Cable Segments
| Section / description | Conductor | Length (m) | Drop (V) |
|---|
Rule note
Add one row per cable section. Lengths are the total loop cable in that section (out and back). For a one-way route, enter double the route length.
Circuit Parameters
Rule note
Copper resistance rises about 0.393 % per °C above 20 °C. Use the expected conductor temperature.
Rule note
Voltage across the load, excluding the cable drop calculated here. If your figure is already the CCR output including the cable, read the drop percentage only and ignore the last result card. Leave 0 to skip the percentage checks. The 850 V shown is only a placeholder; estimate your own as load kVA × 1000 ÷ circuit current (Calculator #13).
Report details
Build-up
Conductor Comparison
The whole loop length re-run in a single conductor size. The last column is the longest loop that stays within your drop limit.
| Conductor | Resistance (Ω) | Drop (V) | Drop (%) | Loss (W) | Max length at limit (m) |
|---|
How the drop is calculated
Every step is shown so the result can be checked by hand.
1. Section resistance
Each section's resistance comes from the conductor's nominal resistance per km at 20 °C, corrected for temperature and scaled by length.
2. Drop and loss
The series current is the same in every section, so the section values add directly.
3. Share of load voltage
Compared with your design limit. If a load voltage is not entered, only the volts and watts are reported.
4. Maximum length at the limit
Here k_T is the temperature factor 1 + 0.00393 × (T − 20). This assumes one conductor size over the whole loop.
Worked example
| Item | Value |
|---|---|
| #8 AWG, 3,000 m loop, 20 °C | R = 6.306 Ω |
| Circuit current | 6.6 A |
| Voltage drop | 41.6 V |
| Cable loss | 275 W |
| Load voltage | 850 V |
| Drop share | 4.90 % |
| Longest loop at 5 % | 3,063 m |
What the drop means in a series circuit
The CCR holds the current constant, so a larger cable drop does not dim the lamps. It raises the output voltage the CCR must supply (load voltage plus drop, before any margin) and so the kVA it must deliver, and it adds heat in the cable. Compare the sum with the rated output voltage and kVA of the CCR.
What this tool does not do
It does not include cable reactance, secondary cable tails, connectors or the effect of brightness steps. Resistance values are nominal DC figures, so confirm them against your cable data sheet. AWG sizes use nominal stranded-copper values at 20 °C (ASTM B3/B8 basis, about 2 % above the ideal-copper figures); metric sizes use the IEC 60228 Class 2 maximum.