Runway Exit Light

A visual guidance fixture installed on the runway surface that identifies the location of a runway exit or turnoff point. These lights assist pilots in locating taxiway exits during landing roll, particularly in low‑visibility conditions, enabling efficient runway vacating and improved airfield throughput.

Runway Exit Light

Image disclaimer: For identification and illustration only. It may show a product by another manufacturer and may not depict the exact item described; it is not a statement of any product’s quality, approval or performance. Third-party image and trademark rights belong to their owners. See full notice.

Overview

What Is It?

A Runway Exit Light is an inset or elevated light fixture positioned on the runway surface to mark the location of a taxiway exit, rapid exit taxiway, or runway turnoff point. These lights are typically arranged in a row or pattern across the runway, providing pilots with a clear visual indication of where to turn off during the landing roll. The lights are usually green (for the exit path) or yellow (for caution areas), and they may be uni‑directional or bidirectional depending on the exit configuration. Runway exit lights are a critical component of airfield surface movement guidance, helping to reduce runway occupancy time and improve safety by ensuring pilots can quickly and confidently locate exits, especially in low visibility (RVR conditions) and at unfamiliar airports.

Purpose

Purpose & Function

The runway exit light's purpose is to let a pilot identify and commit to a taxiway exit while still decelerating on the runway, rather than needing to slow further or come to a stop while searching for the correct turnoff — a difference that translates directly into reduced runway occupancy time and, at busy airports, meaningfully higher runway capacity. Its colour coding does double duty in this role: green marks the exit path itself so a pilot can identify it unambiguously, while yellow flags caution areas that should not be mistaken for the intended exit, a distinction that matters most in the low-visibility conditions where a wrong turn or a missed exit has the greatest operational consequence.

Application

Where Is It Used?

Runway exit lights are installed at the intersection of the runway and a taxiway exit, typically at the beginning of the exit curve. They are used on both precision and non‑precision runways, with rapid exit taxiways (RETs) often having dedicated exit light configurations. The lights are placed at regular intervals along the exit path, starting from the runway centreline and extending into the taxiway. They are commonly found at airports with high traffic volumes, where efficient runway vacating is essential for capacity. The fixtures may be flush‑mounted (inset) in the pavement for high‑speed exits or elevated on frangible poles for lower‑speed exits. In some configurations, the exit lights are integrated with lead‑off lights to provide sequential guidance towards the exit.

Placement

Installation & Location

Exit lights are set out starting at the runway centreline and running along the exit path into the taxiway, spaced at regular intervals so the row of lights traces the curve a departing aircraft will follow. High-speed rapid exit taxiways typically use inset (flush) fixtures set into the pavement, since the exit curve is taken at speed and an elevated fixture would be a strike risk, while lower-speed exits may use elevated fixtures on frangible poles where the surface and traffic pattern allow it. Each fixture is tied into the same centreline and taxiway survey used for the runway and exit geometry, so the light row lines up exactly with the paved curve, and cabling is run underground back to the nearest junction box or isolating transformer serving that section of the runway edge circuit.

Function

How Does It Work?

Each runway exit light is powered from the series circuit via an isolating transformer, with intensity controlled by the CCR's current steps (typically 5‑step, 2.8A – 6.6A). The fixture uses a precision optical system (reflector and prism) to project a narrow beam towards the approaching aircraft, aligned along the runway centreline or angled towards the exit. The green colour indicates the exit path direction, while yellow may be used for caution areas or holding positions. Some exit lights are bidirectional, visible to pilots on both approach and departure, while others are uni‑directional, visible only from the approach side. Because all fixtures on a loop are switched and dimmed together by the CCR, the sense of direction is built into the row optically — through fixture aim, uni-/bi-directional lensing, and colour — rather than through any per-fixture electrical sequencing or flashing. The fixtures are designed to withstand heavy aircraft loads (up to 100,000 kg for inset versions) and harsh environmental conditions.

Architecture

System Architecture & Control Logic

Runway exit lights are not individually addressable — control is exercised at the loop level through the constant current series circuit, typically the same runway edge circuit or a dedicated exit-lighting loop. An Airfield Lighting Control and Monitoring System (ALCMS), operated by the tower or an automated visibility-linked routine, selects the required brightness step based on prevailing RVR, ATC instruction, or (at smaller aerodromes) pilot-controlled lighting input. This command is passed to the CCR, which regulates the entire loop to the corresponding fixed current (one of 5 steps between 2.8A and 6.6A). Every fixture on that loop, via its own isolating transformer, draws from the same current and burns at the same intensity simultaneously — there is no way to dim, brighten, or sequence a single exit light independently of the rest of the loop, so directional or sequenced flash patterns are implemented optically (lens angle, reflector aim) rather than through per-fixture electrical commands. Fault detection is likewise loop-based: the CCR monitors loop voltage against the commanded current, and a voltage rise signals increased circuit impedance — typically an open-circuit lamp or a failed isolating transformer — reported to the ALCMS as a loop fault rather than pinpointed to an exact fixture without further sectionalised testing.

ALCMS → CCR → Series Circuit Loop → Isolating Transformer → Exit Light Fixture (with loop-level feedback)

AIRFIELD LIGHTING CONTROL SYSTEM (ALCMS) Selects brightness step (RVR / ATC / PCL) CONSTANT CURRENT REGULATOR Converts step command to fixed current SERIES CIRCUIT LOOP Same current for every fixture — no individual control ISOLATING TRANSFORMER (PER FIXTURE) Taps fixed loop current to fixture secondary RUNWAY EXIT LIGHT FIXTURE Emits green/yellow beam at commanded intensity LOOP-LEVEL CONTROL — NOT PER-FIXTURE All fixtures on a loop switch and dim together Direction/colour set optically, not electrically LOOP FEEDBACK CCR tracks loop voltage against commanded current Voltage rise flags an open circuit or failed transformer
Beam Logic

Directional Visibility & Colour Coding

CCR Current Step Sets Intensity5‑step, 2.8A – 6.6A
▼
Reflector & Prism Shape the BeamAligned to centreline or angled towards the exit
▼
Bidirectional Fixture
Visible on Approach AND Departure
Uni‑Directional Fixture
Visible Only From Approach Side
▼
Green = Exit Path Direction · Yellow = Caution / Holding Position
Construction

Physical Construction

The fixture follows the same general construction as other runway inset or elevated lights: a die-cast aluminium housing, anodised or powder-coated for corrosion resistance, with the optical assembly — an LED array or halogen lamp behind a green or yellow filtered lens or prism — gasket-sealed with an O-ring to achieve an IP67/IP68 rating for surface-mounted, wheel-loaded installations. Inset units seat in an L-867/L-868-style base can recessed into the runway pavement with the top surface load-rated for aircraft wheel traffic, while elevated units mount on a frangible coupling designed to shear cleanly under impact, seated on a base can set into the surrounding grade. Because exit lights are frequently arranged as a directional row or curve marking the turnoff path, each fixture in the set is individually aimed during installation to project its beam along the intended taxi path. Internal wiring terminates at sealed L-823 primary connectors mating to the secondary leads of a nearby isolating transformer, with stainless-steel fasteners and a base can drainage provision completing the assembly.

Specification

Technical Parameters

ParameterTypical Value
Light SourceLED array or 45W / 65W halogen
ColourGreen (exit path) or Yellow (caution zone)
Intensity (Max)Up to 10,000 cd (green) / 5,000 cd (yellow) at 6.6A
Intensity Steps5‑step (2.8A – 6.6A) CCR controlled
Beam PatternUni‑directional or bidirectional (3° vertical x 6° horizontal)
SpacingTypically 15–30m along exit path
Mounting TypeInset (flush) or Elevated (frangible pole)
Load Capacity (Inset)100,000 kg (220,000 lbs) wheel load
Isolating Transformer45W / 65W (6.6A series circuit)
Protection ClassIP67 / IP68 (submersible)
Power Supply

Electrical Requirements

RequirementTypical Value
Circuit TypeSeries circuit, constant current (CCR fed)
Rated Series Current6.6A (5-step: 2.8A / 3.4A / 4.1A / 5.2A / 6.6A)
IsolationVia dedicated isolating transformer (45W/65W), not directly connected to series loop
Transformer SecondaryMatched to fixture wattage; sized to series circuit rating
Cable TypeL-824 single-conductor, direct-burial rated, 5kV or 600V per circuit design
ConnectorL-823 primary connector, submersible-rated splice
Insulation Resistance≥ 50 MΩ (megger test, cable-to-ground)
Earthing/GroundingFixture body and base can bonded to airfield earth grid
Fault ProtectionCCR-level ground fault and open-circuit detection
Power SourceCCR output, regulated per ICAO/FAA intensity step schedule
Optical Performance

Photometric Requirements

ParameterTypical Value
Main Beam Intensity (Green, Exit Path)≥ 6,500 cd on-axis, up to 10,000 cd at full intensity
Main Beam Intensity (Yellow, Caution Zone)≥ 3,000 cd on-axis, up to 5,000 cd at full intensity
Beam PatternUnidirectional or bidirectional (3° vertical × 6° horizontal), per site configuration
Isocandela DistributionPer ICAO Annex 14 Attachment A / FAA AC 150/5340-30 figures for runway exit/taxiway centreline lights
ChromaticityWithin ICAO Annex 14 green or yellow boundary as applicable (CIE coordinates)
Intensity Tolerance± 25% of rated value at each CCR step (field measurement)
Maintenance Factor≥ 50% of new-fixture intensity before lamp/lens replacement is due
Test MethodMobile photometric van/goniophotometer or fixed test bench per fixture
Compliance

Applicable Standards

ICAO Annex 14

Runway exit light colour, spacing, and photometric requirements

FAA AC 150/5345-46

Specification for runway exit lights and lead‑off lights

IEC 61827

Characteristics of inset and elevated luminaires used on aerodromes and heliports

FAA Engineering Brief #67

Light Sources Other Than Incandescent and Xenon for Airport and Obstruction Lighting Fixtures — LED exit light performance and durability requirements

Prerequisites

Installation Requirements

Exit Curve Setting-Out
Civil

Set out fixture positions from the same centreline and exit survey used for the runway and exit geometry, spacing units at regular intervals so the row traces the paved exit curve exactly.

Base Can Installation
Civil

Install the inset (flush) base can on high-speed rapid exit sections, or the elevated frangible base can on lower-speed exits, to the design depth appropriate for the exit's speed and surface.

Duct & Cable Route to Isolating Transformer
Electrical

Run cable underground back to the nearest junction box or isolating transformer serving that section of the runway edge circuit.

Isolating Transformer Matching
Electrical

Confirm the isolating transformer wattage and ratio match the fixture and the series circuit's rated current step before connection.

Frangible Coupling / Base Can Fixing
Mechanical

Torque the frangible coupling (elevated units) or seat and level the base can (inset units) to specification, confirming the fitting behaves correctly under lateral load.

Beam Direction & Colour Orientation Setting
Mechanical

Orient the fixture so the correct colour shows from the intended approach direction, matching the design aiming diagram before the site is closed.

Pre-Energisation Sign-off
Documentation

Record base can position, cable route, connector seal, and orientation as-built before backfill, since these are not inspectable once the site is closed.

Verification

Testing & Commissioning

Insulation Resistance (Megger) Test
Pre-Energisation

Megger-test the isolating transformer and series loop before the circuit is energised, confirming insulation resistance clears the acceptable minimum ahead of backfill.

Loop Continuity & Resistance Test
Pre-Energisation

Verify series loop continuity end to end and record total loop resistance, ruling out open circuits or high-resistance splices before first energisation.

Primary/Secondary Voltage Verification
Energisation

With the CCR energised, confirm secondary voltage at the L-823 connector matches the transformer's rated ratio at the commissioned current step.

CCR Brightness Step Response
Energisation

Cycle the CCR through every intensity step and confirm the fixture responds correctly at each, ruling out marginal transformers or loose connections.

Beam Alignment & Direction Verification
Final Acceptance

Check beam direction (uni- or bidirectional as specified) and elevation against the design aiming diagram, confirming the correct colour — green or yellow — shows from the intended approach direction.

Photometric Commissioning Test
Final Acceptance

Measure beam intensity, colour, and beam spread with a calibrated photometer against ICAO/FAA commissioning tolerances prior to operational handover.

Frangibility / Base Can Verification
Pre-Energisation

Confirm the frangible coupling (elevated units) or base can depth and drainage (inset units) meet as-built tolerances before the site is finally backfilled.

Documentation & As-Built Sign-off
Final Acceptance

Record insulation, continuity, voltage, and photometric readings alongside as-built position in the commissioning dossier for handover.

Upkeep

Inspection & Maintenance

Beam Alignment Check
Semi-annual

Verify the beam remains correctly angled to the exit path it's guiding traffic along.

Lens Cleaning
Quarterly

Clean the lens of rubber deposits and debris to maintain light output.

Seal & Drainage Check
Annual

For inset fixtures, check seals and drainage to prevent water ingress.

Frangible Coupling Inspection
Annual

For elevated versions, check the coupling for fatigue and confirm it shears freely if struck.

Field Notes

Common Field Issues

Beam Misalignment from Exit Angle

Runway exit lights must be precisely aligned to guide pilots towards the exit, especially on high‑speed exits where the turn angle is sharp. Pavement settlement or improper installation can cause the beam to point off‑axis, reducing visibility. Regular alignment checks using a digital level and alignment jig are critical.

Lens Contamination from Rubber Deposits

Exit lights are located in areas of high tyre friction, leading to rapid rubber accumulation on the lens. Frequent cleaning with approved solvents and soft brushes is essential to maintain photometric performance, especially at busy airports.

Water Ingress in Inset Fixtures

Inset exit lights are exposed to standing water, de‑icing fluids, and jet blast. Failed seals or O‑rings can allow moisture ingress, causing corrosion and electrical faults. Regular seal inspection and pressure‑vent maintenance are necessary to maintain IP68 integrity.

Frangible Coupling Fatigue (Elevated Version)

Elevated exit lights rely on a frangible coupling to break on impact. Over time, the coupling may become brittle due to weather or shear fatigue. Routine replacement intervals are recommended for high‑impact zones to ensure breakaway performance.

Diagnostics

Troubleshooting Guide

Single Fixture Dark, Rest of Circuit Normal
Likely Cause
Failed lamp/LED module, or an open isolating transformer (blown primary fuse-wire link or failed secondary winding).
Diagnostic Steps
Confirm series loop continuity is unbroken through the fixture's transformer primary; megger the transformer; check secondary voltage at the connector with the CCR energised.
Corrective Action
Replace the lamp/LED module if the transformer checks healthy; otherwise swap the isolating transformer and re-seal the L-823 connectors before backfill.
Entire Series Circuit Dark / CCR Will Not Regulate
Likely Cause
Open-circuit fault in the series loop (severed cable, corroded L-823 splice, or a failed transformer acting as an open point).
Diagnostic Steps
Check the CCR fault/open-circuit indication first; loop-resistance test from the CCR output to isolate the faulted segment; sectionalise and megger cable runs to narrow down the break.
Corrective Action
Excavate and repair or replace the faulted cable section and connector; re-test insulation resistance before reinstating the circuit.
CCR Trips on Overcurrent or Ground Fault
Likely Cause
Moisture ingress at an inset fixture's seal or O-ring has degraded insulation resistance, creating a short or partial ground fault.
Diagnostic Steps
Megger the full circuit to identify the low-resistance segment; visually inspect suspect fixtures for cracked gaskets, condensation, or a failed pressure vent.
Corrective Action
Dry out or replace the affected fixture, renew O-rings and gaskets, and confirm IP68 integrity before re-energising.
Beam Off the Exit Guidance Angle
Likely Cause
Pavement settlement or improper installation has shifted the fixture's aim off the designed exit angle.
Diagnostic Steps
Check fixture aim against the design angle using a digital level and alignment jig; inspect the base can and surrounding pavement for settlement.
Corrective Action
Re-align the fixture to the specified exit angle and address any base can or subgrade settlement to prevent recurrence.
Reduced Light Output from Rubber Deposits
Likely Cause
Rapid rubber accumulation on the lens from the exit area's high tyre friction.
Diagnostic Steps
Visually inspect the lens for contamination; run a photometric intensity check against ICAO/FAA thresholds.
Corrective Action
Clean the lens with approved solvents and a soft brush on a frequent schedule, and re-verify intensity afterward.
Elevated Fixture Leaning or Down (Frangible Coupling)
Likely Cause
Weather or shear fatigue has made the frangible coupling brittle, or it has already broken from an impact.
Diagnostic Steps
Inspect the frangible coupling for cracking, brittleness, or completed breakaway; check whether the fixture is within its routine replacement interval for high-impact zones.
Corrective Action
Replace the frangible coupling per the routine replacement interval, or replace the fixture entirely if it has already broken away.
Reliability

Failure Modes & Root Causes

Isolating Transformer / LED Module Failure
High Severity
Root Cause
Component ageing, moisture ingress, or a blown primary fuse-wire link in the isolating transformer or LED module.
Effect
The single fixture goes dark while the rest of the series circuit continues to operate normally.
Detection Method
Megger test of the transformer and a secondary voltage check at the connector with the CCR energised.
Series Loop Open Circuit
High Severity
Root Cause
A severed cable, corroded L-823 splice, or a failed transformer acting as an open point in the loop.
Effect
The entire series circuit goes dark and the CCR fails to regulate.
Detection Method
Loop-resistance testing from the CCR output, followed by sectionalised megger testing to narrow down the break.
Moisture Ingress / Ground Fault
Medium Severity
Root Cause
A cracked gasket, condensation, or a failed pressure vent on an inset fixture.
Effect
The CCR trips on overcurrent or ground fault as insulation resistance degrades.
Detection Method
Full-circuit megger testing to identify the low-resistance segment, followed by visual inspection of suspect fixtures.
Beam Misalignment from Settlement
Medium Severity
Root Cause
Pavement settlement or improper installation shifting the fixture off the designed exit angle.
Effect
Degraded guidance toward the exit, particularly critical on high-speed exits with a sharp turn angle.
Detection Method
Alignment check against the design angle using a digital level and alignment jig.
Lens Contamination from Rubber Deposits
Low Severity
Root Cause
Rapid rubber accumulation from the high tyre friction typical of exit areas.
Effect
Reduced light output that can fall below photometric thresholds.
Detection Method
Photometric intensity check against ICAO/FAA thresholds, alongside visual inspection of the lens.
Frangible Coupling Fatigue (Elevated Version)
Medium Severity
Root Cause
Weather or shear fatigue embrittling the coupling on an elevated exit light.
Effect
Reduced or unpredictable breakaway performance on impact.
Detection Method
Inspection of the frangible coupling for cracking, brittleness, or completed breakaway.
Precautions

Safety & Operational Notes

Series Circuit Isolation
Electrical Safety

Runway exit lights run on a constant-current series circuit that can carry several kV across the loop. De-energise and lock out the CCR, then verify zero energy at the fixture before opening a base can or handling cable connectors.

Airside Work Coordination
Operational

Any work on or near an active runway or high-speed exit requires ATC/airside coordination and a NOTAM where the fixture will be dark or out of tolerance, with vehicle and personnel movement kept clear of the runway strip per the aerodrome's safety management procedures.

Frangibility Not to Be Defeated
Mechanical

Never substitute the frangible coupling with a rigid fitting or over-torque it during installation or repair, particularly on elevated versions; the coupling must still shear cleanly and predictably on aircraft impact to limit damage under the frangibility requirement.

Verify Exit Angle Alignment
Operational

After any maintenance affecting fixture position, confirm the beam angle against the design exit angle before returning the fixture to service; guidance accuracy is especially critical on high-speed exits with a sharp turn angle, where a misaligned light degrades pilot guidance at speed.

FOD Control at the Base Can
Operational

Keep tools, fasteners, and removed gaskets accounted for at all times when the base can is open, and secure or remove any loose material before reinstating the fixture, to prevent foreign object debris on the movement area.

Insulation Test Before Re-Energisation
Electrical Safety

After any cable, connector, or transformer work, megger test the affected series loop before restoring power, since a residual fault at re-energisation can trip the CCR or damage healthy fixtures on the same circuit.

PPE & Grounding
Personnel Safety

Use insulated tools and appropriate PPE when working on series-circuit connections, and confirm the fixture and base can are bonded/grounded per the electrical design before reconnecting the loop.

Restore to Compliant State
Compliance

Do not leave a fixture out of aim tolerance, at reduced intensity, or otherwise non-compliant after maintenance; verify photometric and positional conformance before closing out the work and cancelling the associated NOTAM.

Field Insight

Engineering & Expert Notes

Exit Angle Fixtures Aren't Interchangeable Between Exits
Design

Runway exit lights are often photometrically aimed to the specific geometry of their exit angle; a fixture pulled from stock for a different exit taxiway without re-aiming to that exit's actual angle can leave the beam pointed slightly off the intended egress path.

High-Speed Exits See More Wheel-Load Cycling
Mechanical

Exit lights on high-speed turn-offs take more frequent, higher-load wheel passes than lights on lower-traffic taxiways. Prioritise flushness and housing-integrity checks on high-speed exit fixtures over a uniform inspection interval applied fleet-wide.

Sequencing With Centreline Lights Should Be Verified as a Cue, Not Just Wiring
Operational

Exit lights are meant to work with runway centreline lighting to cue the turn-off point; confirming the exit light circuit is correctly wired doesn't confirm the combined visual cue actually reads clearly to a pilot at typical exit speed. Walk or drive the sequence at operational speed where practical during commissioning.

Colour Consistency With the Rest of the Runway Circuit Matters More Than Spec Sheets Suggest
Compliance

Exit lights installed or replaced at a different time than the rest of the runway edge lighting can show a subtle colour or brightness mismatch that individually passes tolerance but reads as inconsistent to an approaching or departing pilot. Check exit light output against the adjacent runway lighting batch, not only against the spec in isolation.

Loop Position in the Series Circuit Affects Fault Symptoms
Troubleshooting

An exit light near the end of a long series loop can show subtly different voltage/current behaviour than one nearer the CCR; a fault that presents as a dim exit light might actually be a cumulative loop issue rather than a problem local to that fixture. Check loop position before assuming a single-fixture fault.

Exit Taxiway De-Icing Traffic Ages Seals Faster
Durability

High-speed exits see concentrated de-icing fluid application during winter operations; glycol exposure degrades gaskets and lens seals faster than general weathering. Inspect seal condition on exit fixtures on a shorter cycle than lower-traffic taxiway lighting.

Quick Answers

Frequently Asked Questions

Short answers about runway exit lights: colours, where they are used, spacing, photometrics, standards, maintenance and common faults.

Q1What is a runway exit light?

A runway exit light is an inset or elevated fixture positioned on the runway surface to mark a taxiway exit, rapid exit taxiway or runway turnoff point. Arranged in a row or pattern, it shows pilots where to turn off during the landing roll.

Q2What colours do runway exit lights show?

Green marks the exit path and yellow marks caution areas. Fixtures may be uni-directional or bidirectional depending on the exit configuration.

Q3Why do runway exit lights matter?

They let a pilot identify and commit to an exit while still decelerating, rather than slowing or stopping to search for the turnoff. That reduces runway occupancy time and, at busy airports, increases runway capacity.

Q4Where are runway exit lights installed?

At the junction of the runway and a taxiway exit, typically at the start of the exit curve, and along the exit path from the runway centreline into the taxiway. They are used on precision and non-precision runways, and rapid exit taxiways often have dedicated exit light configurations.

Q5How far apart are runway exit lights?

Typically 15–30 m along the exit path, so the row traces the curve the aircraft will follow.

Q6Should exit lights be inset or elevated?

High-speed rapid exit taxiways typically use inset (flush) fixtures because the curve is taken at speed and an elevated fixture would be a strike risk. Lower-speed exits may use elevated fixtures on frangible poles. Inset units are rated for about 100,000 kg wheel loads.

Q7How bright are runway exit lights?

Green units are at least 6,500 cd on-axis and up to 10,000 cd at full intensity. Yellow units are at least 3,000 cd and up to 5,000 cd. The beam is typically 3° vertical by 6° horizontal, with field intensity tolerance of ±25% at each CCR step.

Q8Which standards apply to runway exit lights?

The main references are ICAO Annex 14, FAA AC 150/5345-46 (runway exit and lead-off lights), IEC 61827 and FAA Engineering Brief #67 for LED performance. Always verify the current edition and your approved requirements.

Q9How often should runway exit lights be maintained?

Typical intervals are quarterly for lens cleaning, semi-annual for beam alignment checks, and annual for seal and drainage checks on inset units and frangible coupling inspection on elevated units. Your approved maintenance programme takes precedence.

Q10Why is one exit light dark while the rest of the circuit works?

A failed lamp or LED module, or an open isolating transformer, is the usual cause. Confirm loop continuity through the transformer primary, megger the transformer, and check secondary voltage at the connector with the CCR energised. Replace the module if the transformer is healthy; otherwise swap the transformer and re-seal the L-823 connectors.

Go Further

Go Beyond the Component. Understand the Complete AGL System.

You have explored the component. Now understand how it works within the complete Airfield Ground Lighting system.

Learn AGL from fundamentals to design, installation, testing, photometry, commissioning, maintenance and troubleshooting through structured technical training at Precision AGL Academy.

Build practical knowledge. Understand the circuit. Read the standards. Troubleshoot with confidence.

Your next step in AGL starts here.

The Learning Pathway
Learn Understand Design Test Maintain Document Apply Certify

Need expert guidance on runway exit light selection or installation?

Precision AGL Academy provides advice on exit light positioning, alignment, and field testing to optimise runway vacating efficiency.