Calculator #15

Cable Voltage Drop

Voltage drop and I²R loss along a primary AGL cable run from conductor size, length, temperature and series current.

About this calculator

In a series circuit the same current flows through the whole cable, so the drop is simply current times the total loop resistance. Add each cable segment, and the tool reports the drop, the power lost as heat, the drop as a share of the load voltage, and how the other conductor sizes would compare. In a constant-current series circuit the lamps still receive the set current: the cable drop appears as extra voltage the CCR must supply, not as dimmer lamps.

Cable Segments

Section / descriptionConductorLength (m)Drop (V)
Rule note

Add one row per cable section. Lengths are the total loop cable in that section (out and back). For a one-way route, enter double the route length.

Circuit Parameters

Full-brightness series current.
Rule note

Copper resistance rises about 0.393 % per °C above 20 °C. Use the expected conductor temperature.

Rule note

Voltage across the load, excluding the cable drop calculated here. If your figure is already the CCR output including the cable, read the drop percentage only and ignore the last result card. Leave 0 to skip the percentage checks. The 850 V shown is only a placeholder; estimate your own as load kVA × 1000 ÷ circuit current (Calculator #13).

Your project's own design limit, not a standard value.
FAQ

Cable Voltage Drop Calculator: Frequently Asked Questions

Quick answers on voltage drop and I squared R loss along a primary AGL cable run.

What does the Cable Voltage Drop calculator do?

It calculates voltage drop and I squared R loss along a primary AGL cable run from conductor size, length, temperature and series current. In a series circuit the same current flows through the whole cable, so the drop is the current times the total loop resistance. It also reports the drop as a share of the load voltage and compares the other conductor sizes.

How is the section resistance worked out?

Each section's resistance comes from the conductor's nominal resistance per km at 20 degrees C, corrected for temperature and scaled by length. Copper resistance rises about 0.393 percent per degree C above 20, so the correction is 1 plus 0.00393 times the temperature minus 20. Use the expected conductor temperature.

Should the length be one-way or the whole loop?

Enter the total loop cable in each section, which is out and back. For a one-way route, enter double the route length. Add one row per cable section, and the section values add directly because the series current is the same in every section.

How are the drop and the loss calculated?

Voltage drop is the circuit current times the sum of the section resistances, and cable power loss is the current squared times that resistance. The loss is lost as heat. Enter the full-brightness series current.

What are the load voltage and maximum drop settings?

The load voltage is optional and is the voltage across the load, excluding the cable drop calculated here. The 850 V shown is only a placeholder, so estimate your own as load kVA times 1,000 divided by circuit current. The maximum drop is your project's own design limit, not a standard value. Leave the load voltage at 0 to skip the percentage checks.

What does the conductor comparison show?

It re-runs the whole loop length in a single conductor size and shows the resistance, drop, drop percentage and loss for each. The last column is the longest loop that stays within your drop limit. It assumes one conductor size over the whole loop.

Can you give a worked example?

A #8 AWG loop of 3,000 m at 20 degrees C has a resistance of 6.306 ohms. At 6.6 A the drop is 41.6 V and the cable loss is 275 W. Against a load voltage of 850 V that is a drop of 4.90 percent, and the longest loop at a 5 percent limit is 3,063 m.

What does the tool not do?

It does not include cable reactance, secondary cable tails, connectors or the effect of brightness steps. Resistance values are nominal DC figures, so confirm them against your cable data sheet. Final design shall be verified against the cable manufacturer's data and the applicable project specification.