CCR Class, Steps & Cable
Step Currents
Check a Measured Current
How to Read This Table
Percent of full current
This is a share of current, not of light. Light output falls much faster than current, and the relationship depends on the lamp or LED driver, so use the fixture photometric data for actual intensity.
Cable drop and loss by step
Cable loss follows the square of the current, so it is about 18% of the full-brightness value at 2.8 A (6.6 A class). This applies to the cable only; lamp and transformer loads change with current.
Step names
Five-step CCRs label the steps B1 to B5. Three-step units are commonly labelled B10, B30 and B100 on the control side; the name for each step can differ between makers.
Power factor at low steps
Input power factor and efficiency fall at low brightness, by an amount that depends on the CCR design and loading. Use the data sheet for your model, at the loading you expect, when sizing the supply.