AGL Component Library By Precision AGL Academy

CAT I Approach Lighting

A precision approach lighting system for Category I operations, typically configured to ICAO (900m precision approach CAT I system) or FAA (731m/2,400 ft MALSR or ALSF‑1, extendable to 914m/3,000 ft) standards, using barrettes and sequenced flashing lights. It provides pilots with essential visual guidance for approaches down to a 200ft decision height and 550m (1,800 ft) RVR, forming the foundation for reliable low‑visibility operations at thousands of airports worldwide.

CAT I Approach Lighting System

Image disclaimer: For identification and illustration only. It may show a product by another manufacturer and may not depict the exact item described; it is not a statement of any product’s quality, approval or performance. Third-party image and trademark rights belong to their owners. See full notice.

Overview

What Is It?

CAT I Approach Lighting is a precision approach lighting system designed to support Category I instrument approaches. It consists of a series of light bars (barrettes) and sequenced flashing lights (SFL) extending from the runway threshold into the approach area. The system provides both horizontal and vertical guidance, helping pilots maintain the correct approach path and align with the runway centreline. CAT I systems typically have a configuration length of 900 metres under the ICAO precision approach CAT I standard, or 731 metres (2,400 ft) – extendable to 914 metres/3,000 ft on shallow-slope sites – under the FAA MALSR/ALSF‑1 standard, depending on the airfield requirements and the specific standards applied. They support approaches with a decision height of 200 feet and RVR down to 550 metres (1,800 ft).

Purpose

Purpose & Function

CAT I approach lighting exists to make instrument approaches down to a 200-foot decision height and reduced visibility genuinely flyable, by combining horizontal alignment cues (barrettes, centreline) with directional depth cues (sequenced flashing lights) into a single coherent system rather than relying on either type of guidance alone. Its purpose is calibrated specifically to CAT I minimums: providing enough visual structure that a pilot can reliably transition from instruments to visual reference at 200 feet and confirm the runway environment is in sight, without the additional redundancy, red side-row bars, and enhanced intensity that CAT II/III demand for their lower minimums. This makes it the standard configuration wherever an airport wants to support routine low-visibility operations without the substantially higher infrastructure and reliability requirements of the more advanced categories.

Application

Where Is It Used?

CAT I approach lighting systems are installed at airports that support Category I precision approaches. They are typically used on:

  • Precision approach runways with CAT I capability (200ft DH, 550m (1,800 ft) RVR minimum)
  • Regional and international airports that handle commercial air traffic
  • Military airbases requiring all‑weather precision approach capability
  • Runways with moderate traffic volumes that still require reliable low‑visibility operations
  • Airports transitioning to higher CAT (CAT II/III) where CAT I serves as the baseline
Placement

Installation & Location

Fixtures are set out along the extended runway centreline beginning at the threshold, on frangible light stands graded to follow the required approach slope over the 720 m or 900 m configuration length. Barrette stands are positioned at the specified 60 m or 100 m spacing, with the sequenced flashing light heads on their own dedicated stands in line with the centreline. Where the approach area crosses roads, drainage, or uneven terrain, fixtures are elevated on piers or piled structures to keep the array on a consistent plane. Steady-burning and SFL circuits are cabled separately in duct back to their own constant current regulators. Setting-out is tied to the extended centreline and threshold survey to keep the array true to the final approach course.

Function

How Does It Work?

The CAT I approach lighting system operates through a combination of steady‑burning barrettes and sequenced flashing lights:

  • Barrettes: A series of light bars (typically 3 to 5 lights per bar) positioned at regular intervals — 30m (100 ft) on FAA ALSF‑1 or the ICAO barrette section, 61m (200 ft) on FAA MALSR — along the approach path. These provide distance and lateral guidance.
  • Sequenced Flashing Lights (SFL): A row of lights that flash in sequence from the outer end toward the threshold, creating a "rolling" effect that indicates the approach direction and helps pilots maintain the correct glide slope.
  • Centreline Barrette: A short row of lights on the approach centreline, providing precise lateral guidance and helping pilots align with the runway.
  • Crossbar Lights: Additional lights perpendicular to the approach path, providing lateral and distance reference.
  • Intensity Control: The entire system is controlled by CCRs with multiple intensity steps (typically 5 steps), allowing the ATC to adjust brightness for visibility conditions. Higher intensities are used during low visibility.
Architecture

System Architecture & Control Logic

A CAT I approach lighting installation is really two control systems sharing one approach corridor. The steady-burning elements — barrettes, crossbar, and centreline barrette — sit on a constant current series circuit: the ALCMS selects the required brightness step from RVR data or ATC instruction, the CCR regulates the whole loop to a single fixed current, and every steady fixture on that loop, fed through its own isolating transformer, burns at the same intensity simultaneously. The sequenced flashing lights are driven separately by a flasher/sequencer controller that discharges through each SFL lamp in strict outer-to-threshold order to create the rolling effect; the ALCMS commands its intensity tier in step with the steady loop, but the two subsystems are electrically independent, so a fault on one does not affect the other. Fault detection on the steady loop remains loop-based: the CCR monitors loop voltage against commanded current, and a voltage rise flags an open circuit or failed isolating transformer as a loop fault rather than a specific fixture.

ALCMS commands both the steady CCR loop and the SFL sequencer independently

AIRFIELD LIGHTING CONTROL SYSTEM (ALCMS) Selects brightness step (RVR / ATC) for both subsystems CONSTANT CURRENT REGULATOR Converts step command to fixed loop current STEADY-FIXTURE SERIES CIRCUIT LOOP Feeds barrettes, crossbar and centreline together ISOLATING TRANSFORMER (PER FIXTURE) Taps fixed loop current to each steady fixture SFL FLASHER / SEQUENCER CONTROLLER Capacitor-discharge, fires lamps in timed order BARRETTES / CROSSBAR / CENTRELINE Steady-burning — all fixtures at one intensity SEQUENCED FLASHING LIGHTS Outer lamp to threshold, creating the rolling effect APPROACH LIGHT PATTERN TO PILOT Steady bars and rolling flash combine into one visual cue TWO INDEPENDENT SUBSYSTEMS, ONE COMBINED VISUAL CUE
Layout Logic

Approach Layout — Barrettes, Crossbar & SFL

731m/900m Mid-Approach Threshold Centreline Barrettes — 60m/100m Spacing Crossbar Lateral & distance reference SFL — Sequenced Flashing "Rolls" Toward Threshold Runway CCR — 5-Step Control
Centreline barrettes / circuit
Crossbar (lateral reference)
Runway threshold
Construction

Physical Construction

Barrette stands are frangible structures, each carrying multiple lamp housings mounted side-by-side on a rigid bar, with the bar height and stand base graded to keep the whole array on the required approach slope; die-cast aluminium housings behind toughened, gasket-sealed lenses achieve an IP67/IP68 rating on each lamp. The sequenced flashing light heads are a separate assembly — a xenon strobe tube and trigger electronics in a weatherproof dome, backed by a capacitor bank at the base of the stand, engineered to deliver the discharge pulse for each flash in the outer-to-threshold sequence. Where the approach area crosses roads, drainage, or uneven terrain, stands are raised on piers or piled steel structures engineered to keep the barrette bars level and coplanar. Internal wiring for both steady and SFL circuits terminates at L-823 primary connectors sealed for direct burial, feeding separate isolating transformers and regulators so a fault on one circuit cannot extinguish the other. Stainless-steel fasteners and corrosion-resistant finishes are used throughout to withstand prolonged outdoor exposure along the extended approach.

Specification

Technical Parameters

ParameterTypical Value
System TypeCAT I precision approach lighting
Light SourceLED array or halogen (100W – 200W)
ColourWhite (steady and flashing)
Configuration Length900m (ICAO standard) / 731m–914m, 2,400–3,000 ft (FAA standard: MALSR/ALSF‑1)
Barrette Spacing30m/100 ft (FAA ALSF‑1 or ICAO barrette section) or 61m/200 ft (FAA MALSR)
Sequenced Flashing LightsFlashing in sequence from outer end to threshold
Intensity Steps5‑step (2.8A – 6.6A) CCR controlled
Beam PatternUni‑directional towards approach
Mounting TypeElevated or flush‑mounted (inset)
Isolating Transformer100W – 200W (6.6A series circuit)
Protection ClassIP67 / IP68 (submersible)
SupportCAT I precision approach (200ft DH, 550m (1,800 ft) RVR)
Power Supply

Electrical Requirements

RequirementTypical Value
Circuit TypeSeries circuit (CCR fed) for steady/barrette lights; separate discharge circuit for sequenced flashing lights (SFL)
Rated Series Current6.6A (5-step: 2.8A / 3.4A / 4.1A / 5.2A / 6.6A) on the steady circuit
IsolationDedicated isolating transformer (100W – 200W) per steady fixture; SFL heads fed from a dedicated capacitor-discharge unit
Transformer SecondaryMatched to fixture wattage; sized to series circuit rating
SFL Power SupplyCapacitor-discharge trigger unit driving xenon strobe tubes in sequence, synchronised by a flasher controller
Cable TypeL-824 single-conductor, direct-burial rated, 5kV or 600V per circuit design; shielded trigger cable for SFL synchronisation
ConnectorL-823 primary connector, submersible-rated splice
Insulation Resistance≥ 50 MΩ (megger test, cable-to-ground)
Earthing/GroundingFixture body, stands, and base cans bonded to airfield earth grid
Fault ProtectionCCR-level ground fault and open-circuit detection on the steady circuit; independent fault/health monitoring on the SFL controller
Power SourceCCR output for steady lights, regulated per ICAO/FAA intensity step schedule; separate mains-derived supply for the SFL controller
Optical Performance

Photometric Requirements

ParameterTypical Value
Steady/Barrette Intensity10,000 – 20,000 cd (white), 5-step: 100% / 30% / 10% / 3% / 1%
SFL Peak Effective Intensity≥ 20,000 effective cd (white xenon strobe), where fitted
SFL Flash RateApprox. 2 flashes/sec, sequenced outward-to-threshold along the centreline
Vertical Beam SpreadMain beam 1°–12° above horizontal (peak ~2°–3°)
Horizontal Beam Spread± 4.5° either side of runway centreline extended
ChromaticityWhite within ICAO Annex 14 boundary; red terminal/side elements where fitted
Minimum Approach Visibility SupportSized for CAT I decision height/RVR minima per ICAO Annex 14 / Annex 6
Isocandela DistributionPer ICAO Annex 14 Attachment A / FAA AC 150/5340-30 CAT I configuration figures
Test MethodMobile photometric van/goniophotometer per fixture, plus SFL flash-timing verification against the sequencing schedule
Compliance

Applicable Standards

ICAO Annex 14

CAT I approach lighting configuration, spacing, and photometric requirements

FAA AC 150/5345-46

Specification for CAT I approach lighting components

IEC 61827

Electrical and photometric performance for AGL luminaires

FAA Engineering Brief #67

LED CAT I component performance requirements

Prerequisites

Installation Requirements

Frangible Stand Footing & Slope Grading
Civil

Set each barrette and SFL stand footing to the design height across the 720 m or 900 m configuration length so the array follows the required approach slope.

Elevated Piers Over Roads & Obstacles
Civil

Install piled or pier-mounted structures wherever the approach area crosses roads, drainage, or uneven terrain, engineered to keep the barrette bars coplanar.

Duct & Cable Route
Electrical

Lay separate duct runs for the steady-burning and sequenced flashing lights (SFL) circuits back to their own regulators, keeping the two systems electrically isolated.

L-823 Connector Termination
Electrical

Terminate and seal primary connectors on both circuits per manufacturer procedure, keeping every splice fully submersible-rated before backfill.

Isolating Transformer Matching
Electrical

Confirm each fixture's isolating transformer wattage matches its circuit's rated current step, with steady and SFL transformers kept on their respective loops.

Barrette Bar & SFL Stand Assembly
Mechanical

Fix lamp housings to each barrette bar and mount SFL heads on their dedicated stands, torquing frangible fittings to spec so they shear cleanly under lateral load.

Setting-Out to Extended Centreline
Mechanical

Tie stand positions to the extended runway centreline and threshold survey so the barrette spacing and SFL sequence stay true to the final approach course.

Pre-Energisation Sign-off
Documentation

Record stand positions, cable routes, connector seals, and torque values as-built for both circuits before backfill, since these are not inspectable once the site is closed.

Verification

Testing & Commissioning

Insulation Resistance (Megger) Test
Pre-Energisation

Megger-test the steady circuit and the sequenced flashing lights circuit before backfill, confirming insulation resistance clears the acceptable minimum on both.

Loop Continuity & Resistance Test
Pre-Energisation

Verify series loop continuity and record total loop resistance for every barrette along the full 731m–900m run before first energisation.

Primary/Secondary Voltage Verification
Energisation

With the CCR energised, confirm secondary voltage at each barrette's isolating transformer matches the rated ratio at the commissioned current step.

Sequenced Flashing Timing Verification
Energisation

Confirm the SFL controller fires each flasher in the correct outer-to-threshold sequence at the specified flash rate, with no dropped or out-of-order flash heads.

CCR Brightness Step Response
Energisation

Cycle the CCR through every intensity step and confirm the row responds correctly at each, ruling out marginal transformers or loose connections.

Barrette & Crossbar Alignment Verification
Final Acceptance

Check elevation, azimuth, and crossbar alignment of each barrette against the design aiming diagram, correcting any deviation before sign-off.

Photometric Commissioning Test
Final Acceptance

Measure beam intensity and colour with a calibrated photometer against ICAO/FAA CAT I commissioning tolerances prior to operational handover.

Documentation & As-Built Sign-off
Final Acceptance

Record insulation, continuity, voltage, flash-sequence, and photometric readings alongside as-built barrette positions in the commissioning dossier for handover.

Upkeep

Inspection & Maintenance

Photometric Intensity Check
Annual

Verify barrette and centreline beam intensity against ICAO / FAA thresholds using a calibrated photometer across the full 731m–900m configuration length.

Barrette Lens Cleaning
Quarterly

Clear dust, insect residue, and weathering film from every barrette and centreline lens along the approach so beam output stays within spec end to end.

Sequenced Flasher Timing Test
Semi-annual

Confirm the sequenced flashing lights fire in the correct outer-to-threshold order and at the specified rate, since a stuck or out-of-sequence flasher undermines the approach cue.

Seal & Gasket Inspection
Annual

Check top-cap O-rings and gaskets across elevated and inset fixtures for cracking or compression set, and re-torque fasteners to keep each unit watertight.

Insulation Resistance Test
Annual

Megger-test the isolation transformers and series circuit feeding the configuration to confirm resistance stays above minimum, flagging moisture ingress before it causes a circuit-wide fault.

Frangible Coupling Check
Annual

Inspect couplings on elevated fixtures for brittleness, corrosion, or shear fatigue and replace on schedule, since the approach lighting structure sits in the direct overrun path.

Cable & Connector Inspection
Annual

Examine primary and secondary cable connections across the array for corrosion or loose crimps, a common source of intermittent series-circuit faults over a run this long.

Configuration Alignment & Spacing Audit
Annual

Walk the full 731m–900m array to confirm barrette spacing and beam aim still match the design layout, since ground settlement can shift fixtures out of tolerance over such a long run.

Field Notes

Common Field Issues

Lens Contamination

CAT I components are exposed to environmental pollutants, bird droppings, and de‑icing chemicals. Regular cleaning with approved solvents and soft brushes is essential to maintain light output and visibility, especially for the SFL which must be clearly seen.

Sequenced Flashing Light (SFL) Timing Drift

The SFL system relies on precise timing. Over time, control units can drift, causing the sequence to become irregular or out of sync. Regular calibration and testing of the SFL system is critical.

Misalignment of Elevated Fixtures

Elevated approach lights can be knocked out of alignment by wind, wildlife, or maintenance vehicles. Regular alignment checks using a theodolite or laser alignment system are essential to maintain the correct beam direction.

CCR and Power Supply Issues

CAT I systems draw significant power. Voltage fluctuations, CCR faults, or cable damage can cause inconsistent brightness or total failure. Regular power quality monitoring and cable testing are recommended.

Diagnostics

Troubleshooting Guide

Single Light/Bar Dark, Rest of Array Normal
Likely Cause
Failed lamp/LED source, or an open isolating transformer at that fixture (blown primary link or failed secondary winding).
Diagnostic Steps
Confirm series loop continuity through the fixture's transformer primary; megger the transformer; check secondary voltage at the connector with the CCR energised.
Corrective Action
Replace the lamp/LED source if the transformer checks healthy; otherwise swap the isolating transformer and re-seal the L-823 connectors before backfill.
Entire Array Dark / CCR Will Not Regulate
Likely Cause
Open-circuit fault in the series loop feeding the approach lights (severed cable, corroded splice, or a failed transformer acting as an open point).
Diagnostic Steps
Check the CCR fault/open-circuit indication first; loop-resistance test from the CCR output to isolate the faulted segment; sectionalise and megger cable runs along the approach centreline to narrow down the break.
Corrective Action
Excavate and repair or replace the faulted cable section and connector; re-test insulation resistance before reinstating the circuit.
SFL Sequence Irregular or Out of Step
Likely Cause
Timing drift in the sequenced flashing light controller, or a failed flasher unit, has broken the rolling flash pattern.
Diagnostic Steps
Verify controller timing against the specified sequence rate; check each flasher head in turn for correct firing order; inspect flasher control cabling for damage.
Corrective Action
Recalibrate or replace the SFL controller, or replace the faulty flasher head; confirm the rolling sequence is restored end to end.
CCR Trips on Overcurrent or Ground Fault
Likely Cause
Moisture ingress at a fixture or connector has degraded insulation resistance, creating a short or a partial ground fault on the series loop.
Diagnostic Steps
Megger the full circuit to identify the low-resistance segment; visually inspect suspect fixtures for cracked gaskets, condensation, or damaged secondary cable jackets.
Corrective Action
Dry out or replace the affected fixture/connector, renew O-rings and gaskets, and confirm insulation resistance is back above the acceptable minimum before re-energising.
Elevated Fixture Misaligned
Likely Cause
Wind loading, wildlife strike, or contact from a maintenance vehicle has knocked an elevated fixture off its aiming tolerance, or the frangible coupling has begun to fatigue.
Diagnostic Steps
Re-check fixture aim with a theodolite or laser alignment system against the approach centreline; inspect the frangible coupling and mounting stake for cracking, play, or settlement.
Corrective Action
Re-level and re-aim the fixture, replace the frangible coupling if fatigued, and address any base or subgrade settlement to prevent recurrence.
Reduced or Hazy Light Output
Likely Cause
Lens contamination from environmental pollutants or de-icing residue, or an aging light source.
Diagnostic Steps
Run a photometric intensity check against ICAO/FAA thresholds; inspect and clean the lens; confirm the CCR is set to the correct intensity step for prevailing conditions.
Corrective Action
Clean or replace the lens, replace a degraded light source, or correct the CCR step setting; re-verify with a follow-up photometric reading.
Reliability

Failure Modes & Root Causes

Light Source (Lamp/LED) Failure
High Severity
Root Cause
Solder-joint fatigue from repeated thermal cycling, moisture ingress through a compromised fixture seal, or ordinary end-of-life lumen depreciation.
Effect
Single light or bar within the approach array goes dark or drops below minimum intensity while the rest of the array continues to operate normally.
Detection Method
Nighttime visual patrol along the approach centreline, periodic photometric intensity survey, and continuity/secondary-voltage checks at the fixture connector.
Isolating Transformer Winding Failure
High Severity
Root Cause
Moisture ingress leading to insulation breakdown, a manufacturing defect in the winding, or a blown primary fuse-wire link from a transient surge.
Effect
Open-circuit point in the series loop; can darken the single fixture or, if the open extends to the loop itself, take down the entire array.
Detection Method
Megger test of the transformer, secondary voltage check with the CCR energised, and loop-resistance testing from the CCR output.
L-823 Connector / Splice Degradation
Medium Severity
Root Cause
Improper seating or crimping during installation, gasket failure allowing groundwater ingress, or corrosion building up on the pins over time.
Effect
Intermittent operation, flickering, or a partial ground fault that degrades circuit insulation resistance.
Detection Method
Insulation resistance (megger) testing of the circuit and visual inspection of connectors at each fixture base can during maintenance.
Series Cable Insulation Breakdown
High Severity
Root Cause
Cable jacket damage from nearby excavation or wildlife activity, age-related insulation degradation, or prolonged standing water in the duct run beneath the approach centreline.
Effect
Ground fault or short circuit that trips the CCR or darkens the entire series loop feeding the approach lights.
Detection Method
Full-circuit megger test to flag the low-resistance segment, followed by sectionalised testing or time-domain reflectometry to pinpoint the fault location.
Elevated Fixture Frangible Coupling Fatigue
Medium Severity
Root Cause
Cyclic wind loading, wildlife strike, or contact from a maintenance vehicle, combined with ordinary material fatigue over the service interval.
Effect
Fixture leans, loosens, or separates from its mounting stake, pulling the light out of aim tolerance along the approach centreline.
Detection Method
Physical inspection for cracking or play in the coupling, and periodic fixture-aim checks with a theodolite or laser alignment system.
CCR Regulation Fault
High Severity
Root Cause
Internal component failure (control board or output stage), a load mismatch after circuit modification, or a firmware/setpoint fault.
Effect
Incorrect brightness step, failure to hold regulated current across the loop, or nuisance tripping on an otherwise healthy circuit.
Detection Method
CCR self-diagnostic/fault indication, output current verification, and a load-bank test to confirm regulation across all intensity steps.
Lens Contamination / Reduced Intensity
Low Severity
Root Cause
Environmental pollutants, de-icing residue, or airborne particulate building up on the lens surface, combined with ordinary UV-driven material degradation over time.
Effect
Reduced or hazy light output that can fall below the photometric thresholds required for CAT I minima despite the light source itself being healthy.
Detection Method
Scheduled photometric intensity testing against ICAO/FAA thresholds and visual inspection of the lens during routine cleaning.
Sequenced Flasher Timing Drift / Failure
Medium Severity
Root Cause
Ageing capacitor bank in the condenser discharge unit, a failed trigger transformer, or timing drift in the sequenced flashing light controller where the configuration includes SFL.
Effect
Flasher fails to fire or fires out of sequence, weakening or breaking the rolling flash cue that leads pilots down the approach centreline in low-visibility conditions.
Detection Method
Verify controller timing against the specified sequence rate, check each flasher head in firing order, and inspect the condenser discharge unit for capacitor swelling or leakage.
Precautions

Safety & Operational Notes

Series Circuit Isolation
Electrical Safety

Approach light bar and crossbar circuits run on constant-current series loops that can carry several kV. De-energise and lock out the associated CCR, then verify zero energy at the tower base or barrette before opening any enclosure.

Sequenced Flasher Check Where Fitted
Electrical Safety

Where the CAT I configuration includes sequenced flashing lights (as in an ALSF-1 or MALSR build-out), discharge each condenser discharge unit through its bleed resistor and confirm zero voltage before servicing a flasher head, since it retains a high-energy charge after the controller is switched off.

Elevated Tower & Off-Runway Access
Personnel Safety

Light bar towers extend along the extended centreline over terrain that may be uneven, waterlogged, or off the paved movement area; use fall protection when climbing frangible towers and assess ground conditions before positioning vehicles or ladders.

Frangibility Not to Be Defeated
Mechanical

Never substitute a frangible coupling or tower base with a rigid fitting, and do not over-torque connections during installation or repair; the structure must still break away cleanly on aircraft impact within the runway safety area.

Airside Work Coordination
Operational

Work on approach lighting affects an active runway's published CAT I minima; obtain ATC/airside coordination and issue a NOTAM before any bar, crossbar, or flasher is taken out of service, and keep personnel and vehicles clear of the approach surface during aircraft operations.

FOD Control Along the Approach
Operational

Account for tools, fasteners, and hardware at every tower and barrette worked on, and remove or secure loose material before leaving the site, since debris in the approach area can be ingested or strike an aircraft on short final.

Insulation Test Before Re-Energisation
Electrical Safety

After any cable, connector, or transformer work on a bar, crossbar, or flasher circuit, megger test the affected series loop before restoring power, since a residual fault can trip the CCR or damage healthy fixtures on the same circuit.

Restore to Compliant State
Compliance

Do not leave the system with a bar out of aim tolerance, a dark flasher, or an out-of-sequence discharge pattern; verify photometric output against CAT I requirements before closing out the work and cancelling the associated NOTAM.

Field Insight

Engineering & Expert Notes

Confirm Which Standard Governs This Installation
Configuration

CAT I approach lighting can be built to ICAO or FAA configuration standards with different lengths (900m ICAO vs 731–914m FAA) and barrette spacing. Verify which standard applies to this specific runway before comparing measured layout against a generic reference.

Track Margin Against the 550m RVR Minimum, Not Just Pass/Fail
Photometric

Recording only pass/fail against the certification minimum loses the early warning that comes from watching measured intensity decline over successive surveys. Trend the actual numbers so replacement can be planned before the array approaches minimum RVR support.

Elevated Structures Need Periodic Aim Verification, Not Just Structural Inspection
Structural

A bar can be structurally sound — no visible tilt, no impact damage — and still have its beam aim drifted enough to matter at range. Schedule theodolite or laser aim checks on their own cycle, independent of general structural inspection.

SFL Timing Drift Is a Controller Problem, Not a Lamp Problem
Electrical

When the sequenced flashing pattern becomes irregular, the root cause is almost always the control unit's timing reference drifting, not individual flash tube or LED wear. Diagnose and recalibrate the controller before replacing lamp hardware.

Distinguish Genuine Misalignment From Perspective Distortion
Troubleshooting

A bar reported as 'off' from a pilot report can sometimes be a perspective effect at a particular approach angle rather than an actual mechanical misalignment. Verify with survey instruments before dispatching a maintenance crew to physically adjust the fixture.

Document Which Standard Was Used at Certification
Compliance

Because CAT I systems can be built to more than one recognised standard, certification and periodic compliance paperwork should explicitly record which standard the installation was surveyed against, avoiding ambiguity during audits or category renewal.

Quick Answers

Frequently Asked Questions

Short answers about CAT I approach lighting: minima, configuration, control, standards and maintenance.

Q1What is CAT I approach lighting?

It is a precision approach lighting system for Category I instrument approaches. It uses light bars (barrettes) and sequenced flashing lights extending from the runway threshold into the approach area, giving horizontal and vertical guidance to help pilots hold the approach path and align with the centreline.

Q2What operating minima does CAT I approach lighting support?

Approaches down to a 200 ft decision height with an RVR of 550 m (1,800 ft). The system is calibrated to those minima, giving enough visual structure for a pilot to transition from instruments to visual reference at 200 ft and confirm the runway environment.

Q3How long is a CAT I approach lighting system?

Typically 900 m under the ICAO precision approach CAT I standard, or 731 m (2,400 ft) under the FAA MALSR/ALSF-1 standard, extendable to 914 m (3,000 ft) on shallow-slope sites, depending on airfield requirements.

Q4What are the main elements of a CAT I system?

Steady-burning barrettes (typically 3 to 5 lights per bar), a row of sequenced flashing lights that flash from the outer end toward the threshold, a centreline barrette, and crossbar lights. Barrette spacing is 30 m (100 ft) on FAA ALSF-1 or the ICAO barrette section and 61 m (200 ft) on FAA MALSR.

Q5How is CAT I approach lighting controlled?

The whole system is controlled by CCRs with five intensity steps (2.8 A to 6.6 A), letting ATC adjust brightness for visibility. Higher intensities are used in low visibility.

Q6How are sequenced flashing lights powered?

Steady lights run on a CCR-fed series circuit, but the sequenced flashing lights are fed from a separate discharge circuit. A capacitor-discharge trigger unit drives xenon strobe tubes in sequence, synchronised by a flasher controller and a shielded trigger cable.

Q7Where is CAT I approach lighting used?

On precision approach runways with CAT I capability, regional and international airports handling commercial traffic, military airbases needing all-weather precision approach capability, moderate-traffic runways requiring reliable low-visibility operation, and as the baseline at airports moving toward CAT II/III.

Q8Which standards apply to CAT I approach lighting?

The main references are ICAO Annex 14 (configuration, spacing and photometric requirements), FAA AC 150/5345-46 (CAT I components), IEC 61827 and FAA Engineering Brief #67 (LED CAT I component performance). Always verify the current edition and your aerodrome's approved requirements.

Q9How often should CAT I approach lighting be maintained?

Typical practice is quarterly lens cleaning, semi-annual sequenced flasher timing tests, and annual photometric intensity checks, seal and gasket inspection, insulation resistance tests, frangible coupling checks, cable and connector inspection and a configuration alignment and spacing audit. Your airport's approved maintenance programme takes precedence.

Q10What are the common CAT I approach lighting problems?

Lens contamination from pollutants, bird droppings and de-icing chemicals, sequenced flashing light timing drift, elevated fixtures knocked out of alignment (check with a theodolite or laser alignment), and CCR or power supply issues that cause inconsistent brightness or total failure.

Go Further

Go Beyond the Component. Understand the Complete AGL System.

You have explored the component. Now understand how it works within the complete Airfield Ground Lighting system.

Learn AGL from fundamentals to design, installation, testing, photometry, commissioning, maintenance and troubleshooting through structured technical training at Precision AGL Academy.

Build practical knowledge. Understand the circuit. Read the standards. Troubleshoot with confidence.

Your next step in AGL starts here.

The Learning Pathway
Learn Understand Design Test Maintain Document Apply Certify

Need expert guidance on CAT I approach lighting selection, installation, or upgrade?

Precision AGL Academy provides advice on configuration, SFL integration, intensity settings, and field testing of CAT I approach lighting systems.