Calculator #37

Runway & Taxiway Lighting Load / Power

Runway and taxiway lighting load and power, circuit by circuit, from fixture counts and primary cable lengths, in kW and kVA.

About this calculator

List each series circuit, say whether it serves the runway or the taxiway, and enter the fixtures and cable on it. The tool adds fixture load, isolating transformer losses and cable I²R loss for every circuit, then reports kW and kVA for the runway, the taxiway and the whole airfield lighting system, with a CCR loading check on each circuit.

Quick start

Series Circuits

How to fill in this table

One row per CCR circuit. Current is the CCR output at full brightness, normally 6.6 A, so it matches the fixture watts entered below. Loop cable is the full series loop out and back, that is the total primary cable in the circuit. Leave it at 0 to ignore cable loss.

CircuitSystemCurrent (A)Primary cableLoop cable (m)CCR rating

Fixture Load

How to fill in this table

Enter the power each fixture draws at full brightness (the 6.6 A step), from the manufacturer's data sheet, and the circuit it is on. The values shown are placeholders typical of incandescent edge lights; LED fixtures draw much less.

CircuitFixture type / descriptionQuantityWatts each (W)Subtotal (W)

Assumptions & Limits

Rule note

Planning assumption applied to every fixture. FAA AC 150/5345-47 minimums are 80 % for 30/45 W and 65 W, 85 % for 100 W and 150 W, and 90 % for 200 W and above, so 90 % is optimistic for the small sizes. Replace it with data sheet values.

Rule note

Used to convert kW to kVA and to estimate output voltage. Planning assumption. FAA requires at least 0.95 for transformers at rated load. Use the measured value for LED fixtures, which often differ from incandescent loads.

Rule note

Copper resistance rises about 0.393 % per °C above 20 °C.

Rule note

Your project's own design rule, not a standard value.

FAQ

Runway & Taxiway Lighting Load / Power Calculator: Frequently Asked Questions

Quick answers on circuit-by-circuit lighting load and power for the runway, taxiway and whole system.

What does the Runway & Taxiway Lighting Load / Power Calculator do?

It works out runway and taxiway lighting load and power, circuit by circuit, from fixture counts and primary cable lengths. For every circuit it adds fixture load, isolating transformer losses and cable I squared R loss, then reports kW and kVA for the runway, the taxiway and the whole airfield lighting system, with a CCR loading check on each circuit.

How do I fill in the circuit table?

Use one row per CCR circuit, say whether it serves the runway or the taxiway, and enter the current, the primary cable and the CCR rating. The current is the CCR output at full brightness, normally 6.6 A, so it matches the fixture watts entered. The loop cable is the full series loop, out and back, and you leave it at 0 to ignore cable loss. Then enter the fixture types, quantities and watts for each circuit.

How is each circuit's load built up?

The fixture load is the sum of quantity times watts. The transformer loss comes from dividing the fixture load by the transformer efficiency. The cable loss is the current squared times the loop resistance, corrected for temperature. The circuit total is the transformer-side load plus the cable loss.

How are kVA, voltage and the totals worked out?

The apparent power is the real power divided by the power factor, and the approximate output voltage is that kVA divided by the current. The voltage is an approximation for quick checking and is not a substitute for a voltage drop check. The runway, taxiway and system totals are the sums of the circuits, and the kVA values add in the same way because one power factor is applied to every circuit.

How does the CCR check work?

Each circuit's apparent power in kVA is compared with the CCR nameplate rating you selected, which is the conservative reading, since FAA CCRs are rated in kW and IEC 61822 CCRs in kVA. The maximum loading is your project's own design rule, not a standard value. The smallest standard CCR that fits within your loading limit is also shown.

Which assumptions should I replace?

The transformer efficiency of 90 percent is a planning assumption. FAA AC 150/5345-47 minimums are 80 percent for 30/45 W and 65 W, 85 percent for 100 W and 150 W, and 90 percent for 200 W and above, so 90 percent is optimistic for the small sizes. FAA requires at least 0.95 power factor for transformers at rated load, but LED fixtures often differ, so use the measured value. The example fixture watts are placeholders typical of incandescent edge lights.

Can you give a worked example?

Runway circuit R1 has 100 fixtures of 45 W at 90 percent efficiency, which is 5,000 W, plus 359 W of cable loss on 4,000 m of #8 AWG. That is 5.36 kW or 5.64 kVA at power factor 0.95, and 75 percent of a 7.5 kVA CCR. Taxiway circuit T1 has 60 fixtures of 30 W, which is 2,000 W plus 269 W of cable loss on 3,000 m, giving 2.27 kW or 2.39 kVA, and 60 percent of a 4 kVA CCR. The system total is 7.63 kW and 8.03 kVA.

What does the tool not do?

The load shown is at the CCR output and not the supply demand, because the CCR's own losses and input power factor are not included. It does not size cable for voltage drop or insulation, model brightness steps, or account for secondary cable, connectors or lamp-out conditions. Stop bars, guard lights, approach lighting and signs go in as fixture rows, as long as you enter their watts. Use Calculators #15 and #36 for cable drop and size, and verify the final design against manufacturer data and the applicable standards.