tongue/Pad: A flattened section with a hole for bolting to the equipment. The hole size matches the stud or bolt diameter, and the pad provides a large surface area for low contact resistance and mechanical strength.
- Plating: Copper lugs are often tin‑plated to resist corrosion and prevent oxidation, which can increase resistance. Silver or nickel plating is used for high‑temperature or high‑reliability applications. Aluminium lugs are typically unplated but may be coated with a protective layer.
- Insulation (optional): Some lugs are supplied with a pre‑moulded insulating sleeve or can be fitted with heat‑shrink tubing after termination to provide electrical insulation and moisture sealing.
- Bi‑Metallic Design (optional): For connecting aluminium cables to copper bus bars, bi‑metallic lugs are used to prevent galvanic corrosion. These lugs have an aluminium barrel and a copper tongue, welded or friction‑welded together.
When properly installed with the correct crimping tool and torque, a cable lug connection can carry its rated current indefinitely with minimal resistance, ensuring the integrity and reliability of the AGL circuit.
System Architecture & Control Logic
A cable lug is a termination point in the series circuit loop — typically where the primary cable meets an isolating transformer tail, a CCR output terminal, or a bus bar — and it carries the full loop current at that junction. Like every other passive element in the loop, it is not individually addressable and generates no signal of its own; the ALCMS and CCR only see the loop as a whole. A correctly crimped lug adds negligible resistance and is electrically transparent to the control system. Over time, however, a loose bolt, a poorly crimped barrel, or galvanic corrosion at a mismatched metal pairing increases contact resistance at that single point, and because the CCR regulates current rather than voltage per node, that added resistance shows up as a rise in overall loop voltage at the commanded current step rather than as a fault flagged at the terminal itself. In more severe cases the termination heats under load, accelerating its own degradation, until the connection opens entirely and the CCR reports a standard open-circuit loop fault — again with no indication of which of the loop's many terminations caused it until the loop is sectionalised and each termination is checked in the field.
ALCMS → CCR → Series Circuit Loop → Cable Lug (termination) → Transformer / Bus Bar (with loop-level feedback)
Metal Compatibility at the Termination
Conductor & Bus Bar Metals Identified
Copper, aluminium, or a mix of the two at the termination point
Standard Lug Used
Homogeneous metal-to-metal contact throughout the joint
Stable Long-Term Resistance
No dissimilar-metal reaction to degrade the connection
Standard Lug Used in Error
Aluminium and copper placed in direct contact
Galvanic Corrosion, Rising Resistance
Joint resistance climbs over time and can eventually fail
Bi-Metallic Lugs (Aluminium Barrel + Copper Tongue) Exist Specifically to Prevent This Failure When Aluminium and Copper Must Meet
Physical Construction
A cable lug is a two‑part shape formed from a single piece of metal: a hollow barrel at one end, sized to accept the stripped conductor, and a flat tongue or pad at the other, punched or drilled with a bolt hole for connection to the equipment terminal. The barrel is either crimped with a hydraulic or mechanical tool, which deforms the metal inward to grip the conductor strands and squeeze out air gaps, or soldered, where molten solder is drawn into the barrel to bond it to the conductor; some designs allow either method. Material and plating are matched to the conductor and connection type, with tinned copper used for corrosion resistance in earthing and general power applications, bare copper for pure copper‑to‑copper joints, and aluminium or bi‑metallic (copper‑aluminium transition) lugs specified wherever an aluminium conductor must terminate onto copper equipment, since a direct copper‑aluminium joint would otherwise corrode galvanically.
Technical Parameters
| Parameter | Typical Value |
|---|---|
| Material | Copper (EC grade, tinned or bare), Aluminium, or Bi‑metallic |
| Conductor Size Range | 1.5mm² to 300mm² (AWG 16 to 600 MCM) |
| Stud Hole Diameter | M4 to M20 (4mm to 20mm) or equivalent imperial sizes |
| Plating | Tin (standard), Silver, Nickel, or Bare copper |
| Barrel Type | Standard, deep, or long barrel (for double crimps) |
| Orientation | Straight, 45°, or 90° (right‑angle) |
| Termination Method | Crimp (hexagonal or indenting), solder, or bolted (compression) |
| Operating Temperature | -40°C to +105°C (tin‑plated); up to +200°C (silver‑plated) |
| Standards | IEC 61238‑1, UL 486A‑486B, FAA AC 150/5345‑53 |
Electrical Requirements
| Requirement | Typical Value |
|---|---|
| Circuit Position | Termination point at CCR, transformer, or earth bar (not in series loop itself) |
| Rated Current (Continuous) | Sized to conductor cross-section (e.g. 6mm²–16mm² for AGL primary/secondary) |
| Contact Resistance | ≤ 0.5 mΩ per properly crimped/bolted termination |
| Galvanic Compatibility | Match lug material to conductor (copper-to-copper or approved bi-metallic) to avoid corrosion |
| Torque (bolted connections) | Per manufacturer spec for stud size — under/over-torque both raise resistance |
| Insulation Clearance | Adequate creepage/clearance maintained at termination enclosure |
Applicable Standards
IEC 61238‑1
Compression and mechanical connectors for power cables — test methods and requirements
UL 486A‑486B
Standard for wire connectors and soldering lugs
FAA AC 150/5345‑53
Airport Lighting Equipment Certification Program (qualification listing for terminal/lug hardware)
Installation Requirements
Conductor Strip Length
FitStrip the conductor to the length specified for the lug's barrel before crimping, so the full barrel length grips conductor strands rather than insulation.
Matched Crimp Tooling & Die
FitCrimp or solder using tooling and a die matched to the lug and conductor size, since an incorrect crimp is one of the more common causes of a high-resistance joint.
Torque to Specification
FitBolt the lug's tongue to its terminal pad at the torque specified for the stud size and plating, with a flat washer fitted.
Dissimilar Metal Protection
FitFit an anti-oxidant compound or bi-metallic barrier where dissimilar metals meet, to limit galvanic corrosion at the joint.
Strain-Free Cable Slack
FitLeave sufficient cable slack on the approach to the lug so the termination isn't placed under mechanical strain.
Weather Protection
FitCover lugs used outdoors or below grade with heat-shrink or a boot to keep moisture off the crimped joint.
Pre-Energisation Sign-off
DocumentationRecord lug type, crimp method, and torque value achieved before the termination is closed up or buried, since these are not inspectable afterward.
Testing & Commissioning
Crimp Pull-Out (Tensile) Test
Pre-EnergisationPull-test a sample crimp from the same batch and die set to confirm it meets the minimum retention force before the lugs are put into service.
Contact Resistance (Micro-Ohm) Test
Pre-EnergisationMeasure resistance across each crimped lug with a micro-ohmmeter, flagging any joint above the acceptable threshold for re-crimping.
Crimp Dimension & Die Verification
Pre-EnergisationCheck crimp width or diameter against the manufacturer's chart to confirm the correct die and number of crimps were used for the conductor size.
Visual Inspection for Cracking or Voids
Pre-EnergisationInspect each lug barrel for cracking, incomplete crimps, or exposed strands before the connection is insulated or terminated.
Documentation & As-Built Sign-off
Final AcceptanceRecord crimp test results and micro-ohm readings alongside terminal locations in the commissioning dossier for handover.
Inspection & Maintenance
Bolted Connection Torque Check
AnnualRe-torque bolted lug connections to the manufacturer's specified value (typically 10-30 N·m for M6-M12 studs) to prevent arcing and overheating from loosened joints.
Corrosion & Anti-Oxidant Check
AnnualInspect for oxidation and reapply anti-oxidant compound, especially on untinned copper lugs in coastal or industrial environments.
Bi-Metallic Connection Check
AnnualVerify aluminium-to-copper connections use proper bi-metallic lugs and protective coating to rule out galvanic corrosion.
Thermal Imaging Scan
AnnualThermally scan lug connections under load to catch high-resistance joints before they overheat and fail.
Strain Relief Check
AnnualConfirm cable ties, clamps, or strain relief brackets near the termination are intact so mechanical stress doesn't fracture or pull out the lug.
Pull-Test Verification
At installPerform a pull-test on crimped connections immediately after crimping to confirm the connector is fully seated and secure.
Common Field Issues
Incorrect Lug Size Selection
Using a lug with a barrel that is too large or too small for the conductor will result in a poor crimp, high resistance, and potential overheating. Always match the lug's barrel size to the conductor cross‑section, and use the manufacturer's recommended crimping tool and die set.
Improper Crimping Technique
Under‑crimping or over‑crimping can cause a high‑resistance joint or damage the conductor. Use the correct die set, ensure full closure of the crimping tool, and perform a pull‑test to verify the connection. Follow the tool manufacturer's instructions.
Corrosion and Oxidation
Untinned copper lugs can oxidise over time, increasing resistance. In coastal or industrial environments, corrosion is accelerated. Use tin‑plated or silver‑plated lugs, apply anti‑oxidant compound, and ensure the connection is properly torqued to prevent moisture ingress.
Insufficient Torque on Bolted Connections
Loose bolted connections can cause arcing, overheating, and eventual failure. Use a torque wrench set to the manufacturer's specified value (typically 10‑30 N·m for M6‑M12 studs) and use lock washers or thread‑locking compound to prevent loosening.
Galvanic Corrosion (Bi‑Metallic Connections)
Connecting aluminium cables directly to copper bus bars without a bi‑metallic lug can cause galvanic corrosion. Always use bi‑metallic lugs for aluminium‑to‑copper connections and apply anti‑oxidant compound.
Inadequate Cable Stripping
Stripping too much or too little insulation from the cable can cause the conductor to enter the lug incorrectly, leading to a poor connection. Use the correct stripping tool and follow the manufacturer's strip length instructions.
Mechanical Stress on the Lug
If the cable is not properly supported, mechanical stress on the lug can cause it to fracture or pull out. Use cable ties, clamps, or strain relief brackets to support the cable near the termination point.
Troubleshooting Guide
Lug Runs Hot or Shows Discoloration in Service
Loose or Arcing Bolted Connection
Green or White Corrosion Product at the Lug
Lug Pulls Out or Fractures
Conductor Not Fully Seated in Barrel
Failure Modes & Root Causes
Incorrect Lug Size or Crimp
Loose Bolted Connection
Galvanic or Oxidation Corrosion
Inadequate Strain Relief
Incomplete Conductor Insertion
Safety & Operational Notes
De-Energise Before Terminating
Electrical SafetyNever crimp or bolt a lug onto a live series-circuit conductor; de-energise and lock out the CCR and verify zero energy before stripping or terminating cable.
Correct Tool, Die & Torque
WorkmanshipUse the crimp tool and die matched to the lug and conductor size, or torque bolted connections to the manufacturer's specified value; an incorrect crimp or under/over-torqued bolt is a common source of hot-spot failures.
Dissimilar Metal Connections
WorkmanshipNever join aluminium and copper conductors directly at a lug; use a bi-metallic lug and appropriate anti-oxidant compound to prevent galvanic corrosion at the joint.
Sharp Edge & Pinch Hazard
Personnel SafetyHandle lug barrels and crimping tools with care to avoid cuts or pinch injuries, and wear appropriate gloves suited to the crimping or bolting operation.
Verify Before Re-Energisation
Electrical SafetyCheck crimp integrity, torque, and conductor seating before restoring power; a marginal termination found after re-energisation can trip the CCR or damage healthy fixtures on the same circuit.
PPE & Grounding
Personnel SafetyUse insulated tools and appropriate PPE when working on series-circuit terminations, and confirm bonding/grounding is intact per the electrical design before reconnecting the loop.
Restore to Compliant State
ComplianceDo not leave a termination without adequate strain relief or with an unrecorded crimp/torque value; verify and document the connection before closing out the work.
Engineering & Expert Notes
Hot-Spot Failures Often Start as a Fine Crimp
DurabilityA technically-in-spec crimp made with a worn or slightly mismatched die can still pass initial resistance checks yet develop a hot spot months later as the crimp relaxes under thermal cycling; inspect and calibrate crimp dies on a schedule, not just when a failure prompts it.
Anti-Oxidant Compound Needs Reapplication, Not Just Presence
WorkmanshipAnti-oxidant compound on an aluminium lug can migrate or dry out if the connection sits open too long before final crimping; apply it as the last step before crimping, not early in the prep sequence.
Strip Length Errors Are Invisible After Crimping
WorkmanshipA conductor stripped too short leaves insulation trapped under the crimp barrel, while too long leaves bare copper exposed beyond it; both defects are hidden once the lug is crimped, so verify strip length against the lug's spec before crimping, not after.
Track Termination Resistance Over Successive Visits
TroubleshootingA marginally high-resistance termination often measures within tolerance at any single visit but trends upward across visits before it fails; logging resistance readings over time catches this pattern that a single spot-check cannot.
Match Lug Barrel Length to Conductor Stranding, Not Just Gauge
DesignFine-stranded and coarse-stranded conductors of the same nominal gauge can need different barrel lengths or crimp profiles to achieve full contact area; check the lug manufacturer's stranding chart rather than gauge alone.
Uninsulated Lugs Need Their Own Seal Plan
DurabilityA bolted, uninsulated lug connection buried or in a wet base can needs a separate moisture-exclusion method such as heat-shrink or a grease cap; the lug itself provides no seal, and assuming the enclosure alone is enough overlooks the connection's own corrosion risk.
Related Components
Frequently Asked Questions
Short answers about cable lugs: function, materials, bi-metallic use, torque, standards and maintenance.
Q1What is a cable lug?
A cable lug, also called a cable terminal or termination lug, is a metallic connector that terminates a cable conductor so it can be bolted, soldered or crimped to a bus bar, terminal block, isolating transformer, earthing system or other equipment. It has a barrel that takes the conductor and a flat tongue with a hole for bolting.
Q2What is the purpose of a cable lug in an AGL system?
It preserves the conductor's low resistance through the point where the cable ends and bolts to something else, which would otherwise be the weakest link. A crimped or soldered lug forms a gas-tight, high-surface-area joint so current crosses the interface without concentrating heat at individual strands.
Q3Where are cable lugs used in AGL?
At CCR output terminals, isolating transformer connections, earthing and bonding terminations, distribution panels and terminal blocks, wiring inside L-823 connectors, and internal wiring in light fixtures, signs and beacons.
Q4What are cable lugs made of?
Copper (EC grade, tinned or bare), aluminium, or bi-metallic. Copper lugs are often tin-plated to resist corrosion, with silver or nickel plating for high-temperature or high-reliability use. Tin-plated lugs are rated -40°C to +105°C and silver-plated up to +200°C.
Q5When do I need a bi-metallic lug?
When an aluminium cable connects to a copper bus bar or terminal. A bi-metallic lug has an aluminium barrel and a copper tongue, joined by welding or friction welding, to prevent galvanic corrosion. Joining aluminium and copper directly with a standard lug causes rising joint resistance over time.
Q6How do I select the right cable lug?
Match it to the conductor cross-section, material (copper or aluminium), termination method (crimp, solder or bolted) and the equipment interface (stud size, orientation and plating). Typical ranges are 1.5 mm² to 300 mm² conductors and M4 to M20 stud holes, with straight, 45° or 90° orientation.
Q7What torque and contact resistance should a lug termination have?
Contact resistance should be 0.5 mΩ or less per properly crimped or bolted termination. Bolted connections must be torqued to the manufacturer's value for the stud size (typically 10 to 30 N·m for M6 to M12 studs), since both under- and over-torque raise resistance.
Q8Which standards apply to cable lugs?
The main references are IEC 61238-1 (compression and mechanical connectors for power cables), UL 486A-486B (wire connectors and soldering lugs) and FAA AC 150/5345-53 (Airport Lighting Equipment Certification Program). Always verify the current edition.
Q9How often should lug connections be checked?
Annually: re-torque bolted connections, check corrosion and anti-oxidant compound, verify bi-metallic connections, thermally scan under load and check strain relief. Perform a pull-test on crimped connections immediately after crimping. Your airport's approved maintenance programme takes precedence.
Q10What causes a cable lug to overheat or fail?
The usual causes are the wrong lug size for the conductor, under- or over-crimping, insufficient torque on bolted joints, corrosion or oxidation of untinned copper, galvanic corrosion from unprotected aluminium-to-copper joints, incorrect stripping length, and mechanical stress from missing strain relief.
Go Beyond the Component. Understand the Complete AGL System.
You have explored the component. Now understand how it works within the complete Airfield Ground Lighting system.
Learn AGL from fundamentals to design, installation, testing, photometry, commissioning, maintenance and troubleshooting through structured technical training at Precision AGL Academy.
Build practical knowledge. Understand the circuit. Read the standards. Troubleshoot with confidence.
Your next step in AGL starts here.
Need expert guidance on cable lug selection and installation for your AGL project?
Precision AGL Academy provides advice on lug sizing, crimping techniques, torque specifications, and corrosion prevention for reliable cable terminations.
Follow the Academy
Important Notice, Disclaimer & Limitation of Liability
Please read before relying on any content on this page.
- Purpose and intended users. This page on Cable Lug is an independent educational and informational reference for competent, suitably trained and authorised airfield ground lighting (AGL) and aerodrome electrical personnel. It is not professional engineering, legal or regulatory advice, and using it does not create any professional or client relationship.
- Safety. Work on series circuits, constant current regulators (CCRs), isolating transformers, cables, connectors and lighting equipment can be fatal. Always apply the aerodrome’s permit-to-work and isolation/LOTO procedures, prove dead, use correctly rated instruments and PPE, and follow the manufacturer’s instructions. Nothing here authorises work on live equipment or the bypassing of any safety device or interlock.
- Aviation operations. Nothing here authorises installation, modification, energisation, adjustment, return to service, a change of operating category (CAT I/II/III), a NOTAM or any aerodrome certification or approval decision. These rest with the aerodrome operator, the air navigation service provider and the competent regulator.
- Specifications, ratings and typical values. Descriptions, parameters, ratings, dimensions, photometric values, wattages, service lives, maintenance tasks and intervals, failure modes, certifications (for example CE, FCC, UL or IEC marks) and part or type designations are general, typical and indicative. They may not match any particular product, make, model or version, and they are not a datasheet, design, specification, selection, sizing, procurement or acceptance criterion. The manufacturer’s current documents, the approved design and the project specification prevail.
- Standards and regulations. References to ICAO, FAA, IEC, IEEE, ISO, BIS, DGCA and other standards are paraphrased summaries for orientation only. They may be incomplete or out of date, and standards are revised from time to time. Consult the current official editions. Following this content does not guarantee compliance with any law, standard or regulatory approval, and the regulator’s requirements always prevail.
- No warranty. Content is provided “as is” and “as available”, without warranty of any kind, express or implied, including accuracy, completeness, currency or fitness for a particular purpose. Real installations differ in design, equipment make and model, age and condition.
- Limitation of liability. To the fullest extent permitted by applicable law, Precision AGL Academy, Precision AGL Solutions and their owners, authors and contributors are not liable for any injury, death, loss, damage, downtime, penalty or regulatory consequence, whether direct or indirect, arising from the use of, reliance on, or inability to use this content. Nothing in this notice excludes or limits any liability that cannot lawfully be excluded or limited.
- Independence, brands and no endorsement. This is an independent publication. It is not affiliated with, sponsored by or endorsed by ICAO, the FAA, the IEC, DGCA, AAI, any airport, regulator, supplier or equipment manufacturer. Third-party names, product designations, standard designations and trademarks (including Megger®, Siemens, Eaton, Crouse-Hinds, ADB SAFEGATE, Fluke, ABB and Honeywell) belong to their respective owners and are used only for identification and description. Mention of a brand, product or supplier is not a recommendation, and we do not sell, supply or quote for any component described.
- Images and third-party content. Images and illustrations are shown to help identify the type of component. They may show products of various manufacturers, may not depict the exact item described, and are not a statement about any product’s quality, approval or performance. Copyright and trademarks in third-party images, logos and photographs belong to their respective owners and are not claimed as ours. If you are a rights holder and want an image removed, replaced or credited, email precisionaglsolutions@gmail.com with the page address and we will act promptly.
- Training and services. Mentions of training, courses, consultation, advice, selection, installation, calibration or other support, including the “Learn…Certify” pathway, describe learning stages and are not an offer, quotation, tender or promise of any result. Contacting us or our replying creates no engagement or duty of care; an engagement exists only under a written agreement. We are not a regulator or certification body, and completing any course or reading this content is not a certification, accreditation or authorisation to work on any aerodrome.
- Copyright, privacy and corrections. © 2026 Precision AGL Academy. All rights reserved. Text, structure, compilations and diagrams may be viewed for personal reference and internal training only; any other copying, republication or commercial use needs our written permission. If you email, telephone or message us, we use your details only to respond and handle your matter, in line with applicable Indian law including the Digital Personal Data Protection Act, 2023; please do not send confidential or security-sensitive information. To display this page your browser requests fonts, icons and images from third-party servers, which receive your IP address and browser details under their own policies. Content is reviewed periodically with no obligation to update. To report an error, safety concern or rights issue, write to precisionaglsolutions@gmail.com.