What are the L-823 connector types?

The FAA plug and receptacle connectors for airfield lighting cables, sorted by type and by class.

L-823 CONNECTOR TYPES PLUG AND RECEPTACLE PAIRS · SIDE VIEW TYPE I · ONE CONDUCTOR · 25 A · 5000 V RECEPTACLEPLUGUNMATED · OPENMATED · CLOSEDTYPE II · TWO CONDUCTORS · 20 A · 600 VRECEPTACLEPLUGUNMATED · OPENMATED · CLOSEDMATCHED PAIRS ONLY · CURRENT FLOWS ONLY WHEN MATED THE CLASSIFICATION TYPE I · ONE CONDUCTOR 25 A, 5000 V · typically the series circuit cable TYPE II · TWO CONDUCTORS 20 A, 600 V · typically the secondary leads CLASS A · FACTORY MOULDED moulded to the cable at the factory CLASS B · FIELD ATTACHED fitted to the cable on site FROM CIRCUIT TO MATCHED CONNECTOR CIRCUIT SIDE PRIMARY OR SECONDARY CHOOSE THE TYPE CONDUCTORS, AMPS, VOLTS CHOOSE THE CLASS MOULDED OR FIELD FITTED MATCHED PAIR PLUG AND RECEPTACLE SCHEMATIC · NOT TO SCALE · SEE FAA AC 150/5345-26 FOR DIMENSIONS AND STYLES
Type I · 1 conductor
Type II · 2 conductors
Class A / Class B
The Fact Connectors & plugs

L-823 is the FAA specification for plug and receptacle cable connectors used in airfield lighting circuits, in FAA AC 150/5345-26. A connector is described by its type, which sets the conductors, current and voltage, and by its class, which sets how it is attached to the cable.

1The type sets the electrical rating

Type I has one conductor and is rated 25 A, 5000 V to ground. It is typically used on the series circuit cable. Type II has two conductors and is rated 20 A, 600 V between contacts (1500 V to ground). It is typically used on the secondary leads to the light. The circuit design decides which applies.

2The class sets how it is attached

Class A connectors are factory moulded to the cable. Class B connectors are field attached, fitted on site, so the quality of the workmanship decides how well the joint performs. Each type and class comes as a plug and a receptacle, and the specification also defines numbered styles for their shapes.

3Match the connector to the circuit

Type I and Type II are not interchangeable. Use the type, class and style that the circuit design and the manufacturer specify, never one rated below what the circuit needs, and confirm the requirements against the edition in force. A connector must also never be moulded to, or fitted on, a cable rated for a higher voltage than the connector itself. Never separate a primary connector on an energised series circuit: isolate at the CCR, lock out and prove the circuit dead first, because an open series circuit can reach a dangerous voltage.

DesignationWhat it meansTypical use
Type I1 conductor, 25 A, 5000 VSeries circuit cable
Type II2 conductors, 20 A, 600 VSecondary leads to the light
Class AFactory moulded to the cablePre-moulded leads and assemblies
Class BField attached to the cableCable terminated on site
Schematic: dimensions, styles and ratings are set by FAA AC 150/5345-26, which has been revised several times; AC 150/5345-26E (2021) is the current FAA edition. Check the edition that applies to your project, and follow the manufacturer’s instructions for fitting and sealing.
Entry 25 · Mounting hardware Entry 27 · Plug and receptacle anatomy

Frequently Asked Questions

Q1What is an L-823 connector?

L-823 is the FAA specification for plug and receptacle cable connectors used in airfield lighting circuits, FAA Advisory Circular 150/5345-26. A connector is described by its type, which sets the number of conductors and the current and voltage rating, and by its class, which sets how it is attached to the cable.

Q2What are the two L-823 connector types?

Type I has one conductor and is rated 25 amperes and 5000 volts. Type II has two conductors and is rated 20 amperes and 600 volts. In practice Type I is typically used on the series circuit cable and Type II on the secondary leads to the light, but the circuit design decides.

Q3What is the difference between Class A and Class B?

Class A connectors are factory moulded to the cable. Class B connectors are field attached, meaning they are fitted to the cable on site, so the quality of that workmanship matters.

Q4Can Type I and Type II connectors be mixed?

No. They differ in conductors, current and voltage rating, and they are not interchangeable. Use the type the circuit design and the manufacturer specify, and never use a connector with a lower rating than the circuit needs.

Q5Where can I find the full specification?

In FAA AC 150/5345-26, which also defines numbered styles for the plug and receptacle shapes. The advisory circular has been revised several times, so confirm which edition applies to your project and your airport authority's requirements.

Precision AGL Academy

See It. Understand It. Then Learn How to Engineer It.

Recognising an AGL system visually is the first step. The next step is knowing how to design, install, test, commission and maintain them correctly.

Build Practical AGL Engineering Skills

Go deeper with structured training from Precision AGL Academy, covering:

AGL Fundamentals Design & Electrical Engineering Approach Lighting Photometry Installation & Commissioning Maintenance & Troubleshooting

Learn how each light, sign and circuit works as part of a complete airport lighting system, not just as an isolated diagram.

See. Understand. Apply. Engineer.