How do you find a ground fault when the lights stay on?

A series circuit floats clear of earth, so one insulation fault changes nothing you can see. Ground-fault detection and insulation monitoring are how that silent leak gets found early.

1 · A FLOATING LOOP WITH ONE INSULATION FAULT 2 · THE TREND THE MONITOR FOLLOWS CCRFLOATS CLEARFROM EARTHLEAKAGE CURRENTTO EARTHINSULATION DEFECTEARTHGROUND-FAULT ANDINSULATION MONITORMEASURES THE LEAKAGEAND ITS TRENDLOOP STAYS CLOSED · LIGHTS STAY ONA SINGLE LEAK IS SILENT WITHOUT MONITORINGNO LOOP BREAK, NO TRIP INSULATION RESISTANCE OVER TIMEWARNING LEVELALARM LEVELWET-WEATHER DIP,RECOVERSTREND WARNSALARMUP = BETTER INSULATIONTIME →ILLUSTRATIVE: NO REAL VALUES OR SCALE ACT ON THE FIRST FAULT A SECOND EARTH FAULT CAN BYPASS A SECTION THE MONITOR SAYS THERE IS A LEAK NOT WHERE, SPLIT THE LOOP AND TEST FIRST FAULT IS SILENT · MONITOR THE LEAKAGE · TREND IT · ACT BEFORE A SECOND FAULT
series loop
insulation defect and leakage
monitor and its trend
loop closed, lights on
The Fact FAA AC 150/5340-26 · IEC 61822

Because an AGL series circuit is not referenced to earth, a single insulation fault does not stop the lights. Ground-fault detection and insulation monitoring exist to find that silent leak early, before a second fault turns it into an outage or a hazard.

1Why the first fault matters

One leak leaves the loop closed, so nothing looks wrong. A second earth fault elsewhere can give current a path through the ground and bypass the section between the two faults, in the same way as a short circuit. Faulted insulation can also put voltage on metalwork or the ground nearby, so a suspected fault is a safety matter.

2Ground-fault detection

The CCR, or a separate unit, senses leakage from the loop to earth and raises a ground-fault alarm when it passes a set level. The alarm goes out through the CCR’s fault indication to the control system. How the leakage is sensed varies between manufacturers.

3Insulation monitoring

Monitoring measures how good the insulation is and follows it over time. A slow fall points to ageing, damage or moisture ingress, and gives a warning before the alarm level. It complements, and does not replace, the periodic insulation resistance test done on an isolated circuit.

4What it cannot do, and what goes wrong

The monitor sees the circuit as a whole, so it says there is a leak, not where. Locating it means isolating the circuit, splitting the loop and testing each section. Wet weather can lower readings and then recover, so trends and sensible levels matter more than one reading. Levels set too loosely hide a real fault, and levels set too tightly cause nuisance alarms. A circuit with no monitor relies entirely on periodic testing.

MethodCircuit stateWhat it tells youLimit
Ground-fault detectionEnergisedLeakage to earth has passed the set levelDoes not say where
Insulation monitoringEnergisedInsulation level and its trendWeather affects readings
Insulation resistance testIsolated, locked out, proved deadInsulation of the loop or a sectionPeriodic only
Section testingIsolated, loop splitWhich section is faultyTakes time and access
Principles summarised from FAA AC 150/5340-26 (maintenance of airport visual aid facilities) and IEC 61822 (constant current regulators). Clause numbers shift between editions, so confirm against the edition in force. The diagram and graph are schematic, with no real values or scale. Sensing method, warning and alarm levels and test voltages come from the CCR manufacturer, the project specification and the airport’s maintenance procedures. Isolate, lock out and prove dead before testing or touching a series circuit.
Entry 20 · Lamp-out behaviour in a series circuit Entry 22 · Primary cable

Frequently Asked Questions

Q1Why does an AGL series circuit need ground-fault detection?

The series loop is not referenced to earth, so a single insulation fault does not stop the lights and nothing looks wrong. A second fault elsewhere can give current a path through the ground and bypass the section between the two faults. Detection finds the first fault while it is still harmless to the lighting.

Q2What is the difference between ground-fault detection and insulation monitoring?

Ground-fault detection raises an alarm when leakage from the loop to earth passes a set level. Insulation monitoring measures the state of the insulation and follows it over time, so a slow decline can be seen and acted on before the alarm level is reached. Some equipment does both.

Q3Does the monitor say where the fault is?

No. It sees the circuit as a whole, so it tells you there is a leak and how serious it is, not which cable, connector or transformer is at fault. Locating it means isolating the circuit, splitting the loop and insulation-testing each section.

Q4Why can rain trigger an insulation alarm?

Moisture can lower the measured insulation for a while and then recover as things dry. That is why a trend, and sensible warning and alarm levels, are more reliable than a single reading. A fall that does not recover is treated as a real fault.

Q5Can insulation be tested with the circuit running?

Monitoring equipment measures an energised circuit, but a full insulation resistance test is done with the circuit isolated, locked out and proved dead. Never test or touch a series circuit that has not been isolated, because the loop carries a hazardous current and voltage.

Q6What should be done when a warning or alarm appears?

Record it, check the trend and the weather, and follow the airport's maintenance procedure. If the fault is real, the circuit is isolated, the section is located by testing, and the repair is re-tested before the circuit returns to service. Warning and alarm levels come from the CCR manufacturer and the project specification.

Precision AGL Academy

See It. Understand It. Then Learn How to Engineer It.

Recognising an AGL system visually is the first step. The next step is knowing how to design, install, test, commission and maintain them correctly.

Build Practical AGL Engineering Skills

Go deeper with structured training from Precision AGL Academy, covering:

AGL Fundamentals Design & Electrical Engineering Approach Lighting Photometry Installation & Commissioning Maintenance & Troubleshooting

Learn how each light, sign and circuit works as part of a complete airport lighting system, not just as an isolated diagram.

See. Understand. Apply. Engineer.