How is a fault isolated in a series circuit?

Make the circuit safe, read the symptom at the CCR, then narrow the fault down section by section until one part remains.

FAULT-ISOLATION FLOWCHART · SYMPTOM, TYPE, SECTIONFIRSTTELL ATC · SWITCH OFF AND ISOLATE THE CCR · LOCK OFF · AUTHORISED PERSONNEL ONLYALL LIGHTS OUTCCR open-circuit alarm, no currentOPEN CIRCUITa break in the loopTEST CONTINUITY BY SECTIONFault is where it failsCCR TRIPSEarth-fault or overcurrent alarmEARTH FAULTinsulation to earth is lowTEST INSULATION RESISTANCE BY SECTIONLow reading marks the sectionSOME LIGHTS OUTCCR normal, circuit runningLOCAL FAULTfixture, connector or transformerCHECK THE DEVICE ITSELFLight, secondary connector, transformerNARROW DOWN BY HALF-SPLITTEST: GOOD · SET ASIDEBAD · SPLIT AGAINfault sectionTHEN1 Repair the faulty part2 Retest section and circuit3 Restore, run, confirm status4 Record results, tell ATC
open circuit / step
earth fault / safety
local fault
good section
The Fact Fault tracing

Fault isolation finds a fault in a series circuit by narrowing it down in steps. The circuit is first made safe: ATC is told, and the CCR is switched off, isolated and locked off. The symptom at the CCR then suggests the fault type. All lights out with an open-circuit alarm points to an open circuit, tested with continuity checks. A trip or earth-fault alarm points to an earth fault, tested with insulation resistance checks. Some lights out with the CCR running normally points to a local fault at a fixture, connector or isolation transformer.

For the first two, the circuit is divided at accessible points and each section tested. The method is half-split: test about half the circuit, set the good half aside, and split the bad half again until one section or device remains. After repair, the section and the whole circuit are retested, the CCR is restored and status confirmed, and the results are recorded. Test methods, limits and isolation points come from the manufacturer, the standards and the airport’s safe-working rules.

Step 1Make safe, tell ATC
Step 2Read the CCR symptom
Open circuitContinuity by section
Earth faultInsulation resistance by section
Local faultFixture, connector, transformer
MethodHalf-split
After repairRetest, restore, record
ReferenceICAO Aerodrome Design Manual Part 5 (Doc 9157); FAA AC 150/5340-26 (maintenance of airport visual aid facilities); manufacturer manuals and airport safe-working rules
Awareness schematic only, not a fault-finding procedure. Series circuits carry high current and can be lethal. Isolation, lock-off, test methods, test limits and permits come from the manufacturer, the standards and the airport’s own safe-working rules, and only trained and authorised personnel work on them.
Entry 15 · Optical failure Entry 17 · CCR troubleshooting

Frequently Asked Questions

Q1What is fault isolation in an AGL series circuit?

It is the step-by-step method of narrowing a fault down from the whole circuit to one section, cable, connector or device. The circuit is split into parts, each part is tested, and the part that fails is investigated further.

Q2What must be done before any fault isolation starts?

ATC is told as the airport procedure requires, and the CCR is switched off, isolated and locked off under the permit or safe-working rules. A series circuit carries a high current, so only trained and authorised personnel work on it.

Q3How does the symptom at the CCR guide the search?

All lights out with an open-circuit alarm points to a break in the loop. A trip or earth-fault alarm points to low insulation to earth. Some lights out with the CCR running normally points to a local fault at a fixture, connector or isolation transformer.

Q4What does half-split mean?

The circuit is divided roughly in half and one half is tested. The good half is set aside and the bad half is divided again. Repeating this finds the faulty section in a few steps instead of testing every point.

Q5Why test by section instead of at every light?

A series circuit can be long, with many lights, connectors and transformers. Testing section by section removes large parts of the circuit from doubt quickly, so the work and the time the lights are out are both kept down.

Q6What happens after the fault is found?

It is repaired, then the section and whole circuit are tested again, the CCR is restored and run, and status is confirmed. The findings and test results are recorded, and ATC is told the circuit is back in service.

Precision AGL Academy

See It. Understand It. Then Learn How to Engineer It.

Recognising an AGL system visually is the first step. The next step is knowing how to design, install, test, commission and maintain them correctly.

Build Practical AGL Engineering Skills

Go deeper with structured training from Precision AGL Academy, covering:

AGL Fundamentals Design & Electrical Engineering Approach Lighting Photometry Installation & Commissioning Maintenance & Troubleshooting

Learn how each light, sign and circuit works as part of a complete airport lighting system, not just as an isolated diagram.

See. Understand. Apply. Engineer.