Ethernet Switch

The central hub for IP-based communication in modern AGL systems. Industrial Ethernet switches provide reliable, high-speed data connectivity between the ALCMS server, PLCs, Remote I/O, fiber converters, and other network devices, ensuring deterministic communication and fault-tolerant network topologies across the airfield.

Ethernet Switch

Image disclaimer: For identification and illustration only. It may show a product by another manufacturer and may not depict the exact item described; it is not a statement of any product’s quality, approval or performance. Third-party image and trademark rights belong to their owners. See full notice.

Overview

What Is It?

An Ethernet Switch is a network device that connects multiple devices on a local area network (LAN), forwarding data packets between them based on MAC addresses. In AGL applications, industrial-grade Ethernet switches are used to build the communication backbone that links the Airfield Lighting Control and Monitoring System (ALCMS) server, programmable logic controllers (PLCs), Remote I/O units, fiber converters, and other intelligent devices. Unlike standard commercial switches, industrial Ethernet switches are designed for harsh environments: they support extended temperature ranges (-40°C to +75°C), provide redundant power inputs, offer ruggedized enclosures, and implement advanced networking features such as redundant ring topologies (e.g., ERPS, RSTP), VLAN segmentation, quality of service (QoS), and cybersecurity features (port security, ACLs). These switches ensure reliable, deterministic, and secure communication critical for airfield lighting control.

Purpose

Purpose & Function

The industrial Ethernet switch exists to give the ALCMS server, PLCs, and Remote I/O units a communication backbone that's actually reliable in the same environment the lighting equipment itself has to survive — extreme temperatures, electrical noise from high-voltage AGL circuits, and continuous operation with no acceptable downtime. A standard commercial-grade switch simply isn't built to survive those conditions without becoming a point of failure for the entire control network.

Features like redundant ring topologies and redundant power inputs exist specifically because a single point of network failure in an airfield lighting control system could mean losing visibility or control over multiple circuits at once. By designing resilience into the network layer itself, the switch ensures that a single cable break or power supply fault doesn't cascade into a broader control system outage.

Application

Where Is It Used?

Ethernet switches are deployed in all areas of the AGL network infrastructure, including:

  • ALCMS Control Room: Core switches connecting servers, workstations, and network management consoles to the airfield network.
  • CCR Substations: Managed switches connecting PLCs, Remote I/O, and fiber converters to the main network backbone.
  • Runway Edge Cabinets: Switches providing local connectivity for lighting control modules, sensor nodes, and cameras.
  • Approach Lighting Control Shelters: Switches for sequencer modules, strobe controllers, and fiber media converters.
  • RWSL (Runway Status Light) Systems: Dedicated switches for the RWSL processing units, field controllers, and sensors.
  • Airfield Sensor Networks: Connecting weather stations, visibility sensors, wind measurement systems, and RVR equipment.
  • Gate & Apron Control Systems: Switches for docking guidance, gate management, and apron surveillance.
  • Security & Surveillance: Switches supporting IP cameras, access control, and perimeter monitoring systems.
Placement

Installation & Location

Switches are DIN-rail or rack-mounted inside the control room, substation, or field cabinet they serve, with industrial-rated (wide-temperature, vibration-resistant) units specified for outdoor runway-edge cabinets and approach lighting shelters, and standard rack-mount units for the air-conditioned ALCMS control room. Power is fed from the same DC supply as the other equipment in that cabinet, often with a redundant supply input on critical switches; uplink connections to the network backbone run on fibre between cabinets/shelters (for distance and electrical isolation) and on copper for short local runs within a single cabinet, with cable routing kept separate from lighting series-circuit power cable throughout.

Function

How Does It Work?

The Ethernet switch operates at Layer 2 of the OSI model, forwarding data frames based on MAC address tables. Key functional aspects in AGL networks include:

  • MAC Address Learning: The switch builds a table of MAC addresses associated with each port, learning which devices are on which segments to forward frames only to the necessary port (reducing unnecessary traffic).
  • Store-and-Forward Switching: Receives the entire frame, checks for errors using CRC, and forwards it to the destination port, ensuring error-free transmission.
  • Redundant Ring Topology: Supports protocols like RSTP (Rapid Spanning Tree Protocol) or ERPS (Ethernet Ring Protection Switching) to provide automatic failover in case of a cable break or switch failure, with recovery times as fast as 50 ms (ERPS).
  • VLAN Segmentation: Virtual LANs allow logical separation of traffic (e.g., control data, video surveillance, management traffic) for improved security and performance.
  • Quality of Service (QoS): Prioritizes critical AGL control traffic (e.g., PLC-to-CCR commands) over less time-sensitive data (e.g., video streams) to ensure deterministic communication.
  • Network Management: Supports SNMP (Simple Network Management Protocol) for remote monitoring, diagnostics, and configuration, allowing administrators to view port status, traffic statistics, and alarms.
  • Cybersecurity: Implements features like port security (MAC locking), Access Control Lists (ACLs), and DHCP snooping to protect the network from unauthorized access and cyber threats.

Industrial switches are typically powered by 24 VDC (airfield standard) or 48 VDC, with dual redundant power inputs for high availability. They are often DIN-rail mounted in control cabinets.

Architecture

System Architecture & Control Logic

The Ethernet switch is the shared backbone that every IP-capable node in the AGL system connects through — PLCs, Remote I/O, Communication Gateways, the SCADA Interface, Touchscreen HMIs, weather stations, and surface movement radar all terminate on switch ports rather than wiring directly to the ALCMS server. It does not participate in control logic itself; it forwards frames at Layer 2 based on MAC address tables and, where configured, segments traffic into VLANs so lighting-control data, radar/A-SMGCS data, and general IT traffic stay logically separated on the same physical fibre or copper backbone. Airfield deployments typically run switches in a redundant ring or dual-homed topology with RSTP or similar, so that a single fibre cut or switch failure reroutes traffic within milliseconds rather than dropping the affected branch off the network entirely.

Field Controllers
PLC / Remote I/O

Circuit control & status

Sensors & Aids
Weather Station / SMR

Environmental & movement data

Interfaces
Gateway / SCADA / HMI

Protocol bridging & local control

Ethernet Switch (Redundant Ring)

Layer-2 forwarding, VLAN segmentation, sub-second failover

ALCMS Server

Single logical destination for all connected nodes

The switch carries traffic but makes no control decisions itself — a ring or dual-homed topology is what keeps a single link fault from taking a branch off the network.
Mechanism

How the Switch Handles Traffic & Failover

Frame Arrives at Switch Port

Incoming Ethernet frame from a connected device or uplink

MAC Address Table Lookup

Learns source address, matches destination to the correct port

Normal Forwarding
Store-and-Forward

Frame CRC-checked, forwarded only to the destination port

Traffic Priority
QoS Prioritization

PLC↔CCR control traffic prioritized over video/management data

Cable Break / Failure
RSTP / ERPS Reroute

Ring topology restores traffic in as fast as 50 ms

VLAN segmentation keeps control, video and management traffic logically isolated across all three paths.
Construction

Physical Construction

The switch is housed in a rugged extruded-aluminium or steel enclosure with a wide operating-temperature rating, built for DIN-rail mounting inside a control cabinet or field enclosure rather than a server-room rack. Copper ports use shielded RJ-45 connectors with integrated magnetics, while SFP cages for fibre uplinks are soldered directly to the backplane and accessed through dedicated front-panel cutouts, keeping the fibre optics separate from the copper ports for EMI isolation. Internal electronics are conformally coated to resist dust, humidity, and airborne contaminants, and the dual redundant power inputs terminate at screw-clamp terminals rated for the nominal 24 VDC supply. Where deployed outside a conditioned cabinet, the switch is fitted into a sealed IP65 enclosure with cable glands for each cable entry, and a chassis earth stud is provided for bonding to the cabinet ground bus.

Specification

Technical Parameters

ParameterTypical Value
Port Configuration8, 16, or 24 ports (10/100/1000BASE-T copper) + SFP slots (for fiber uplinks)
Fiber UplinksSFP slots supporting 100BASE-FX, 1000BASE-SX/LX/ZX (multi-mode/single-mode)
Switching CapacityUp to 56 Gbps (non-blocking) for managed switches
Forwarding RateUp to 41.7 Mpps (for 24-port Gigabit switch)
Redundancy ProtocolsRSTP, MSTP, ERPS (ring), link aggregation (LACP)
ManagementWeb GUI, CLI (SSH/Telnet), SNMP v1/v2c/v3, RMON
CybersecurityPort security, MAC filtering, ACLs, IEEE 802.1X (RADIUS), DHCP snooping
QoSIEEE 802.1p, DiffServ (DSCP), 8 priority queues
Power Supply24 VDC (nominal, 18‑32 VDC) with dual redundant inputs
Power Consumption10‑50 W self-consumption (port count dependent); PoE-enabled ports draw additional power per the connected load, separate from this figure
Operating Temperature-40°C to +75°C (industrial grade)
Storage Temperature-40°C to +85°C
Protection ClassIP30 (DIN-rail mount), IP40 (ruggedized), IP65 (field mount with enclosure)
MountingDIN rail (standard) or panel mount
DiagnosticsPort status LEDs, system log, SNMP traps, port mirroring
CertificationsCE, FCC, UL, IEC 61000‑6‑2 (EMC immunity), IEC 61850 (substation)
Power Supply

Electrical Requirements

RequirementTypical Value
Circuit PositionStandalone powered networking device, field or control-room mounted
Power Supply24 VDC (nominal, 18‑32 VDC) with dual redundant inputs
Power Consumption10‑50 W self-consumption (port count dependent); PoE load is additional, sized to the connected devices
PoE OutputUp to the port-rated PoE budget for connected field devices
IsolationPowered separately from the AGL series circuit
Fault ProtectionDual-input redundancy; per-port overcurrent protection on PoE ports
Compliance

Applicable Standards

IEEE 802.3

Ethernet standards (10BASE-T, 100BASE-TX, 1000BASE-T, 1000BASE-X)

IEEE 802.1D/1w/1s

Spanning Tree Protocol (STP/RSTP/MSTP) for redundancy

IEEE 802.1Q

VLAN tagging and traffic segmentation standard

FAA AC 150/5345‑56

Specification for AGL control and monitoring equipment

Prerequisites

Installation Requirements

Environment-Rated Unit Selection
Civil

Specify an industrial-rated, wide-temperature, vibration-resistant switch for outdoor runway-edge cabinets and approach lighting shelters, and a standard rack-mount unit for the air-conditioned ALCMS control room.

DIN-Rail or Rack Mounting
Mechanical

Mount the switch inside the control room, substation, or field cabinet it serves, positioned for clear access to its port panel for cabling and maintenance.

DC Power Feed
Electrical

Feed power from the same DC supply as the other equipment in that cabinet, wiring a redundant supply input where the switch is specified with one.

Fibre & Copper Uplink Routing
Electrical

Run fibre uplinks between cabinets or shelters for distance and electrical isolation, and copper for short local runs within a single cabinet, keeping routing separate from lighting series-circuit power cable.

VLAN & Port Configuration
Documentation

Configure port assignments, VLANs, and redundancy protocols per the network design before the switch is brought into service.

Pre-Commissioning Sign-off
Documentation

Record mounting location, power feed, and uplink cabling as-built before commissioning testing begins.

Verification

Testing & Commissioning

Cable & Port Continuity Test
Pre-Commissioning

Verify every port and cable run tests clean before the switch is placed into service.

Network Topology & Redundancy Test
Commissioning

Confirm the ring/redundant topology (e.g. ERPS, RSTP) correctly reroutes traffic when a link is broken.

VLAN & QoS Configuration Verification
Commissioning

Confirm VLAN segmentation and QoS priorities match the design before live traffic is carried.

Throughput & Latency Test
Commissioning

Confirm the switch sustains the required traffic load without excessive latency or packet loss.

Power Supply Redundancy Test
Commissioning

Where dual power inputs are fitted, confirm the switch continues operating uninterrupted on a single source.

Security Configuration Verification
Pre-Commissioning

Confirm port security and access control lists match the design before go-live.

Enclosure & Thermal Check
Pre-Commissioning

Confirm the enclosure is correctly sealed and the switch operates within its rated temperature range.

Documentation & As-Built Sign-off
Final Acceptance

Record configuration, VLAN mapping, and test results in the commissioning dossier for handover.

Upkeep

Inspection & Maintenance

Cable & Connector Inspection
Annual

Check cabling and connectors for damage or degraded contacts that can cause intermittent link loss.

Traffic Health Check
Semi-annual

Review switch logs and port statistics for signs of broadcast storms or abnormal traffic patterns.

Power Supply Check
Annual

Verify power input stability and inspect the supply unit for signs of stress or ageing.

Enclosure Thermal Check
Semi-annual

Confirm ventilation or cooling is adequate and the enclosure isn't trapping heat around the switch.

Firmware & Configuration Audit
Annual

Review firmware version and configuration against baseline to catch unplanned drift.

Security Patch Review
Annual

Check for and apply relevant security patches to address known vulnerabilities.

Field Notes

Common Field Issues

Cable Damage & Faulty Connections

Damaged Ethernet cables (RJ‑45 connectors, broken wires) are a common cause of intermittent connectivity. Use shielded, industrial-grade cables (CAT5e/CAT6) and inspect connectors regularly. Consider using M12 connectors in harsh outdoor environments.

Broadcast Storms

Network loops caused by misconfiguration (e.g., connecting two ports without STP) can lead to broadcast storms, crippling the network. Always enable STP/RSTP and use ring topologies with proper redundancy protocols.

Power Supply Failure

Switches rely on stable power. Use dual redundant power supplies (if supported) and connect to a UPS system to prevent switch reboots during power fluctuations.

Overheating in Enclosures

Switches generate heat; inadequate ventilation or high ambient temperatures can cause performance degradation or premature failure. Ensure cabinets have proper cooling (fans, vents) and keep ambient temperature within the rated range.

Firmware/Configuration Drift

Updates or changes to switch configurations without proper documentation can introduce errors. Use configuration backup and version control, and perform firmware updates in a planned maintenance window.

Cybersecurity Vulnerabilities

Exposed management interfaces (e.g., default passwords, unsecured protocols) can be exploited. Implement strong passwords, disable unused services, and use SNMPv3 with encryption.

Diagnostics

Troubleshooting Guide

Intermittent Connectivity on One Port
Likely Cause
A damaged Ethernet cable, worn RJ-45 connector, or broken conductor on that specific run, especially likely in harsh outdoor environments without M12-rated connectors.
Diagnostic Steps
Swap the suspect cable with a known-good one to isolate the fault; inspect the RJ-45 connector and cable jacket for physical damage; check the port's link light behaviour for flapping.
Corrective Action
Replace the damaged cable with shielded, industrial-grade CAT5e/CAT6 cable, upgrading to M12 connectors if the run is exposed to harsh outdoor conditions.
Network-Wide Slowdown or Total Loss of Connectivity
Likely Cause
A broadcast storm caused by a network loop, typically from a misconfiguration such as two ports connected together without STP/RSTP enabled.
Diagnostic Steps
Check switch port statistics for abnormally high broadcast traffic; verify STP/RSTP is enabled and check its topology for a detected loop; review recent cabling or port changes.
Corrective Action
Remove the looped connection causing the storm; enable STP/RSTP if it was disabled, and confirm ring topology redundancy protocols are correctly configured to prevent recurrence.
Switch Reboots Unexpectedly
Likely Cause
Power supply instability or failure, particularly if the switch isn't running from dual redundant supplies or a UPS.
Diagnostic Steps
Check power supply status indicators (if dual redundant supplies are fitted, confirm which one failed); correlate reboot timing with known power fluctuations on site.
Corrective Action
Replace the failed power supply module; connect the switch to a UPS system if not already protected, to prevent reboots during power fluctuations.
Performance Degrades or Switch Fails During Warm Weather
Likely Cause
Overheating inside the enclosure due to inadequate ventilation or high ambient temperature exceeding the switch's rated operating range.
Diagnostic Steps
Check enclosure/cabinet temperature against the switch's rated range; inspect cooling fans and vents for blockage or failure.
Corrective Action
Clear blocked vents, repair or replace failed cooling fans, and improve cabinet ventilation to keep ambient temperature within the rated range.
Switch Behaving Differently Than Documented Configuration
Likely Cause
A configuration change was made without proper documentation, or a firmware update was applied outside a planned maintenance window and altered default behaviour.
Diagnostic Steps
Compare the switch's running configuration against the last known-good backup; check firmware version history against the maintenance log.
Corrective Action
Restore the last verified configuration backup; enforce configuration version control and scheduled maintenance windows for future firmware updates.
Unauthorised Access or Configuration Change Detected
Likely Cause
An exposed management interface using default passwords or an unsecured protocol has allowed unauthorised access.
Diagnostic Steps
Review management access logs for unrecognised logins or configuration changes; check whether default credentials remain in use and whether SNMPv3 encryption is enforced.
Corrective Action
Change default passwords, disable unused services, and migrate to SNMPv3 with encryption; review and revert any unauthorised configuration changes found.
Reliability

Failure Modes & Root Causes

Cable / Port Degradation
Medium Severity
Root Cause
A damaged Ethernet cable, worn RJ-45 connector, or broken conductor on a specific run, especially without M12-rated connectors in harsh outdoor environments.
Effect
Intermittent connectivity on one port while the rest of the switch continues to operate normally.
Detection Method
Cable swap to isolate the fault, physical inspection of the connector and cable jacket, and monitoring of link light behaviour for flapping.
Network Loop / Broadcast Storm
High Severity
Root Cause
A network loop from misconfiguration, typically two ports connected together without STP/RSTP enabled.
Effect
Network-wide slowdown or total loss of connectivity as broadcast traffic overwhelms the network.
Detection Method
Switch port statistics review for abnormal broadcast traffic, and verification of STP/RSTP status and topology.
Power Supply Failure
Medium Severity
Root Cause
Power supply instability or failure, particularly where the switch is not running from dual redundant supplies or a UPS.
Effect
Switch reboots unexpectedly, causing a brief but disruptive loss of network connectivity.
Detection Method
Power supply status indicator check, and correlation of reboot timing with known power fluctuations on site.
Thermal Overload
Low Severity
Root Cause
Overheating inside the enclosure from inadequate ventilation or ambient temperature exceeding the switch's rated range.
Effect
Performance degrades or the switch fails during warm weather periods.
Detection Method
Enclosure/cabinet temperature check against the switch's rated range, and inspection of cooling fans and vents for blockage or failure.
Undocumented Configuration Drift
Low Severity
Root Cause
A configuration change made without proper documentation, or a firmware update applied outside a planned maintenance window.
Effect
Switch behaves differently than the documented configuration, complicating troubleshooting of unrelated issues.
Detection Method
Comparison of the running configuration against the last known-good backup, and review of firmware version history against the maintenance log.
Unauthorised Access
High Severity
Root Cause
An exposed management interface using default passwords or an unsecured protocol.
Effect
Unauthorised access or configuration changes are detected on the switch.
Detection Method
Management access log review for unrecognised logins, and a check of default credential and SNMPv3 encryption status.
Precautions

Safety & Operational Notes

Isolate Both Redundant Power Inputs
Electrical Safety

Where the switch is fed by dual redundant 24VDC inputs, isolate and verify zero energy on both before internal work, since disconnecting only one leaves the unit powered from the other.

PoE Port Voltage
Electrical Safety

If any ports supply Power over Ethernet to connected devices, treat those ports as carrying hazardous voltage (up to around 55-57V) even when the switch's main supply appears isolated at a glance; disconnect or confirm PoE is disabled before handling those cables.

Fiber Port Laser Safety
Personnel Safety

Never look directly into an active fiber port or the end of a connected fiber patch lead on SFP-equipped switches; although typically low-power (Class 1) and normally eye-safe, use an optical power meter rather than direct viewing to check for a live signal.

ESD-Sensitive Electronics
Operational

Use anti-static precautions when handling internal boards or SFP modules.

Coordinate Before Taking Down the Comms Backbone
Operational

The switch may carry traffic for the ALCMS server, PLCs, and Remote I/O across the airfield; confirm what monitoring or control capability is lost before isolating it, and coordinate with control-room operators accordingly.

Restore to Compliant State
Compliance

Confirm all connected devices re-establish communication and link status is correct on every active port before closing out the work.

Field Insight

Engineering & Expert Notes

An Uncommissioned Redundancy Protocol is a Loop Waiting to Happen
Network Design

A ring topology wired correctly but with RSTP/ERPS left at default or misconfigured settings doesn't fail safely — it can create a genuine broadcast storm the moment a second physical path is connected. Verify the actual ring protocol convergence behaviour by testing a real link break during commissioning, not just confirming the protocol is "enabled" in the configuration.

Cabinet Heat Load Compounds Over Years, Not Just Summers
Thermal

A switch that runs within its rated temperature range in its first year can start showing intermittent faults years later as cabinet ventilation degrades — dust-clogged fans, aging seals letting in less airflow than designed, or added equipment sharing the same enclosure. Re-verify actual cabinet internal temperature periodically rather than assuming the original thermal design still holds.

VLAN Misconfiguration Often Hides Behind "It Works Most of the Time"
Troubleshooting

A VLAN tagging mismatch between two switches in a ring can allow normal traffic through while silently dropping specific VLANs during a failover reroute, so the fault only appears under the exact condition the redundancy protocol was meant to handle. Test VLAN behaviour specifically during a simulated link failure, not only under normal operation.

Verify Both Power Inputs Are Actually Independent
Electrical

Dual power inputs only deliver real redundancy if they're fed from genuinely separate sources; wiring both inputs from the same distribution panel or the same UPS output defeats the purpose while still passing a basic connectivity test. Trace both feeds back to their actual origin during commissioning, not just confirm the switch accepts two cables.

Configuration Drift Accumulates Quietly Across Field Visits
Configuration

Ad hoc port or VLAN changes made during troubleshooting visits, without updating the master configuration backup, gradually pull the live switch config away from what's documented. Pull and diff a configuration backup at every scheduled maintenance visit, not only after planned changes, to catch this kind of unrecorded drift.

SNMP is Often the Overlooked Attack Surface
Cybersecurity

Teams commonly harden the switch's web/CLI management access while leaving SNMPv1/v2c community strings at default, forgetting that SNMP itself can expose or even allow modification of switch configuration. Audit SNMP settings with the same rigor as login credentials, and prefer SNMPv3 with authentication and encryption wherever the equipment supports it.

Quick Answers

Frequently Asked Questions

Short answers about industrial Ethernet switches in AGL networks: redundancy, VLANs, specifications, standards and maintenance.

Q1What is an industrial Ethernet switch in an AGL system?

It is a network device that connects multiple devices on a LAN and forwards data frames by MAC address. In AGL applications, industrial-grade switches build the communication backbone linking the ALCMS server, PLCs and remote I/O units.

Q2Why use industrial-grade switches instead of office switches?

The backbone has to be reliable in the same environment the lighting equipment survives: extreme temperatures and electrical noise. Industrial switches are rated for -40°C to +75°C and have dual redundant power inputs.

Q3Where are Ethernet switches deployed?

Across the AGL network: core switches in the ALCMS control room connecting servers, workstations and management consoles, and managed switches at CCR substations connecting local controllers to the backbone.

Q4How does an Ethernet switch work?

It operates at Layer 2, learning which MAC address sits on which port and forwarding each frame only to the right port instead of flooding the network.

Q5What are the typical specifications?

8, 16 or 24 copper ports (10/100/1000BASE-T) plus SFP slots for fibre uplinks (100BASE-FX, 1000BASE-SX/LX/ZX), switching capacity up to 56 Gbps non-blocking, and 8 QoS priority queues using IEEE 802.1p and DiffServ.

Q6What redundancy and security features are typical?

Redundancy protocols include RSTP, MSTP, ERPS (ring) and LACP link aggregation. Security features include port security, MAC filtering, ACLs, IEEE 802.1X (RADIUS) and DHCP snooping, with management via web GUI, SSH, SNMP v1/v2c/v3 and RMON.

Q7How is an industrial Ethernet switch powered?

Typically from 24 VDC (18-32 VDC) with dual redundant inputs, separate from the AGL series circuit. Self-consumption is 10-50 W depending on port count, and PoE ports draw additional power for connected devices.

Q8Which standards apply?

IEEE 802.3 (Ethernet), IEEE 802.1D/1w/1s (STP/RSTP/MSTP), IEEE 802.1Q (VLAN tagging and segmentation) and FAA AC 150/5345-56 for AGL control and monitoring equipment.

Q9How often should an Ethernet switch be maintained?

Semi-annually for traffic health (logs and port statistics for broadcast storms) and enclosure thermal checks, and annually for cable and connector inspection, power supply checks, firmware and configuration audits against baseline, and security patch review.

Q10Why does one port show intermittent connectivity?

Likely a damaged Ethernet cable, worn RJ-45 connector or broken conductor on that run, especially outdoors without M12-rated connectors. Swap the suspect cable and re-test.

Explore Further

Related Components

Go Further

Go Beyond the Component. Understand the Complete AGL System.

You have explored the component. Now understand how it works within the complete Airfield Ground Lighting system.

Learn AGL from fundamentals to design, installation, testing, photometry, commissioning, maintenance and troubleshooting through structured technical training at Precision AGL Academy.

Build practical knowledge. Understand the circuit. Read the standards. Troubleshoot with confidence.

Your next step in AGL starts here.

The Learning Pathway
Learn Understand Design Test Maintain Document Apply Certify

Need expert guidance on Ethernet switch selection, network design, or cybersecurity for your AGL system?

Precision AGL Academy provides advice on switch specifications, ring topologies, VLAN design, and best practices for secure industrial networks.