Cable Sections
| Section / description | Conductor | Length (m) | Loss at full (W) |
|---|
Rule note
Used by any section set to "Custom". Take it from your cable data sheet.
Brightness Steps & Operating Time
Rule note
Hours the circuit is energised, on any step. The 4,000 h shown is a placeholder; use your own airfield operating profile.
| Step | Current (A) | Share of hours (%) |
|---|
Rule note
For example from Calculator #13. Real power of the lamps and transformers, not including the cable loss. Used to show the cable loss as a share of the load. Leave 0 to skip.
Report details
Loss by Brightness Step
| Step | Current (A) | Loss (W) | Of full-brightness loss | Hours / year | Energy (kWh) |
|---|
Build-up
Conductor Comparison
The whole loop length re-run in a single conductor size, with the same steps and hours. The last column is the change against the design above.
| Conductor | Loop resistance (Ω) | Loss at full (W) | Energy (kWh / yr) | Change vs design |
|---|
How the loss is calculated
Every step is shown so the result can be checked by hand.
1. Loop resistance
Each section's resistance comes from the conductor's nominal Ω/km at 20 °C, corrected for temperature, then the sections are added.
2. Loss at each step
The same current flows through the whole series loop, so each section's loss adds directly.
Halving the current cuts the loss to a quarter, so the lower steps lose much less than full brightness.
3. Yearly energy and cost
Hours on each step are the operating hours multiplied by that step's share.
4. Share of load and heat per metre
Worked example
| Item | Value |
|---|---|
| #8 AWG, 3,000 m loop, 20 °C | R = 6.306 Ω |
| Loss at 6.6 A | 274.7 W |
| Loss at 5.2 A | 170.5 W |
| Loss at 2.8 A | 49.4 W |
| Heat per metre at 6.6 A | 0.092 W/m |
| Share of a 5 kW load | 5.49 % |
| Energy, 4,000 h at default shares | 440.5 kWh |
What this tool does not do
It does not calculate voltage drop (see Calculator #15), include the isolating transformer or fixture losses, connectors, splices or reactance, or cover aluminium conductors. Resistance values are nominal DC figures, so confirm them against your cable data sheet. AWG sizes use nominal stranded-copper values at 20 °C (ASTM B3/B8 basis, about 2 % above the ideal-copper figures); metric sizes use the IEC 60228 Class 2 maximum.