Division 17 of 25 · INS-OBS Series

Obstruction & Associated Lighting Inspection

A standardized inspection methodology for obstruction lighting and associated aerodrome lighting assets that fall outside the main runway/taxiway AGL divisions — obstruction lights and their supporting structures, apron lighting, apron-edge lighting, apron floodlighting, windcone lighting, and windsock assemblies. Covers physical, optical, mechanical, electrical, structural, and environmental condition, together with control, monitoring, and alarm functions where applicable.

12 / 12
Topics Published
INS-OBS-1398 → 1516
Inspection ID Range
15
Sections A–O
Rev 0
Initial Issue

Critical control — Obstruction and associated lighting should be inspected according to the specific function and installation type of each asset. A single inspection criterion should not automatically be applied to all assets, because obstruction lights, apron floodlights, and windcone systems have different operational purposes and performance requirements. This division is kept separate from the main runway/taxiway AGL inspection divisions because these assets have different functions and different inspection priorities.

Illumination alone does not establish compliance — an obstruction light being ON does not necessarily mean correct intensity/characteristic, correct visibility, and correct structural installation. A windcone light being ON does not necessarily mean the windsock assembly is serviceable and clearly visible/moving correctly. Particular attention should be given to obstruction-light availability, flashing characteristics where applicable, lens/optical contamination, visibility, structural corrosion, mounting/support integrity, cable and power connections, apron floodlight aiming, apron-edge-light condition, windcone lighting, windsock fabric and support, vegetation/environmental encroachment, and failure monitoring/alarms.

Division 17 · Obstruction & Associated Lighting Topics

12 of 12 topics published
INS-OBS-1398 Obstruction-Light Condition Inspection
What's Inspected

Inspection of the complete obstruction-light installation for physical, mechanical, and environmental condition, and verification of light identification, location, structure association, asset records, and correspondence with the approved application/design.

Inspection Points
  • Identification, location, and structure association
  • Type verification against approved application/design
  • Cracks, deformation, impact damage, broken components, deterioration
  • Dust, dirt, insects, bird deposits, oil, chemical contamination
  • Effects of weather, moisture, temperature, corrosion, wind
Classify As
Normal Defective Unserviceable Immediate Action Required
INS-OBS-1404 Obstruction-Light Illumination Inspection
What's Inspected

Verification of normal visible light output, applicable ON/OFF operating state, brightness/intensity, flashing operation and flash characteristic where required, applicable colour, visibility from relevant operational viewpoints, and review of applicable photometric/test records.

Inspection Points
  • Normal visible light output and applicable operating state
  • Visibly abnormal brightness/intensity
  • Flashing operation and flash characteristic where specified
  • Applicable light colour
  • Visibility from relevant operational viewpoints
  • Applicable inspection and test record review
Classify As
Normal Defective Unserviceable Immediate Action Required
INS-OBS-1412 Obstruction-Light Lens & Optics Inspection
What's Inspected

Inspection of lens/optical window and applicable optical component condition, including cracking, contamination, discoloration, internal condensation, and evidence of water entering the fixture.

Inspection Points
  • Cracks, chips, fractures, or other lens damage
  • Dirt, dust, bird deposits, insects, other contamination
  • Clouding, yellowing, browning, abnormal colour change
  • Applicable optical component condition
  • Moisture/condensation inside the optical assembly
  • Evidence of water entering the fixture
Classify As
Normal Defective Unserviceable Immediate Action Required
INS-OBS-1419 Obstruction-Light Mounting Inspection
What's Inspected

Inspection of the mechanical mounting arrangement, mounting hardware, fixture stability, applicable orientation, alignment, excessive movement/vibration where relevant, and corrosion of mounting hardware and fixture components.

Inspection Points
  • Bolts, nuts, brackets, clamps, associated hardware
  • Secure mounting and fixture stability
  • Applicable fixture orientation
  • Movement or misalignment
  • Excessive movement or vibration where relevant
  • Corrosion of mounting hardware and fixture components
Classify As
Normal Defective Unserviceable Immediate Action Required
INS-OBS-1426 Obstruction-Light Cable Inspection
What's Inspected

Inspection of cables associated with obstruction lighting, including routing and mechanical protection, insulation condition, mechanical damage, cable supports and attachment, cable entry into the fixture/equipment, and applicable cable-entry sealing.

Inspection Points
  • Suitable routing and mechanical protection
  • Visible insulation deterioration or damage
  • Cuts, abrasion, crushing, bending, impact damage
  • Cable supports, clamps, attachment arrangements
  • Cable entry into the fixture/equipment
  • Applicable cable-entry sealing
Classify As
Normal Defective Unserviceable Immediate Action Required
INS-OBS-1433 Obstruction-Light Power Connection Inspection
What's Inspected

Inspection of the electrical power connection, accessible terminals, applicable power-cable termination, power-supply status, electrical protection, protective earthing/bonding, and applicable power-failure monitoring/alarm functionality, including command/feedback consistency where remotely controlled or monitored.

Inspection Points
  • Accessible terminals and connections
  • Applicable power-cable termination
  • Applicable power-supply status
  • Applicable electrical protection
  • Applicable protective earthing and bonding
  • Power-failure monitoring/alarm functionality
  • Command/feedback consistency where remotely controlled or monitored
Classify As
Normal Defective Unserviceable Immediate Action Required
INS-OBS-1440 Structural-Support Condition Inspection
What's Inspected

Inspection of the structure supporting obstruction lighting, including corrosion and material deterioration, cracks/deformation/impact damage, accessible fasteners, the supporting foundation, base plates/brackets, verticality, applicable lightning-protection arrangements, structure-mounted cable supports, and effects of wind, weather, corrosion, and pollution.

Inspection Points
  • Corrosion and material deterioration
  • Cracks, deformation, impact damage, structural defects
  • Accessible bolts, nuts, clamps, structural fasteners
  • Supporting foundation and base plates/brackets
  • Abnormal movement, leaning, settlement, deformation
  • Applicable lightning-protection arrangements
  • Cable supports attached to the structure
Classify As
Normal Defective Unserviceable Immediate Action Required
INS-OBS-1450 Apron-Lighting Condition Inspection
What's Inspected

Inspection of apron lighting installations and individual fixtures, including general illumination condition, fixture orientation/aiming, mounting arrangements and stability, associated cables and cable entries, applicable connectors, lenses/optical surfaces, corrosion, moisture/water entry, contamination, and applicable local or remote control.

Inspection Points
  • General illumination condition
  • Fixture orientation and aiming
  • Mounting arrangements and stability
  • Associated cables, cable entries, and applicable connectors
  • Lenses and optical surfaces
  • Corrosion, water-ingress, and contamination (dust, dirt, fuel/oil, bird deposits)
  • Applicable local or remote control arrangements
Classify As
Normal Defective Unserviceable Immediate Action Required
INS-OBS-1461 Apron-Edge-Lighting Condition Inspection
What's Inspected

Inspection of apron-edge lighting fixtures, including applicable installation location, fixture orientation, normal illumination, fixture stability and mounting hardware, optical surfaces, cable entry/condition, connectors, base/base-can and pavement interface, and impact or mechanical damage.

Inspection Points
  • Applicable installation location
  • Fixture orientation and normal illumination
  • Fixture stability and mounting hardware
  • Optical surfaces (lens)
  • Cable entry/condition and connectors
  • Base/base-can and pavement interface
  • Impact or mechanical damage
Classify As
Normal Defective Unserviceable Immediate Action Required
INS-OBS-1471 Apron-Floodlight Condition Inspection
What's Inspected

Inspection of floodlighting equipment, including normal light output, fixture aiming and orientation, poles/brackets/mounting hardware and stability, lens/optical condition, contamination, power and control cables, electrical connections and supply condition, applicable local or remote control arrangements, and supporting structure corrosion/deterioration.

Inspection Points
  • Normal light output
  • Fixture aiming and orientation
  • Poles, brackets, mounting hardware, and stability
  • Lens/optical condition and contamination
  • Power and control cables, electrical connections and supply
  • Applicable local or remote control arrangements
  • Structural corrosion and deterioration
Classify As
Normal Defective Unserviceable Immediate Action Required
INS-OBS-1482 Windcone-Lighting Condition Inspection
What's Inspected

Inspection of lighting associated with the windcone/windsock system, including normal illumination, mounting arrangements, applicable fixture orientation, optical surfaces, cable condition and routing, electrical supply and connections, moisture/water entry, corrosion, applicable control arrangements, and vegetation affecting windsock visibility or movement.

Inspection Points
  • Normal illumination and applicable fixture orientation
  • Mounting arrangements
  • Optical surfaces (lens)
  • Cable condition, routing, and power connection
  • Water-ingress and corrosion
  • Applicable local or remote control arrangements
  • Vegetation affecting windsock visibility or movement
Classify As
Normal Defective Unserviceable Immediate Action Required
INS-OBS-1491 Windsock-Assembly Condition Inspection
What's Inspected

Inspection of the complete windsock assembly, including fabric/seams/colour/tearing/fading/contamination/deterioration, visibility under applicable operating conditions, mounting arrangements, support poles/brackets/arms, free movement/rotation, mechanical damage, foundation condition where accessible, associated cables and lighting connections, and effects of corrosion, weathering, contamination, and vegetation encroachment.

Inspection Points
  • Fabric, seams, colour, tearing, fading, contamination, deterioration
  • Visibility under applicable operating conditions
  • Mounting arrangements and support poles/brackets/arms
  • Applicable free movement/rotation
  • Broken, bent, cracked, or damaged components
  • Foundation condition where accessible
  • Associated cables and lighting connections
  • Corrosion, weathering, contamination, vegetation encroachment
Classify As
Normal Defective Unserviceable Immediate Action Required
No topics match your search.

Division-Wide Requirements

Standard parameters, classification, minimum record content, and inspection workflow that apply across obstruction lighting, structural supports, apron lighting/edge-lighting/floodlighting, windcone lighting, and windsock assemblies.

ParameterInspection Status
Asset IdentificationCorrect / Incorrect / Missing
Fixture ConditionGood / Damaged
IlluminationNormal / Abnormal
ColourNormal / Abnormal
FlashingNormal / Abnormal / N/A
Flash CharacteristicCorrect / Abnormal / N/A
VisibilityGood / Restricted
LensGood / Damaged / Contaminated
MountingSecure / Deficient
OrientationCorrect / Misaligned
CableGood / Damaged
Cable EntryGood / Deficient
Power ConnectionGood / Deficient
Earthing/BondingGood / Deficient / N/A
Structural SupportGood / Defective
FoundationGood / Defective / N/A
CorrosionNone / Present
Water/MoistureNone / Present
Environmental ConditionGood / Deficient
Apron LightingNormal / Defective / N/A
Apron Edge LightingNormal / Defective / N/A
Apron FloodlightingNormal / Defective / N/A
Windcone LightingNormal / Defective / N/A
WindsockGood / Damaged
Windsock MovementNormal / Restricted
Control/MonitoringNormal / Defective / N/A
AlarmNormal / Abnormal / N/A
Defect StatusNormal / Defective / Unserviceable / Immediate Action Required

A. Standard Inspection Classification

Every observation should be assigned an appropriate status:

NormalEquipment/condition satisfactory and operating as expected.

DefectiveAbnormality or defect identified but equipment remains operational or condition does not require immediate withdrawal.

UnserviceableEquipment or system is not available for its intended function.

Immediate Action RequiredCondition presents an operational, electrical, safety, or airside risk requiring immediate escalation/action.

B. Minimum Inspection Record

Each obstruction/associated-lighting inspection record should include:

  • Date and inspection time
  • Inspector name and designation
  • Asset type and location/structure association
  • Asset identification reference
  • Inspection observation
  • Status classification per parameter
  • Defect description, where applicable
  • Immediate action taken
  • Person/department notified
  • Corrective-action reference
  • Structural/foundation repair reference, where applicable
  • Closure date/time and sign-off

C. Standard Inspection Workflow

Obstruction Light
IDENTIFY ASSET VERIFY LOCATION/TYPE INSPECT FIXTURE CHECK LENS CHECK ILLUMINATION CHECK COLOUR CHECK FLASHING CHECK VISIBILITY INSPECT MOUNTING INSPECT CABLE INSPECT POWER CONNECTION CHECK EARTHING INSPECT STRUCTURE CHECK CORROSION CHECK WATER/MOISTURE CHECK CONTROL/ALARM RECORD CORRECT REINSPECT CLOSE
Apron Lighting
IDENTIFY ASSET INSPECT FIXTURE CHECK ILLUMINATION CHECK AIMING CHECK LENS INSPECT MOUNTING INSPECT CABLE CHECK POWER CHECK CONTROL INSPECT STRUCTURE/BASE CHECK CORROSION/CONTAMINATION RECORD CORRECT REINSPECT CLOSE
Windcone / Windsock
IDENTIFY ASSEMBLY INSPECT WINDSOCK FABRIC CHECK VISIBILITY CHECK SUPPORT CHECK ROTATION/MOVEMENT INSPECT LIGHTING CHECK CABLE CHECK POWER INSPECT FOUNDATION CHECK CORROSION CHECK VEGETATION/ENVIRONMENT RECORD CORRECT REINSPECT CLOSE

Frequently Asked Questions

Quick answers about obstruction & associated lighting inspection in the AGL Inspection Handbook.

Q1What is Division 17 — Obstruction & Associated Lighting Inspection in the AGL Inspection Handbook?

Division 17 contains 12 published topics in 15 sections (A–O). It gives a standardized inspection methodology for obstruction lighting and associated aerodrome lighting assets that fall outside the main runway and taxiway AGL divisions, including their supporting structures.

Q2Which assets does Division 17 cover?

It covers obstruction lights and their supporting structures, apron lighting, apron-edge lighting, apron floodlighting, windcone lighting and windsock assemblies. It considers physical, optical, mechanical, electrical, structural and environmental condition, together with control, monitoring and alarm functions where applicable.

Q3Does an obstruction light being on mean it is compliant?

No. Illumination alone does not establish compliance. An obstruction light being on does not necessarily mean the intensity or characteristic, visibility and structural installation are correct, and a windcone light being on does not necessarily mean the windsock assembly is serviceable, visible and moving correctly.

Q4What parameters are recorded for obstruction and associated lighting?

The checklist includes asset identification, fixture condition, illumination, colour, flashing and flash characteristic, visibility, lens, mounting, orientation, cable and cable entry, power connection, earthing/bonding, structural support, foundation, corrosion, water/moisture, apron lighting types, windcone lighting, windsock condition and movement, control/monitoring and alarms.

Q5What status classifications are used in this division?

Every observation is assigned one of four statuses. Normal means the equipment or condition is satisfactory and operating as expected. Defective means an abnormality or defect exists but the equipment remains operational or the condition does not require immediate withdrawal. Unserviceable means the equipment or system is not available for its intended function. Immediate Action Required means the condition presents an operational, electrical, safety or airside risk requiring immediate escalation and action.

Q6What should an obstruction or associated-lighting inspection record include?

Alongside the usual date, inspector, observation, status, action and sign-off fields, the record includes the asset type and its location or structure association, the asset identification reference, and a structural or foundation repair reference where applicable.

Q7Do airport procedures take precedence over this handbook?

Yes. This handbook is an uncontrolled educational reference, not an approved procedure. The airport's approved inspection schedule, SMS procedures, ATC instructions, NOTAM procedures and local aerodrome regulations always take precedence, and the current revision of any official document should be verified before use.

Q8Can I download a printable checklist for each inspection topic?

Yes. Each inspection topic has a Download as Word option that produces an uncontrolled Word checklist template (description, a tick-box inspection table and an inspector sign-off block) for personal reference and internal training, to be reviewed and adopted under the user’s own document control.

Precision AGL Academy

Don't Just Inspect Obstruction Lights. Understand the System.

Obstruction and associated lighting inspection is where hazard-marking condition awareness begins. Go beyond identifying defects and build the technical knowledge to understand why abnormalities occur, how they affect system serviceability, and when further testing, troubleshooting, maintenance or corrective action is required.

Build Practical AGL Inspection & Maintenance Capability

Develop structured knowledge across:

AGL Fundamentals Components Inspection Electrical Systems Photometry Testing Troubleshooting Maintenance Commissioning

Learn to connect the inspection process with the wider AGL engineering lifecycle.

Inspect with purpose. Understand the system. Act with technical confidence.