Clearance Bar Light
A row of yellow in-pavement lights that marks a holding position or intersecting taxiway to increase its conspicuity, particularly in low-visibility conditions. Known as Intermediate Holding Position (IHP) lights under ICAO Annex 14, and as clearance bar lights in FAA terminology, they identify where a hold is located rather than signalling that a pilot is cleared to cross it.
Image disclaimer: For identification and illustration only. It may show a product by another manufacturer and may not depict the exact item described; it is not a statement of any product’s quality, approval or performance. Third-party image and trademark rights belong to their owners. See full notice.
What Is It?
A Clearance Bar Light — called an Intermediate Holding Position (IHP) Light under ICAO Annex 14 — is a row of three in-pavement steady-burning yellow lights that marks a holding position on a taxiway, increasing its conspicuity in low-visibility conditions. It may also be installed to mark the location of an intersecting taxiway during darkness. It is frequently co-located with a stop bar, but the two fixtures serve different roles: the stop bar's red lights are what pilots watch for the actual stop/proceed instruction — switched on to hold traffic, switched off (in conjunction with an explicit ATC clearance) to indicate traffic may proceed — while the clearance bar's yellow lights simply make that hold point or intersection visible, whether or not it is currently protected by an active stop bar.
Purpose & Function
The clearance bar light exists to make a hold point unmistakably findable, especially when visibility is poor enough that the pavement marking and any co-located stop bar are hard to pick out early. A pilot taxiing in fog or at night needs to identify the holding position with enough lead time to slow and stop correctly, not spot it only once already close; the row of yellow lights gives that early, unambiguous visual cue independent of whether a stop bar is currently on. Where it marks an intermediate holding position rather than a runway-holding position, it also protects against the more subtle risk of a pilot drifting past an intersection they didn't register was there at all. It is a conspicuity aid, not a substitute for the actual stop/proceed instruction, which pilots still take from ATC and, where fitted, the stop bar's own on/off state.
Where Is It Used?
Clearance bar lights are installed at various locations on the airfield where a hold point or intersection needs added conspicuity, particularly in low visibility:
- Runway-holding positions, typically co-located with stop bar lights
- Intermediate holding positions on taxiways, marking the position itself
- Intersecting taxiways, to indicate their location during darkness
- ILS critical area boundaries, where the hold point needs to be conspicuous
- Low visibility operations, where conspicuity of the hold point is essential
- Military airfields requiring clearly marked hold points
Installation & Location
Fixtures are set out in a row across the taxiway at the holding position, ILS critical area boundary, or apron entry/exit point they protect, using the standard load-rated inset base can recessed into the pavement (or an elevated frangible-mount fixture where the location falls on an unpaved shoulder). Because the bar is switched independently of the taxiway centreline lighting whenever it protects an ILS boundary or a holding point, each fixture is wired on its own control cable back to the local controller or Remote I/O in addition to the series-circuit power feed, with cabling and setout typically shared with the co-located stop bar or holding-position installation it accompanies.
How Does It Work?
Clearance bar lights operate as an integral part of the taxiway guidance and control system:
- Power: Powered from the constant current series circuit via an isolating transformer (typically 15W – 45W).
- Light Source: Utilizes yellow/amber LED arrays or yellow-filtered halogen lamps, per the standard aeronautical yellow used for taxiway and holding-position markings.
- Configuration: Installed as a row of three in-pavement lights across the taxiway at the holding position or intersection, typically adjacent to a co-located stop bar.
- Control: Illuminated continuously, or switched together with taxiway centreline lighting under low-RVR conditions, via the ALCMS.
- Indication: When illuminated, the clearance bar makes the hold point or intersection conspicuous; it does not itself indicate that a pilot may cross — that instruction comes from ATC and, where fitted, the co-located stop bar's on/off state.
System Architecture & Control Logic
Where the clearance bar protects an ILS critical area boundary or a runway-holding position alongside a stop bar, it is typically wired on its own control cable back to the local controller or Remote I/O, in addition to its series-circuit power feed, so the ALCMS can switch it independently of loop current selection elsewhere on the field. Its switching logic is separate from the stop bar's: the stop bar is what carries the actual stop/proceed instruction — on for hold, off (with an explicit ATC clearance) for proceed — while the clearance bar is commonly switched together with the taxiway centreline lighting it accompanies, illuminated to improve conspicuity of the hold point under low-RVR conditions rather than toggled in lockstep with the stop bar's state. Status and fault reporting flow back to the ALCMS per fixture rather than per loop, since — unlike the edge lighting series circuit — a fault at a protected hold point has direct operational significance and needs to be pinpointed quickly, not just flagged as a general loop-level anomaly.
ALCMS → Local Controller / Remote I/O → Two Independent Fixtures, Two Different Jobs
Stop/Proceed Logic vs. Conspicuity Switching
ATC / ALCMS
Issues the hold or proceed instruction, and switches conspicuity lighting for RVR conditions
Isolating Transformer
15W – 45W, feeds the bar from the series circuit
Switched with Centreline Lighting
Illuminated under low-RVR conditions, or continuously where fitted
Conspicuity
Marks the hold point or intersection — no stop/proceed meaning of its own
ON = Hold
All traffic must stop
OFF + ATC Clearance = Proceed
Switched off only with an explicit ATC clearance
Physical Construction
A clearance bar light fixture is typically built as a set of three inset (or occasionally elevated) lamp units housed in a single die-cast aluminium or heavy-duty polymer base, set flush with the pavement at the holding position. Each of the three lamp positions uses an LED array or incandescent/halogen lamp behind an amber/yellow filtered lens or coloured LED optic, gasket-sealed with an O-ring to the housing to achieve an IP67/IP68 rating suitable for continuous wheel loading and standing water. The unit is load-rated for aircraft wheel traffic and is typically installed in an L-867-style base can recessed into the pavement, with stainless-steel or corrosion-resistant fasteners securing the top assembly. Internal wiring from all three lamp positions is bundled and terminates at a sealed L-823 primary connector, which mates to the secondary lead of the isolating transformer housed in a nearby base can, allowing the whole bar to be switched on and off (or flashed) as a single circuit element.
Technical Parameters
| Parameter | Typical Value |
|---|---|
| Light Source | Yellow/Amber LED array or 15W – 45W halogen with yellow filter |
| Colour | Yellow/Amber (clearance indication) |
| Luminous Intensity | 100 – 500 candela (depending on setting) |
| Intensity Steps | 3 to 5-step (2.8A – 5.2A) CCR controlled |
| Configuration | Row of lights across taxiway at holding position |
| Beam Pattern | Uni-directional or omnidirectional |
| Mounting Type | Flush-mounted (inset) or elevated |
| Load Capacity (inset) | ≈27,000 kg (59,400 lbs) wheel load — governing case: fully loaded A380-800 tyre, per FAA Engineering Brief 83A |
| Isolating Transformer | 15W – 45W (6.6A series circuit) |
| Protection Class | IP67 / IP68 (submersible) |
| Operating Temperature | -40°C to +55°C |
Electrical Requirements
| Requirement | Typical Value |
|---|---|
| Circuit Type | Series circuit, constant current (CCR fed) |
| Rated Series Current | 6.6A (5-step: 2.8A / 3.4A / 4.1A / 5.2A / 6.6A) |
| Isolation | Via dedicated isolating transformer (15W–45W) per unit |
| Transformer Secondary | Matched to fixture wattage; sized to series circuit rating |
| Cable Type | L-824 single-conductor, direct-burial rated, 5kV or 600V per circuit design |
| Connector | L-823 primary connector, submersible-rated splice |
| Insulation Resistance | ≥ 50 MΩ (megger test, cable-to-ground) |
| Earthing/Grounding | Fixture body and base can bonded to airfield earth grid |
| Fault Protection | CCR-level ground fault and open-circuit detection |
| Power Source | CCR output, regulated per ICAO/FAA intensity step schedule |
Photometric Requirements
| Parameter | Typical Value |
|---|---|
| Main Beam Intensity (Yellow/Amber) | ≥ 50 cd on-axis, up to 500 cd at full intensity |
| Beam Pattern | Unidirectional (towards approaching traffic) or omnidirectional, per site configuration |
| Vertical Beam Spread | ± 5° about set axis (unidirectional) or full hemisphere (omnidirectional) |
| Isocandela Distribution | Per ICAO Annex 14 Attachment A / FAA AC 150/5340-30 figures for intermediate holding position lights |
| Chromaticity (Yellow/Amber) | Within ICAO Annex 14 yellow boundary (CIE coordinates) |
| Row Uniformity | Adjacent units in the clearance bar matched to within ± 25% of each other's intensity |
| Intensity Tolerance | ± 25% of rated value at each CCR step (field measurement) |
| Maintenance Factor | ≥ 50% of new-fixture intensity before lens/filter or LED replacement is due |
| Test Method | Mobile photometric van/goniophotometer or fixed test bench per fixture |
Applicable Standards
ICAO Annex 14
Clearance bar light requirements and installation standards
FAA AC 150/5345-46
Specification for clearance bar lights
IEC TS 61827
Characteristics of inset and elevated AGL luminaires
IES LM-79 / LM-80
LED clearance bar light electrical/photometric performance and lumen-maintenance durability testing
Installation Requirements
Base Can Excavation & Grade
CivilExcavate and compact the sub-grade to design depth before setting the load-rated inset base can (or elevated frangible-mount base can on an unpaved shoulder), holding it flush and level.
Row Set-out at Protected Boundary
CivilSet out the fixture row across the taxiway at the holding position, ILS critical area boundary, or apron entry/exit point it protects, sharing cabling and setout with the co-located stop bar installation where applicable.
Independent Control Cable
ElectricalWire each fixture on its own control cable back to the local controller or Remote I/O, in addition to the series-circuit power feed, since the bar switches independently of the taxiway centreline lighting.
Duct & Cable Route
ElectricalLay the series circuit and control cable duct to design depth, avoiding sharp bends that could stress connectors at final termination.
L-823 Connector Termination
ElectricalTerminate and seal the primary connector per manufacturer procedure, keeping the splice submersible-rated before backfill or reinstatement of the base can.
Isolating Transformer Matching
ElectricalConfirm the isolating transformer wattage matches the fixture and the series circuit's rated current step before connection.
Mount-Type Fixing
MechanicalFor elevated units, torque the frangible coupling to spec; for inset units, seat the housing flush and confirm it meets wheel-load tolerance.
Pre-Energisation Sign-off
DocumentationRecord base can position, cable route, connector seal, and control cable routing as-built before backfill, since these are not inspectable once the site is closed.
Testing & Commissioning
Insulation Resistance (Megger) Test
Pre-EnergisationMegger-test the series loop feeding the clearance bar before energisation, confirming insulation resistance clears the acceptable minimum.
Loop Continuity & Resistance Test
Pre-EnergisationVerify series loop continuity through the clearance bar fixtures and record total loop resistance before first energisation.
Switching Sequence Check with Stop Bar
EnergisationConfirm the clearance bar switches correctly with taxiway centreline lighting under commanded RVR conditions, and confirm the adjacent stop bar's on/off sequence operates independently and correctly on its own control logic.
Primary/Secondary Voltage Verification
EnergisationWith the CCR energised, confirm secondary voltage at each fixture's connector matches the transformer's rated ratio at the commissioned current step.
Photometric & Chromaticity Test
Final AcceptanceMeasure beam intensity and amber/yellow chromaticity with a calibrated photometer against ICAO/FAA commissioning tolerances.
Alignment & Aim Verification
Final AcceptanceCheck elevation and azimuth of each fixture in the bar against the design aiming diagram, correcting any deviation before sign-off.
Documentation & As-Built Sign-off
Final AcceptanceRecord loop resistance, switching sequence, and photometric readings in the commissioning dossier for handover.
Inspection & Maintenance
Yellow Filter / LED Output Check
AnnualVerify light output and colour against rated values to catch filter or LED degradation.
Lens Cleaning
QuarterlyClean the lens of contamination to maintain light output.
Control System Integration Test
AnnualVerify the fixture responds correctly to control system commands, catching integration issues early.
Seal & Gasket Inspection
AnnualCheck seals and gaskets for degradation that could let moisture into the fixture.
Common Field Issues
Yellow Filter/LED Degradation
Yellow light sources and filters are susceptible to UV degradation and thermal stress. Regular photometric testing and replacement is essential to maintain clear yellow colour indication.
Lens Contamination
Clearance bar lights are exposed to rubber deposits, dust, and de-icing fluids. Regular cleaning with approved solvents and soft brushes is required to maintain light output.
Control System Integration Issues
Clearance bar lights must be properly integrated with stop bar lights and ATC control systems. Incorrect sequencing or timing can lead to confusion or safety risks. Regular system testing is essential.
Troubleshooting Guide
Yellow Colour Fade or Reduced Intensity
Reduced Light Output from Contamination
Clearance Bar Out of Sequence with Stop Bar
Fixture Dark or Fails to Illuminate on Command
Failure Modes & Root Causes
Loss of Synchronization With the Paired Stop Bar Circuit
Amber / Yellow Lens Chromaticity Fade
LED Array / Isolating Transformer Failure
L-823 Connector / Series Circuit Insulation Breakdown
Frangible / Housing Fatigue
Safety & Operational Notes
Series Circuit Isolation
Electrical SafetyClearance bar circuits run on a constant-current series loop that can carry several kV. De-energise and lock out the CCR, then verify zero energy at the fixture before opening its housing or handling cable connectors.
Never Force a Clearance Bar or Stop Bar Off-Script
Runway Incursion SafetyThe stop bar, not the clearance bar, carries the actual stop/proceed instruction pilots rely on. Never force either fixture on, off, or into a manual state without ATC/airside authorisation — an incorrect clearance bar state can mislead a pilot about which hold point they're approaching, and an incorrect stop bar state can lead directly to a runway incursion.
Frangibility Not to Be Defeated
MechanicalNever substitute the frangible mount with a rigid fitting or over-torque it during installation or repair; the mount must still shear cleanly on aircraft or vehicle impact to limit damage under the frangibility requirement.
Airside Work Coordination
OperationalBecause the clearance bar works alongside stop bar protection at a holding position, obtain ATC/airside coordination and issue a NOTAM before taking any unit out of service, and keep personnel and vehicles clear of the holding position during active movements.
FOD Control at the Fixture
OperationalKeep tools, fasteners, and removed gaskets accounted for at all times when the housing is open, and secure or remove any loose material before reinstating the fixture, to prevent foreign object debris on the movement area.
Insulation Test Before Re-Energisation
Electrical SafetyAfter any cable, connector, or transformer work, megger test the affected series loop before restoring power, since a residual fault at re-energisation can trip the CCR or damage healthy fixtures on the same circuit.
PPE & Grounding
Personnel SafetyUse insulated tools and appropriate PPE when working on series-circuit connections, and confirm the fixture and base are bonded/grounded per the electrical design before reconnecting the loop.
Restore to Compliant State
ComplianceDo not leave a unit dark, dim, or out of step with the co-located stop bar after maintenance; verify photometric output and correct control-logic response before closing out the work and cancelling the associated NOTAM.
Engineering & Expert Notes
Switching Logic Should Be Tested as a System, Not Assumed From Wiring Diagrams
OperationalClearance bar and stop bar switching behaviour is safety-critical, even though the two fixtures serve different jobs; confirm actual switching function by testing the live sequence rather than relying on the as-built wiring diagram, since a field modification or control logic update can drift from documentation over time.
Amber Colour Consistency Needs Checking Against the Full Set
ComplianceWhere multiple clearance bar fixtures exist at a single holding position, check colour consistency across the full set rather than against a single reference fixture elsewhere on the airfield; lens batch variation between installation dates can create a visible mismatch within one bar.
Never Treat a Controller Override as a Permanent Fix
OperationalA temporary manual override used to keep a clearance bar functional during a fault investigation should be logged and time-limited; leaving an override in place past the troubleshooting window risks the bar no longer reflecting the actual holding-position status it's meant to mark.
Confirm Which Circuit Segment You're Isolating Before Work Begins
ElectricalClearance bar lighting is often on a circuit segment shared with or adjacent to stop bar control wiring; confirm the specific segment being isolated before starting work, since isolating the wrong adjacent segment can leave live control wiring energised unexpectedly.
Frangibility Applies Even to Low-Profile Holding Position Fixtures
MechanicalClearance bar fixtures are typically low-profile, which can make the frangibility requirement feel less pressing than on a taller fixture; the coupling still needs to shear correctly under load, and a rigid substitution during field repair defeats that requirement regardless of the fixture's height.
Restore and Re-Verify Switching Logic Before Returning to Service
ComplianceAfter any maintenance affecting a clearance bar, re-verify its switching sequence and confirm the associated stop bar still operates correctly on its own logic before closing out the work and cancelling any associated NOTAM; a fixture that looks correct in isolation can still leave broken switching logic behind it.
Frequently Asked Questions
Short answers about clearance bar lights: what they mark, how they differ from stop bars, intensity, standards, maintenance and common faults.
Q1What is a clearance bar light?
A clearance bar light, called an Intermediate Holding Position (IHP) light under ICAO Annex 14, is a row of three in-pavement steady-burning yellow lights that marks a holding position on a taxiway and increases its conspicuity in low visibility. It may also mark the location of an intersecting taxiway during darkness.
Q2What is the difference between a clearance bar and a stop bar?
They are often co-located but play different roles. A stop bar's red lights give the actual stop/proceed instruction: on to hold traffic, off together with an explicit ATC clearance to allow it to proceed. A clearance bar's yellow lights simply mark the hold point so it is easy to find.
Q3Where are clearance bar lights used?
At runway holding positions (usually alongside stop bars), intermediate holding positions on taxiways, intersecting taxiways, ILS critical area boundaries, low visibility operations and military airfields needing clearly marked hold points.
Q4How many lights make up a clearance bar?
A row of three lights across the taxiway at the holding position or intersection, typically adjacent to a co-located stop bar. Fixtures are inset in a load-rated base can, or elevated on a frangible mount where the location is an unpaved shoulder.
Q5What colour and intensity are clearance bar lights?
Yellow or amber within the ICAO Annex 14 yellow boundary, with at least 50 cd on-axis and up to 500 cd at full intensity. Adjacent units in the row are matched within ±25% of each other.
Q6Are clearance bar lights steady or switched?
They are illuminated continuously or switched together with taxiway lighting. When a bar protects an ILS boundary or a holding point it is switched independently of the taxiway centreline lighting, so its control integration with the stop bar and ATC system should be tested.
Q7What load can an inset clearance bar light take?
About 27,000 kg (59,400 lbs) wheel load, based on a fully loaded A380-800 tyre per FAA Engineering Brief 83A. Protection is IP67/IP68 and operating temperature is −40 °C to +55 °C.
Q8Which standards apply to clearance bar lights?
The main references are ICAO Annex 14, FAA AC 150/5345-46 (clearance bar lights), IEC TS 61827 and IES LM-79 / LM-80 for LED performance and lumen maintenance. Always verify the current edition and your approved requirements.
Q9How often should clearance bar lights be maintained?
Typical intervals are quarterly for lens cleaning, and annual for yellow filter and LED output checks, control system integration tests and seal and gasket inspection. Your approved maintenance programme takes precedence.
Q10Why is my clearance bar dim, faded or out of sequence with the stop bar?
A faded colour or reduced intensity is usually UV and thermal degradation of the yellow filter or LED, needing a photometric check and replacement. Dimming can also be lens contamination from rubber, dust and de-icing fluid. An out-of-sequence bar points to incorrect integration or timing between it and the stop bar or ATC control system.
Related Components
Go Beyond the Component. Understand the Complete AGL System.
You have explored the component. Now understand how it works within the complete Airfield Ground Lighting system.
Learn AGL from fundamentals to design, installation, testing, photometry, commissioning, maintenance and troubleshooting through structured technical training at Precision AGL Academy.
Build practical knowledge. Understand the circuit. Read the standards. Troubleshoot with confidence.
Your next step in AGL starts here.
Need expert guidance on clearance bar light selection or installation?
Precision AGL Academy provides advice on control system integration, positioning, and field testing of clearance bar lighting systems.
Follow the Academy
Important Notice, Disclaimer & Limitation of Liability
Please read before relying on any content on this page.
- Purpose and intended users. This page on Clearance Bar Light is an independent educational and informational reference for competent, suitably trained and authorised airfield ground lighting (AGL) and aerodrome electrical personnel. It is not professional engineering, legal or regulatory advice, and using it does not create any professional or client relationship.
- Safety. Work on series circuits, constant current regulators (CCRs), isolating transformers, cables, connectors and lighting equipment can be fatal. Always apply the aerodrome’s permit-to-work and isolation/LOTO procedures, prove dead, use correctly rated instruments and PPE, and follow the manufacturer’s instructions. Nothing here authorises work on live equipment or the bypassing of any safety device or interlock.
- Aviation operations. Nothing here authorises installation, modification, energisation, adjustment, return to service, a change of operating category (CAT I/II/III), a NOTAM or any aerodrome certification or approval decision. These rest with the aerodrome operator, the air navigation service provider and the competent regulator.
- Specifications, ratings and typical values. Descriptions, parameters, ratings, dimensions, photometric values, wattages, service lives, maintenance tasks and intervals, failure modes, certifications (for example CE, FCC, UL or IEC marks) and part or type designations are general, typical and indicative. They may not match any particular product, make, model or version, and they are not a datasheet, design, specification, selection, sizing, procurement or acceptance criterion. The manufacturer’s current documents, the approved design and the project specification prevail.
- Standards and regulations. References to ICAO, FAA, IEC, IEEE, ISO, BIS, DGCA and other standards are paraphrased summaries for orientation only. They may be incomplete or out of date, and standards are revised from time to time. Consult the current official editions. Following this content does not guarantee compliance with any law, standard or regulatory approval, and the regulator’s requirements always prevail.
- No warranty. Content is provided “as is” and “as available”, without warranty of any kind, express or implied, including accuracy, completeness, currency or fitness for a particular purpose. Real installations differ in design, equipment make and model, age and condition.
- Limitation of liability. To the fullest extent permitted by applicable law, Precision AGL Academy, Precision AGL Solutions and their owners, authors and contributors are not liable for any injury, death, loss, damage, downtime, penalty or regulatory consequence, whether direct or indirect, arising from the use of, reliance on, or inability to use this content. Nothing in this notice excludes or limits any liability that cannot lawfully be excluded or limited.
- Independence, brands and no endorsement. This is an independent publication. It is not affiliated with, sponsored by or endorsed by ICAO, the FAA, the IEC, DGCA, AAI, any airport, regulator, supplier or equipment manufacturer. Third-party names, product designations, standard designations and trademarks (including Megger®, Siemens, Eaton, Crouse-Hinds, ADB SAFEGATE, Fluke, ABB and Honeywell) belong to their respective owners and are used only for identification and description. Mention of a brand, product or supplier is not a recommendation, and we do not sell, supply or quote for any component described.
- Images and third-party content. Images and illustrations are shown to help identify the type of component. They may show products of various manufacturers, may not depict the exact item described, and are not a statement about any product’s quality, approval or performance. Copyright and trademarks in third-party images, logos and photographs belong to their respective owners and are not claimed as ours. If you are a rights holder and want an image removed, replaced or credited, email precisionaglsolutions@gmail.com with the page address and we will act promptly.
- Training and services. Mentions of training, courses, consultation, advice, selection, installation, calibration or other support, including the “Learn…Certify” pathway, describe learning stages and are not an offer, quotation, tender or promise of any result. Contacting us or our replying creates no engagement or duty of care; an engagement exists only under a written agreement. We are not a regulator or certification body, and completing any course or reading this content is not a certification, accreditation or authorisation to work on any aerodrome.
- Copyright, privacy and corrections. © 2026 Precision AGL Academy. All rights reserved. Text, structure, compilations and diagrams may be viewed for personal reference and internal training only; any other copying, republication or commercial use needs our written permission. If you email, telephone or message us, we use your details only to respond and handle your matter, in line with applicable Indian law including the Digital Personal Data Protection Act, 2023; please do not send confidential or security-sensitive information. To display this page your browser requests fonts, icons and images from third-party servers, which receive your IP address and browser details under their own policies. Content is reviewed periodically with no obligation to update. To report an error, safety concern or rights issue, write to precisionaglsolutions@gmail.com.