Series circuit electrical fault diagnosis across the AGL constant-current loop — resistance and voltage-drop anomalies, current leakage and earth faults localised through light, transformer, cable, and connector, single- and multiple-point open circuits, high-resistance connections, and faults that only manifest under specific temperature, rainfall, or switching conditions. Each topic follows the full engineering diagnostic record: symptom → observation → measurement → decision → fault location → root cause → verification → corrective action → preventive action.
Symptom — A routine or pre-energisation loop resistance measurement on a series circuit reads noticeably different from the recorded as-built or last-known-good baseline, with no fixture reported dark and no CCR alarm active.
Series circuit primary loop (CCR secondary output through isolation transformers and cable back to CCR), as measured loop-to-loop or loop-to-earth with the circuit isolated.
Confirm the reading is stable and repeatable across at least two independent measurements, and that the circuit record has been reconciled with either an explanation or an updated baseline.
SOP: SOP-SCF-01 (Series Circuit Resistance Test Procedure), SOP-CCR-04 (CCR LOTO Procedure)
Standards: IEC 60364 (insulation/loop testing), ICAO Annex 14 Vol I, FAA AC 150/5340-30
Diagram: Series Circuit As-Built Drawing with Resistance Log
Case Study: Division 01 — CCR Troubleshooting (source-side verification)
Symptom — Total series circuit loop resistance measures significantly above baseline, and the CCR is having to drive a higher output voltage than normal to maintain the commanded constant current, potentially approaching the regulator's voltage limit or triggering a high-voltage alarm.
Series circuit primary loop — cable, splices, connectors, and isolation transformer primary windings in series around the CCR output.
After repair, re-test the full loop resistance and confirm the CCR output voltage for the commanded current has returned to its expected baseline range across all intensity steps.
SOP: SOP-SCF-02 (Loop Resistance Fault Location Procedure), SOP-CCR-04 (CCR LOTO Procedure)
Standards: IEC 60364, ICAO Annex 14 Vol I, FAA AC 150/5345-10 (constant current regulators)
Diagram: Series Circuit As-Built Drawing with Segment Breakpoints
Case Study: Division 01 — CCR Troubleshooting (output voltage limit alarms)
Symptom — Total series circuit loop resistance measures significantly below baseline, without a corresponding earth-fault alarm, suggesting a partial short or reduced-impedance path has developed between conductors or across a transformer winding.
Series circuit primary loop and isolation transformer primary windings, tested loop-to-loop with the circuit isolated.
After repair, re-test the full loop resistance and confirm it has returned to within the expected baseline range, with no residual reduced-impedance path detected.
SOP: SOP-SCF-03 (Reduced-Resistance Fault Location Procedure), SOP-CCR-04 (CCR LOTO Procedure)
Standards: IEC 60364, ICAO Annex 14 Vol I, IS 12290 (isolating transformers)
Diagram: Series Circuit As-Built Drawing
Case Study: Division 01 — CCR Troubleshooting (current regulation behaviour under reduced impedance)
Symptom — The voltage drop measured across a section of the series circuit — or the CCR's total output voltage for the commanded current — is higher than expected, without a hard open or earth fault present.
Series circuit primary loop, CCR output stage, and isolation transformer primary windings across the affected section.
After corrective action, re-measure section voltage drop and confirm CCR output voltage for the commanded current is within its normal operating range across all intensity steps.
SOP: SOP-SCF-04 (Voltage Drop Test Procedure), SOP-CCR-02 (CCR Output Verification)
Standards: ICAO Annex 14 Vol I, FAA AC 150/5345-10, IS 12290
Diagram: Series Circuit As-Built Drawing with Conductor Schedule
Case Study: Division 01 — CCR Troubleshooting (regulator output voltage limits)
Symptom — The measured series circuit current does not consistently match the value commanded for the selected intensity step, or differs when measured at different points around the loop, when in a true series circuit the current should be identical at every point.
CCR output, series circuit primary loop, and current measurement instrumentation/CTs used for monitoring.
After corrective action, confirm current readings match at multiple points around the loop and the earth-fault monitor shows no unexplained leakage, across all commanded intensity steps.
SOP: SOP-SCF-05 (Circuit Current Verification Procedure), SOP-CCR-02 (CCR Output Verification)
Standards: ICAO Annex 14 Vol I, FAA AC 150/5345-10
Diagram: CCR Panel Wiring and Instrumentation Diagram
Case Study: Division 01 — CCR Troubleshooting (current regulation faults)
Symptom — The CCR's earth-fault (ground-fault) monitor indicates a measurable leakage current from the series circuit to earth, below the level that trips protection, without any fixture reported dark.
Series circuit primary loop, isolation transformer insulation systems, and CCR earth-fault/ground-fault monitoring circuit.
After repair, re-megger the full loop and confirm the reading is restored above the acceptable threshold, and monitor the CCR earth-fault trend over subsequent operating cycles.
SOP: SOP-SCF-06 (Earth Leakage Fault Location Procedure), SOP-CCR-04 (CCR LOTO Procedure)
Standards: IEC 60364, ICAO Annex 14 Vol I, FAA AC 150/5340-30
Diagram: Series Circuit Route Drawing with Insulation Test Log
Case Study: Division 25 — Field Case Study Troubleshooting
Symptom — Segment-by-segment insulation testing has localised a confirmed earth fault to an individual light fixture, distinguishing it from a fault in the cable, transformer, or connector serving that fixture.
Light fixture body, base can, and the internal wiring between the fixture's secondary connection and its lamp/LED module.
After repair or replacement, re-megger the fixture in isolation and confirm the reading is restored above the acceptable threshold before reconnecting to the circuit.
SOP: SOP-SCF-07 (Fixture-Level Earth Fault Isolation Procedure), SOP-CCR-04 (CCR LOTO Procedure)
Standards: ICAO Annex 14 Vol I, FAA AC 150/5345-46, IEC 60364
Diagram: Fixture Assembly and Seal Detail Drawing
Case Study: Division 25 — Field Case Study Troubleshooting
Symptom — Segment-by-segment insulation testing has localised a confirmed earth fault to an isolation transformer, with the associated fixture, cable, and connector tested clear.
Individual isolation transformer serving one light fixture on the series circuit, including its primary and secondary windings and core.
After replacement, re-megger the new transformer in isolation and confirm the reading meets specification before reconnecting to the circuit, then re-test the full loop.
SOP: SOP-SCF-08 (Transformer Earth Fault Isolation Procedure), SOP-CCR-04 (CCR LOTO Procedure)
Standards: IS 12290, IEC 60364, FAA AC 150/5345-47 (isolation transformers)
Diagram: Isolation Transformer Test Data Sheet
Case Study: Division 25 — Field Case Study Troubleshooting
Symptom — Segment-by-segment insulation testing has localised a confirmed earth fault to a section of the series circuit primary cable itself, with the fixtures, transformers, and connectors serving that section tested clear.
Series circuit primary cable and its insulation system between two accessible test points (pull boxes, base cans, or transformer connections).
After repair, re-megger the full section and the full loop, and confirm the reading is restored above the acceptable threshold before backfilling and reinstating pavement.
SOP: SOP-SCF-09 (Cable Fault Location and Repair Procedure), SOP-CCR-04 (CCR LOTO Procedure)
Standards: IEC 60364, ICAO Annex 14 Vol I, FAA AC 150/5340-30
Diagram: Series Circuit Cable Route Drawing
Case Study: Division 25 — Field Case Study Troubleshooting
Symptom — Segment-by-segment insulation testing has localised a confirmed earth fault to an L-823 (or equivalent) connector, with the fixture, transformer, and cable on either side of it tested clear.
L-823 primary or secondary connector and its immediate base can environment.
After repair, re-megger the connector in circuit and confirm the reading is restored above the acceptable threshold, and re-check base can drainage before closing out.
SOP: SOP-SCF-10 (Connector Earth Fault Isolation Procedure), SOP-CCR-04 (CCR LOTO Procedure)
Standards: FAA AC 150/5345-26 (L-823 connectors), ICAO Annex 14 Vol I, IEC 60364
Diagram: Base Can and Connector Detail Drawing
Case Study: Division 25 — Field Case Study Troubleshooting
Symptom — Several lights on the same series circuit go dark at the same time, reported together rather than as separate individual failures, distinguishing this from an isolated single-light fault.
Series circuit primary loop feeding the affected run, and the isolation transformers/fixtures downstream of the suspected fault point.
After repair, re-energise the circuit and confirm every previously dark fixture on the run illuminates correctly at all intensity steps, with CCR output current and status normal.
SOP: SOP-SCF-11 (Multiple Light Failure Triage Procedure), SOP-CCR-04 (CCR LOTO Procedure)
Standards: ICAO Annex 14 Vol I, FAA AC 150/5340-30, FAA AC 150/5345-10
Diagram: Series Circuit As-Built Drawing with Run Sequence
Case Study: Division 24 — Complete Runway Lighting Failure
Symptom — A single light on an otherwise correctly functioning series circuit fails to illuminate, with every other fixture on the same circuit operating normally — the classic isolated single-point fault characteristic of a constant-current series circuit.
The individual fixture, its isolation transformer, and its L-823 connectors, isolated from the rest of the series loop.
After repair, re-energise the circuit and confirm the fixture lights correctly at all intensity steps, and verify no adjacent fixtures were disturbed during access.
SOP: SOP-SCF-12 (Single Fixture Fault Isolation Procedure), SOP-CCR-04 (CCR LOTO Procedure)
Standards: ICAO Annex 14 Vol I, FAA AC 150/5345-46, FAA AC 150/5340-30
Diagram: Fixture and Base-Can Layout Drawing
Case Study: Division 01 — CCR Troubleshooting (verify series circuit output)
Symptom — Standard single-fault localisation techniques (bracketing, halving, single-segment isolation) fail to produce a consistent result, because two separate faults exist simultaneously on the same series circuit, each partially masking or confusing the diagnosis of the other.
Series circuit primary loop, considered as a whole where two independent fault locations must be identified rather than one.
After repairing the first identified fault, re-test the full loop before assuming resolution — confirm whether a second anomaly remains, and only close out once both are independently verified clear.
SOP: SOP-SCF-13 (Multi-Fault / Two-Point Fault Diagnostic Procedure), SOP-CCR-04 (CCR LOTO Procedure)
Standards: IEC 60364, ICAO Annex 14 Vol I
Diagram: Series Circuit As-Built Drawing with All Test Points Marked
Case Study: Division 25 — Field Case Study Troubleshooting
Symptom — More than one genuinely independent open-circuit fault exists on the same series circuit at the same time, extinguishing more than one section of the loop and requiring each open point to be located and repaired separately.
Series circuit primary loop, considered across its full length where more than one break must be identified.
After each repair, re-test full loop continuity and confirm every previously dark section is restored before considering the circuit fully resolved.
SOP: SOP-SCF-14 (Multiple Open Circuit Diagnostic Procedure), SOP-CCR-04 (CCR LOTO Procedure)
Standards: ICAO Annex 14 Vol I, FAA AC 150/5340-30
Diagram: Series Circuit As-Built Drawing with Run Sequence
Case Study: Division 24 — Complete Runway Lighting Failure
Symptom — An open circuit exists somewhere on the series loop, but standard visual inspection at accessible points (base cans, pull boxes, connectors) shows no obvious damage — the break is internal to a component or cable that appears externally intact.
Series circuit primary cable, splices, and isolation transformer windings, where the physical break is not visible without further testing or disassembly.
After repair, re-test full loop continuity and resistance, and confirm the reading is stable and matches expectations under normal operating conditions.
SOP: SOP-SCF-15 (Hidden Fault Location Procedure), SOP-CCR-04 (CCR LOTO Procedure)
Standards: IEC 60364, ICAO Annex 14 Vol I
Diagram: Series Circuit As-Built Drawing
Case Study: Division 25 — Field Case Study Troubleshooting
Symptom — One or more lights on a series circuit go dark and then recover, or the CCR shows a momentary current drop, without a sustained fault being present at the time of inspection — the open circuit is making and breaking contact rather than remaining permanently open.
Series circuit primary cable, splices, connectors, and isolation transformer connections, particularly at points subject to vibration, thermal cycling, or moisture ingress.
Monitor the repaired point over several operating cycles, including varying intensity steps and, if possible, the conditions (temperature, vibration) that previously produced the fault, before closing out.
SOP: SOP-SCF-16 (Intermittent Fault Diagnostic Procedure), SOP-CCR-04 (CCR LOTO Procedure)
Standards: ICAO Annex 14 Vol I, FAA AC 150/5340-30
Diagram: Series Circuit As-Built Drawing
Case Study: Division 01 — CCR Troubleshooting (output current logging)
Symptom — A connection point on the series circuit has developed measurably elevated resistance without progressing to a full open circuit, producing localised heating, a voltage-drop anomaly, or gradual light dimming rather than an outright failure.
Any series-circuit connection point — splice, connector, terminal, or transformer connection — where contact resistance has increased above design values.
After remaking the connection, re-test its resistance and voltage drop under load, and re-check with thermal imaging on a subsequent live period to confirm normal temperature.
SOP: SOP-SCF-17 (High Resistance Connection Procedure), SOP-CCR-04 (CCR LOTO Procedure)
Standards: IEC 60364, ICAO Annex 14 Vol I
Diagram: Series Circuit As-Built Drawing
Case Study: Division 25 — Field Case Study Troubleshooting
Symptom — A series circuit fault appears, disappears, or changes in severity in correlation with ambient or component temperature — for example only manifesting on cold mornings, only after several hours of continuous energisation, or only during peak summer heat.
Any series-circuit component whose electrical or mechanical behaviour changes measurably with temperature — cable, splices, connectors, or transformer windings.
Confirm the repair holds under the same temperature/duration conditions that previously produced the fault, not only under comfortable test conditions, before closing out.
SOP: SOP-SCF-18 (Temperature-Correlated Fault Diagnostic Procedure), SOP-CCR-04 (CCR LOTO Procedure)
Standards: IEC 60364, ICAO Annex 14 Vol I
Diagram: Series Circuit As-Built Drawing with Fault Occurrence Log
Case Study: Division 25 — Field Case Study Troubleshooting
Symptom — A series circuit fault — typically an earth-fault trip, leakage reading, or intermittent light — appears specifically during or shortly after rainfall, and clears once the site dries out, without being present during dry-weather testing.
Series circuit primary cable, splices, connectors, base cans, and transformer housings, at any point where water can bridge or enter an otherwise intact insulation system.
Re-test insulation resistance during a subsequent rain event (or with a controlled water application if a genuine rain event is not practical to wait for) to confirm the repair holds under the conditions that previously produced the fault.
SOP: SOP-SCF-19 (Rain-Dependent Fault Diagnostic Procedure), SOP-CCR-04 (CCR LOTO Procedure)
Standards: IEC 60364, ICAO Annex 14 Vol I, FAA AC 150/5340-30
Diagram: Base Can Drainage Detail Drawing
Case Study: Division 25 — Field Case Study Troubleshooting
Symptom — A series circuit fault manifests specifically at the moment of energisation, de-energisation, or an intensity-step change, rather than during steady-state operation, suggesting the fault is related to switching transients rather than continuous loading.
CCR output switching stage, series circuit primary loop, and isolation transformers, considered specifically around the moment of a switching event.
Re-test across multiple subsequent switching events, including energisation, de-energisation, and step changes, to confirm the fault no longer recurs under normal switching operation.
SOP: SOP-SCF-20 (Switching Transient Fault Diagnostic Procedure), SOP-CCR-02 (CCR Output Verification)
Standards: FAA AC 150/5345-10, ICAO Annex 14 Vol I, IEC 60364
Diagram: CCR Output Waveform Reference Profile
Case Study: Division 01 — CCR Troubleshooting (soft-start and step-change behaviour)
A constant current regulator diagram shows the CCR's supply input, its regulated output into the series loop, and the brightness-step control. In series circuit fault work it tells you where to measure CCR output current and loop resistance, and which alarms or protection indications to expect from the regulator. Use it with the circuit's own as-built drawings, and see the AGL diagrams and schematics page for general circuit diagrams.
Quick answers about Series Circuit Electrical Faults troubleshooting in the AGL Troubleshooting Atlas.
Division 15 is the Series Circuit Electrical Faults Troubleshooting reference. It publishes 20 diagnostic topics, SCF-391 to SCF-410, for Series Circuit Electrical Faults on airfield ground lighting systems.
Every topic follows the same diagnostic record: the symptom, equipment/system, possible causes ranked by likelihood (high, medium or low), required tools, safety precautions, diagnostic procedure, test points, root cause verification, corrective action, preventive action and related references (SOPs, standards, diagrams and case studies).
The 20 topics are SCF-391 to SCF-410: Unexpected Circuit Resistance; Excessive Circuit Resistance; Low Circuit Resistance; Circuit Voltage Drop Excessive; Circuit Current Imbalance; Current Leakage to Earth; Earth Fault at Light; Earth Fault at Transformer; Earth Fault at Cable; Earth Fault at Connector; Multiple Simultaneous Light Failure; Single Light Failure; Two-Point Fault; Multiple Open Circuits; Hidden Open Circuit; Intermittent Open Circuit; High Resistance Fault; Temperature-Dependent Fault; Rain-Dependent Fault; Switching-Dependent Fault.
Each procedure starts with observation before any intervention. For example, SCF-391 (Unexpected Circuit Resistance) begins: Re-verify the baseline value in the circuit record and confirm it corresponds to the correct circuit and the correct test method (loop, or loop-to-earth).
Each topic lists its own precautions. For example, SCF-391 (Unexpected Circuit Resistance) starts with: LOTO the CCR before taking any resistance measurement.
Related references in the topics include SOP-SCF-01 (Series Circuit Resistance Test Procedure), SOP-CCR-04 (CCR LOTO Procedure), SOP-SCF-02 (Loop Resistance Fault Location Procedure), SOP-SCF-03 (Reduced-Resistance Fault Location Procedure), SOP-SCF-04 (Voltage Drop Test Procedure), SOP-CCR-02 (CCR Output Verification), SOP-SCF-05 (Circuit Current Verification Procedure) and SOP-SCF-06 (Earth Leakage Fault Location Procedure), and 14 more.
Where a standard applies, it appears in the topic's Related References. Those cited in this division include IEC 60364, ICAO Annex 14 Vol I, FAA AC 150/5340-30, FAA AC 150/5345-10, IS 12290, FAA AC 150/5345-46, FAA AC 150/5345-47 and FAA AC 150/5345-26.
Use the search box at the top of the page to filter the 20 published topics by code, fault name or keyword; matching topics open automatically. Each diagnostic record can also be downloaded as a Word (.doc) file.
Series circuit electrical faults — opens, shorts, ground faults, and insulation breakdown — each leave a distinct measurable signature.
Build the technical knowledge to understand how to read CCR output behavior, insulation resistance trends, and current/voltage anomalies to identify fault type before you ever go to the field.
Diagnose systematically. Understand the circuit. Build real AGL expertise.