AGL Component Library By Precision AGL Academy

Power Quality Monitor

A sophisticated instrumentation device that continuously measures and analyses the quality of electrical power supplied to AGL equipment. It monitors voltage, current, frequency, harmonics, power factor, and other critical parameters to ensure stable and reliable operation of Constant Current Regulators and lighting systems.

Power Quality Monitor

Image disclaimer: For identification and illustration only. It may show a product by another manufacturer and may not depict the exact item described; it is not a statement of any product’s quality, approval or performance. Third-party image and trademark rights belong to their owners. See full notice.

Overview

What Is It?

A Power Quality Monitor (PQM) is an advanced electronic instrument designed to continuously assess the quality of electrical power in AGL distribution systems. It measures a wide range of parameters including voltage sags/swells, harmonics (THD), flicker, unbalance, frequency deviations, and transient events. By providing real-time data and historical trend analysis, the PQM enables early detection of power quality issues that could affect the performance and lifespan of Constant Current Regulators (CCRs), UPS systems, and sensitive electronic controls.

In the context of AGL, power quality is paramount — even minor disturbances can cause flickering lights, erratic CCR behaviour, or premature equipment failure. The PQM acts as a diagnostic tool for maintenance teams, helping them identify root causes of power-related problems and enabling proactive corrective actions.

Purpose

Purpose & Function

The PQM exists because CCRs and other AGL electronics can degrade or fail from power-quality problems that never trip a simple overcurrent or overvoltage protection device — harmonics, flicker, and unbalance can quietly stress equipment for months before a failure finally appears, by which point the root cause is far harder to trace back to its source. By continuously logging these parameters rather than just reacting to gross faults, the monitor turns an otherwise invisible, slow-developing degradation into visible trend data that maintenance teams can act on before a CCR or UPS actually fails. Its purpose is therefore preventive rather than protective: it doesn't stop a bad event from reaching equipment, but it gives the airfield's maintenance program the diagnostic evidence needed to fix the underlying power-supply problem before repeated stress turns into an unplanned outage.

Application

Where Is It Used?

Power Quality Monitors are typically installed at key points in the AGL power distribution network, including:

  • Main Incoming Supply: At the utility metering point to monitor the quality of power entering the airfield.
  • Power Distribution Panels: At the input of each distribution panel to monitor power quality for all connected CCRs.
  • CCR Inputs: At individual CCR input feeders to detect supply anomalies that could affect regulator performance.
  • UPS Input and Output: To verify that the UPS is providing clean power and to detect any degradation in UPS performance.
  • Generator Interface: At generator output to ensure stable power quality when operating on backup.
  • Integration with ALCMS: Providing continuous data to the central ALCMS for remote monitoring, alarming, and historical analysis.

PQM units are also used for compliance verification against IEEE 519, EN 50160, and other power quality standards, and to support warranty claims on sensitive AGL equipment.

Placement

Installation & Location

PQM units are DIN-rail or panel-mounted at the specific point in the network they are monitoring, rather than in one central location — units are fitted at the utility metering point, at the input of each power distribution panel, at individual CCR input feeders, and at the UPS and generator interface, with voltage connections made directly or through PTs and current sensed via CT loops around the incoming conductors. Each unit's communication port (RS-485, Ethernet, or fibre for IEC 61850) is wired back to the ALCMS network so readings from every monitoring point can be trended and alarmed centrally. Because CT and PT wiring must not be opened while energised, units are installed with test terminal blocks or shorting links to allow safe isolation for maintenance.

Function

How Does It Work?

A Power Quality Monitor operates by sampling voltage and current waveforms at high speed (typically up to 512 samples per cycle) and performing digital signal processing to extract a comprehensive set of power quality parameters. Key functions include:

  • Voltage and Current Measurement: True RMS values for each phase, including neutral and ground currents.
  • Harmonic Analysis: Total Harmonic Distortion (THD) and individual harmonic orders up to the 50th or 63rd, identifying harmonic sources and their impact.
  • Power Factor and Energy: Displacement and true power factor, active, reactive, and apparent power, and energy consumption.
  • Event Detection: Detection and recording of sags, swells, transients, interruptions, and frequency deviations with timestamping and waveform capture.
  • Flicker Measurement: Short-term and long-term flicker (Pst and Plt) as per IEC 61000-4-15.
  • Unbalance Monitoring: Negative sequence and zero sequence voltage and current unbalance.
  • Data Logging and Trend Analysis: Continuous recording of parameters with configurable intervals, enabling trend analysis and predictive maintenance.
  • Alarming and Communication: Configurable alarms for threshold violations, with notifications via Modbus, SNMP, or digital outputs to the ALCMS.
Architecture

System Architecture & Control Logic

A Power Quality Monitor is an observation point, not a control point — it has no direct authority over the current loop, the CCR, or any fixture. Its role in the wider control architecture is to sample, analyse, and report: the diagram below shows how one sampled waveform is processed in parallel into every power quality parameter, then merged into a single logging and alarming stream that is pushed upstream via Modbus, SNMP, or a digital output. What happens next is decided elsewhere. Alarm data typically reaches the ALCMS, where it can be correlated with occupancy, weather, or maintenance schedules and turned into an action — dispatching a technician, logging a trend for predictive maintenance, or, where the PQM is monitoring a CCR's output directly, informing a decision to derate or trip that circuit. On sites using a Smart CCR, the two devices often sit side by side on the same communications network: the Smart CCR already self-monitors its own output quality internally, so an independent PQM adds an unbiased second measurement point plus broader visibility across sags, swells, and harmonics that a single regulator's own diagnostics wouldn't otherwise capture.

Voltage & Current Waveform Sampling (up to 512 samples/cycle)
DSP ENGINE
Harmonic Analysis (THD)
Event Detection (Sags/Swells/Transients)
Flicker (Pst/Plt)
Voltage/Current Unbalance
Power Factor & Energy
Data Logging & Trend Analysis
Alarming & Communication (Modbus/SNMP) → ALCMS

Monitoring only — the PQM reports data and alarms upstream but never issues a command back to the circuit itself.

Construction

Physical Construction

A Power Quality Monitor is typically a compact DIN-rail or panel-mounted instrument, housed in a moulded plastic or steel enclosure with a front-facing LCD or LED display for local readout of key parameters. Internally, high-accuracy voltage and current measurement circuitry — fed from voltage taps and current transformers on the monitored circuit — interfaces with a digital signal processor that computes harmonics, flicker, and other power quality indices. Communication ports (Ethernet, RS-485/Modbus, or USB) are provided on the rear or base for integration with the ALCMS or a dedicated power quality management system, along with terminal blocks for the voltage and CT current inputs and the unit's own low-voltage supply. Where installed within a CCR cabinet or distribution panel rather than as a standalone instrument, the PQM is typically DIN-rail mounted alongside the other control electronics, sharing the parent enclosure's cooling and cable entry provisions.

Specification

Technical Parameters

ParameterTypical Value
Measurement TypeTrue RMS, 3-phase + neutral + ground
Input VoltageUp to 600V AC (direct), 1000V with PT (potential transformer)
Input Current1A or 5A CT (current transformer) inputs
Frequency Range45–65 Hz
Harmonic AnalysisUp to 63rd harmonic for voltage and current
Sampling RateUp to 512 samples per cycle (25.6 kHz at 50 Hz)
AccuracyVoltage/current: ±0.1% of reading; Power: ±0.2% of reading
Communication ProtocolsModbus RTU (RS485), Modbus TCP (Ethernet), SNMP, DNP3, IEC 61850
Data StorageInternal memory (up to several GB) for waveform and trend data
DisplayGraphical LCD or touchscreen with real-time waveform display
EnclosurePanel-mount (IP52) or DIN-rail (IP20)
StandardsIEC 61000-4-30 (Class A or S), IEEE 1159, EN 50160
Power Supply

Electrical Requirements

RequirementTypical Value
Auxiliary Power Supply100–240V AC or 24–48V DC for the unit's own control electronics and display
Power Consumption< 15W typical (auxiliary supply, excludes sensed circuit)
Voltage Sensing InputDirect connection up to 600V AC, or via a potential transformer (PT) for higher voltages, with fused disconnect terminals
Current Sensing Input1A or 5A CT secondary inputs, fitted with CT shorting terminals for safe removal
Signal/Data CableShielded twisted-pair (RS-485) or Ethernet run to SCADA/ALCMS
Surge ProtectionSurge arrestors on voltage/current sensing inputs and on communication lines
Earthing/GroundingChassis and CT/PT secondary neutral bonded to the switchboard/panel earth bar
IsolationPT/CT inputs provide galvanic isolation from the primary high-voltage/current circuit being monitored
Backup PowerInternal battery or supercapacitor to maintain real-time clock and event logging through supply interruptions
Compliance

Applicable Standards

IEC 61000-4-30

Testing and measurement techniques — Power quality measurement methods (Class A accuracy)

IEEE 1159

Recommended practice for monitoring electric power quality

EN 50160

Voltage characteristics of electricity supplied by public distribution networks

IEC 61850

Communication networks and systems for power utility automation (for substation integration)

Prerequisites

Installation Requirements

DIN-Rail/Panel Mounting
Mechanical

Fit the instrument to the DIN rail or panel cut-out at the monitored circuit's location, keeping the front display accessible for local readout where fitted.

Voltage Tap Connection
Electrical

Connect the voltage measurement inputs directly or via potential transformers as required, confirming phase rotation and reference matches the monitored circuit.

Current Transformer Installation
Electrical

Install the current transformers with the correct polarity and burden rating, and never leave a CT secondary open-circuit while the primary is energised.

Low-Voltage Supply Connection
Electrical

Terminate the instrument's own low-voltage supply at the labelled terminal block, confirming voltage matches the unit's rating before energising.

Communication Cabling
Systems

Run and terminate the Ethernet, RS-485/Modbus, or USB link to the ALCMS or power quality management system, confirming the protocol and addressing match the design.

Configuration & Calibration
Systems

Configure CT/PT ratios, nominal voltage, and alarm thresholds to match the monitored circuit before any readings are relied upon.

Pre-Energisation Sign-off
Documentation

Record voltage/CT connections, ratio settings, and communication address as-built before the monitor is first energised.

Verification

Testing & Commissioning

Wiring & CT/VT Polarity Check
Pre-Energisation

Verify current and voltage transformer wiring and polarity into the monitor before energisation, since reversed polarity silently corrupts every downstream reading.

Calibration Verification Against Reference Meter
Energisation

Compare the monitor's voltage, current, and power readings against a calibrated reference meter at the same point, confirming accuracy within the specified tolerance.

Sag/Swell & Transient Event Simulation
Energisation

Inject a controlled voltage sag, swell, or transient and confirm the monitor detects, timestamps, and logs the event correctly.

Harmonic & THD Measurement Check
Energisation

Confirm harmonic and THD readings match an independent reference measurement, since these values often drive maintenance decisions on connected CCRs.

Alarm Threshold Verification
Final Acceptance

Confirm each configured alarm threshold triggers at the correct value and reports to the intended destination (panel, ALCMS, or SCADA).

Communication & Data Logging Verification
Final Acceptance

Confirm the monitor's historical log correctly timestamps and stores data, and that the communication link to the monitoring system remains stable under load.

Documentation & As-Built Sign-off
Final Acceptance

Record calibration, event-simulation, and alarm-threshold test results in the commissioning dossier for handover.

Upkeep

Inspection & Maintenance

CT/PT Ratio Verification
Annual

Verify current transformer and potential transformer ratio settings against the installed hardware, especially after any CT/PT replacement.

Calibration Check
Annual

Recalibrate measurement accuracy using a portable calibrator or factory service, since drift accumulates over time and undermines data integrity.

Communication Link Test
Semi-annual

Test Modbus TCP/RTU connectivity to the ALCMS and confirm any redundant communication paths are functional.

Storage & Logging Review
Quarterly

Check internal storage utilisation and logging intervals, and confirm automatic upload to the central historian to prevent data loss.

Firmware Verification
As needed

Apply firmware updates per manufacturer procedure and confirm compatibility with connected CCRs and the ALCMS.

Enclosure & Wiring Check
Annual

Inspect wiring terminations and enclosure seals for corrosion or looseness that could introduce measurement errors.

Field Notes

Common Field Issues

Incorrect CT/PT Ratios

Misconfiguration of current transformer (CT) and potential transformer (PT) ratios is a frequent error, leading to inaccurate readings. Always verify CT/PT settings during commissioning and after any replacement.

Communication Loss with ALCMS

PQMs often use Modbus TCP or RTU. Network interruptions, incorrect IP addressing, or baud rate mismatches can result in loss of data to the central system. Implement redundant communication paths and regular status checks.

Data Overload and Storage Management

Continuous logging of high-resolution data can quickly fill internal storage. Configure appropriate logging intervals and implement automatic data upload to a central historian to prevent loss of critical event data.

Calibration Drift

Over time, measurement accuracy can drift. Regular calibration (typically annually) using a portable calibrator or factory calibration service is essential to maintain the integrity of power quality data.

Diagnostics

Troubleshooting Guide

Inaccurate or Implausible Readings
Likely Cause
Current transformer (CT) or potential transformer (PT) ratios have been misconfigured, a frequent commissioning or replacement error.
Diagnostic Steps
Compare the configured CT/PT ratios in the monitor against the actual installed transformer ratings; cross-check a known load against the displayed reading.
Corrective Action
Correct the CT/PT ratio configuration in the monitor and re-verify readings against a calibrated reference.
Loss of Communication with the ALCMS
Likely Cause
Damaged or poorly terminated RS-485/Ethernet cabling, connector corrosion, or a network configuration mismatch (baud rate, parity, IP addressing) between the two devices.
Diagnostic Steps
Check cable continuity and shielding/grounding along the run; verify termination resistors are correctly placed; confirm both ends are configured with matching communication settings.
Corrective Action
Repair or replace the damaged cable section, correct the termination or configuration mismatch, and confirm stable communication over a sustained test period before returning to service.
Missing Event Data or Full Storage
Likely Cause
Continuous high-resolution logging has filled the monitor's internal storage, overwriting or preventing capture of new event data.
Diagnostic Steps
Check current storage utilisation and logging interval configuration; review whether automatic upload to a central historian is active.
Corrective Action
Adjust logging intervals to an appropriate resolution and configure automatic data upload to a central historian to prevent future storage loss.
Measurement Accuracy Drifting Over Time
Likely Cause
Normal component aging has caused the monitor's measurement accuracy to drift outside acceptable tolerance since its last calibration.
Diagnostic Steps
Compare current readings against a portable calibrator or reference instrument at the same measurement point.
Corrective Action
Perform calibration via a portable calibrator or the manufacturer's factory calibration service, and log the result against the annual schedule.
Reliability

Failure Modes & Root Causes

Sensor / CT Calibration Drift
Medium Severity
Root Cause
Ageing of current transformer or voltage sensing components, or thermal cycling gradually shifting the calibration reference over years of service.
Effect
Inaccurate or implausible readings that erode confidence in the monitor's data without an obvious fault indication.
Detection Method
Periodic calibration check against a reference meter, and trend review of readings for a gradual drift pattern.
Loss of Communication with the ALCMS
High Severity
Root Cause
Damaged or corroded communication cabling, a failed communication port, or electrical noise on a shared conduit run.
Effect
Power quality data stops reaching the ALCMS, leaving a gap in the centralised monitoring and trend record.
Detection Method
Communication diagnostic/heartbeat check at the ALCMS, and continuity testing of the comms cable.
Data Storage Full / Logging Failure
Low Severity
Root Cause
Storage media reaching end of write-cycle life, a full log buffer with no rotation configured, or file-system corruption after an unclean shutdown.
Effect
Missing event data or an inability to log new measurements, leaving gaps in the historical record.
Detection Method
Storage capacity and health check during maintenance, and verification that historical logs are complete after any monitor reboot.
Measurement Accuracy Drifting Over Time
Medium Severity
Root Cause
Component ageing in the analogue front-end, or accumulated thermal stress shifting reference voltages away from factory calibration.
Effect
Readings slowly diverge from actual circuit conditions, potentially masking a genuine developing power quality issue.
Detection Method
Scheduled calibration verification against a certified reference instrument, at the interval specified by the manufacturer.
Surge Damage to Input Circuits
High Severity
Root Cause
A lightning-induced transient or switching surge on the monitored power lines that exceeds the input protection rating.
Effect
Damaged sensing inputs, erratic readings, or complete loss of monitoring function on the affected channel.
Detection Method
Post-storm functional check of each monitored channel, and inspection of onboard surge protection devices for visible damage.
Firmware / Software Fault
Medium Severity
Root Cause
A firmware update interrupted mid-write, an electrical transient during operation, or a latent software fault triggered by a specific data condition.
Effect
Unit becomes unresponsive, reboots unexpectedly, or produces implausible readings until power-cycled or reflashed.
Detection Method
Event log review after an anomaly, and firmware version verification against the latest validated release.
Precautions

Safety & Operational Notes

Never Open-Circuit a Live CT Secondary
Electrical Safety

If the monitor is connected via current transformers, never open the CT secondary circuit while the primary is energised; an open CT secondary can develop a dangerous high-voltage spike. Always short the secondary before disconnecting the monitor's current inputs.

Live Voltage Measurement Points
Electrical Safety

Voltage inputs are typically wired directly to distribution busbars or CCR supply terminals; treat these connections as live at all times the monitored circuit is energised, and use rated test leads and PPE for any measurement or wiring work.

PPE for Work Near Live Instrumentation Wiring
Personnel Safety

Wear appropriate PPE when working inside a panel where the monitor's CT and PT wiring is present, since these connections often can't be isolated without also isolating the circuit being measured.

ESD-Sensitive Electronics
Operational

Use anti-static precautions when handling the monitor's internal processing board or communication interface cards.

Coordinate Before Isolating a Monitored Circuit
Operational

If diagnosing a power-quality event requires isolating the circuit the monitor is connected to, coordinate with ATC and raise a NOTAM as for any other work on that circuit.

Restore to Compliant State
Compliance

Confirm all CT/PT connections are correctly re-terminated and the monitor is reading plausible values before closing out the work, since a swapped or open CT connection can silently produce incorrect readings.

Field Insight

Engineering & Expert Notes

An Incorrect CT/PT Ratio Poisons Every Reading Downstream
Commissioning

If a current or voltage transformer's ratio is entered wrong in the monitor's configuration, every parameter it derives — harmonics, sags, unbalance — will be internally consistent-looking but systematically wrong, and the error can go unnoticed for a long time since nothing looks obviously broken. Verify CT/PT ratio configuration against the actual installed transformers at commissioning, not just trust the default or as-specified value.

Calibration Drift Is Slow and Easy to Miss Without a Reference Check
Calibration

A power quality monitor's own internal sensing can drift gradually from a true reference over years without producing any alarm, since the unit has no independent way to know its own readings have become inaccurate. Periodically verify calibration against a traceable reference meter rather than relying solely on the monitor's self-reported health status.

Alarm Thresholds Should Reflect the Site's Actual Supply, Not Generic Defaults
Configuration

A monitor left on factory-default alarm thresholds can either flood operators with nuisance alarms on a site with naturally noisier supply characteristics, or miss genuinely significant events on an unusually clean supply where the defaults are too loose. Tune alarm thresholds against the site's own baseline power quality data rather than leaving generic defaults in place.

Data Logging Storage Fills Up Silently
Maintenance

A monitor logging detailed waveform captures for every transient event can fill its onboard storage and begin overwriting older data without any obvious operator notification, right around the time a historical trend would actually be needed for an investigation. Review storage utilisation and logging retention settings on a schedule rather than assuming capacity is unlimited.

Losing Comms With the ALCMS Doesn't Mean the Monitor Has Stopped Working
Diagnostics

A power quality monitor can continue measuring and logging correctly at the device itself even while its link to the ALCMS is down, and treating "no data at the ALCMS" as "the monitor has failed" leads to unnecessary equipment replacement. Check the communication link and the device's local logs separately before concluding the monitor itself needs attention.

Correlate PQM Events With CCR Fault Timestamps
Troubleshooting

A sag, swell, or transient event logged by the power quality monitor at the same timestamp as a CCR fault trip is often the real root cause of that trip, but the two systems' records are rarely cross-referenced by default. Make a habit of checking PQM event history against any CCR fault timestamp during root-cause investigation rather than treating the CCR fault in isolation.

Quick Answers

Frequently Asked Questions

Short answers about the Power Quality Monitor: what it is, how it works, typical specifications, standards, maintenance and common faults.

Q1What is a Power Quality Monitor?

A Power Quality Monitor (PQM) is an advanced electronic instrument designed to continuously assess the quality of electrical power in AGL distribution systems. It measures a wide range of parameters including voltage sags/swells, harmonics (THD), flicker, unbalance, frequency deviations, and transient events. By providing real-time data and historical trend analysis, the PQM enables early detection of power quality issues that could affect the performance and lifespan of Constant Current Regulators (CCRs), UPS systems, and sensitive electronic controls.

Q2What is the purpose of a Power Quality Monitor?

The PQM exists because CCRs and other AGL electronics can degrade or fail from power-quality problems that never trip a simple overcurrent or overvoltage protection device — harmonics, flicker, and unbalance can quietly stress equipment for months before a failure finally appears, by which point the root cause is far harder to trace back to its source.

Q3Where is a Power Quality Monitor used and installed?

Power Quality Monitors are typically installed at key points in the AGL power distribution network, including: Main Incoming Supply: At the utility metering point to monitor the quality of power entering the airfield. Power Distribution Panels: At the input of each distribution panel to monitor power quality for all connected CCRs. CCR Inputs: At individual CCR input feeders to detect supply anomalies that could affect regulator performance.

Q4How does a Power Quality Monitor work?

A Power Quality Monitor operates by sampling voltage and current waveforms at high speed (typically up to 512 samples per cycle) and performing digital signal processing to extract a comprehensive set of power quality parameters. Key functions include: Voltage and Current Measurement: True RMS values for each phase, including neutral and ground currents. Harmonic Analysis: Total Harmonic Distortion (THD) and individual harmonic orders up to the 50th or 63rd, identifying harmonic sources and their impact.

Q5What are the typical technical parameters of a Power Quality Monitor?

Typical values are — Measurement Type: True RMS, 3-phase + neutral + ground; Input Voltage: Up to 600V AC (direct), 1000V with PT (potential transformer); Input Current: 1A or 5A CT (current transformer) inputs; Frequency Range: 45–65 Hz; Harmonic Analysis: Up to 63rd harmonic for voltage and current; Sampling Rate: Up to 512 samples per cycle (25.6 kHz at 50 Hz); Accuracy: Voltage/current: ±0.1% of reading; Power: ±0.2% of reading; Communication Protocols: Modbus RTU (RS485), Modbus TCP (Ethernet), SNMP, DNP3, IEC 61850; Data Storage: Internal memory (up to several GB) for waveform and trend data.

Q6What are the electrical requirements for a Power Quality Monitor?

Typical requirements are — Auxiliary Power Supply: 100–240V AC or 24–48V DC for the unit's own control electronics and display; Power Consumption: < 15W typical (auxiliary supply, excludes sensed circuit); Voltage Sensing Input: Direct connection up to 600V AC, or via a potential transformer (PT) for higher voltages, with fused disconnect terminals; Current Sensing Input: 1A or 5A CT secondary inputs, fitted with CT shorting terminals for safe removal; Signal/Data Cable: Shielded twisted-pair (RS-485) or Ethernet run to SCADA/ALCMS; Surge Protection: Surge arrestors on voltage/current sensing inputs and on communication lines.

Q7Which standards apply to a Power Quality Monitor?

The main references are IEC 61000-4-30 — Testing and measurement techniques — Power quality measurement methods (Class A accuracy); IEEE 1159 — Recommended practice for monitoring electric power quality; EN 50160 — Voltage characteristics of electricity supplied by public distribution networks; IEC 61850 — Communication networks and systems for power utility automation (for substation integration). Always verify the current edition and your aerodrome's approved requirements.

Q8How often should a Power Quality Monitor be inspected and maintained?

Typical maintenance tasks and intervals are: CT/PT Ratio Verification (annual); Calibration Check (annual); Communication Link Test (semi-annual); Storage & Logging Review (quarterly); Firmware Verification (as needed); Enclosure & Wiring Check (annual). Your airport's approved maintenance programme takes precedence.

Q9How do I troubleshoot common Power Quality Monitor faults?

Common symptoms covered are: Inaccurate or Implausible Readings; Loss of Communication with the ALCMS; Missing Event Data or Full Storage; Measurement Accuracy Drifting Over Time. For example, for "Inaccurate or Implausible Readings": Likely Cause: Current transformer (CT) or potential transformer (PT) ratios have been misconfigured, a frequent commissioning or replacement error. Diagnostic Steps: Compare the configured CT/PT ratios in the monitor against the actual installed transformer ratings; cross-check a known load against the displayed reading. Corrective Action: Correct the CT/PT ratio configuration in the monitor and re-verify readings against a calibrated reference.

Go Further

Go Beyond the Component. Understand the Complete AGL System.

You have explored the component. Now understand how it works within the complete Airfield Ground Lighting system.

Learn AGL from fundamentals to design, installation, testing, photometry, commissioning, maintenance and troubleshooting through structured technical training at Precision AGL Academy.

Build practical knowledge. Understand the circuit. Read the standards. Troubleshoot with confidence.

Your next step in AGL starts here.

The Learning Pathway
Learn Understand Design Test Maintain Document Apply Certify

Need expert guidance on power quality monitoring for your AGL system?

Precision AGL Academy provides advice on PQM placement, configuration, data interpretation, and integration with ALCMS for proactive maintenance.