Division 06 · FIX · Fixture-Level Physical Maintenance

Lighting Fixture Maintenance

The dedicated maintenance division for the physical AGL light fixture itself — covering every fixture type independent of where it sits on the airfield. Where Divisions 01–05 define when and why maintenance happens (preventive, corrective, predictive, condition-based, emergency), Division 06 is the technical reference for how the fixture is physically maintained: mechanically, optically, electrically, and environmentally.

Core principle: a light fixture is not considered properly maintained merely because it turns ON. Its mechanical condition, optical condition, electrical condition, environmental protection, and alignment must all remain acceptable together.

35
Topics in Division
05
Asset Groups (A–E)
05
Fixture Conditions Assessed
07
Step Core Sequence

Fixture Maintenance Model

Every fixture maintenance activity in this division follows the same underlying sequence, regardless of fixture type or airfield location — and is judged against the same five conditions.

Inspect
Clean
Repair / Replace
Align
Seal / Protect
Test
Record
Mechanical condition Optical condition Electrical condition Environmental condition Functional condition

Applicable Fixture Types

This division applies to the physical fixture regardless of application — the same mechanical, optical, electrical and environmental procedures apply wherever the fixture is installed.

Runway fixtures Taxiway fixtures Centreline fixtures Threshold / end fixtures Touchdown-zone fixtures Runway guard-light fixtures Approach-light fixtures Stop-bar fixtures Other AGL light fixtures

Fixture Maintenance Decision Logic

A working sequence technicians can apply to any fixture, from first observation through to closed-out record.

StepGuiding Question
1 · InspectWhat is physically wrong?
2 · CleanIs contamination causing the condition?
3 · AssessIs the component damaged or deteriorated?
4 · Repair / ReplaceCan the component be restored?
5 · AlignIs the fixture correctly positioned?
6 · Seal / ProtectIs the fixture protected against environmental ingress?
7 · TestDoes the fixture function correctly?
8 · VerifyIs the final condition acceptable?
9 · RecordHas the maintenance history been updated?

The 35 Topics

Grouped by fixture maintenance discipline — click any topic to expand its check points and acceptance condition.

A

Mechanical Maintenance

10 topics
MNT-FIX-001Fixture External Inspection
Inspect For
  • Cracks
  • Damage
  • Deformation
  • Corrosion
  • Missing components
  • Loose hardware
  • Damaged mounting
  • Contamination
  • Water evidence
  • Physical impact
Acceptance / Record

Record: significant defects against the fixture for corrective action.

MNT-FIX-002Housing Cleaning
Remove
  • Dust
  • Mud
  • Oil
  • Grass
  • Foreign material
  • Other contamination
Acceptance / Record

Method: compatible with the fixture material and manufacturer requirements.

MNT-FIX-003Housing Damage Assessment
Check For
  • Cracks
  • Dents
  • Deformation
  • Structural damage
  • Corrosion
  • Damaged sealing surfaces
  • Damaged optical compartments
Acceptance / Record

Classify as: Cosmetic → Repairable → Performance-affecting → Structural.

MNT-FIX-004Mounting-Bolt Tightening
Inspect For
  • Looseness
  • Corrosion
  • Missing hardware
  • Damaged threads
  • Incorrect assembly
Acceptance / Record

Torque: tighten using approved torque requirements — avoid uncontrolled over-tightening, which can damage fixture components or mounting arrangements.

MNT-FIX-005Mounting-Hardware Replacement
Replace
  • Bolts
  • Nuts
  • Washers
  • Clamps
  • Mounting components
Acceptance / Record

Suitability: replacement hardware matched to the fixture and installation environment.

MNT-FIX-006Frangible-Coupling Inspection
Inspect For
  • Cracks
  • Deformation
  • Damage
  • Corrosion
  • Improper installation
  • Evidence of impact
Acceptance / Record

Objective: confirm the fixture's intended frangible arrangement remains intact.

MNT-FIX-007Frangible-Component Replacement
Verify
  • Correct component
  • Correct installation
  • Correct orientation
  • Secure mounting
  • No obstruction or interference
Acceptance / Record

Use: the correct approved frangible component only.

MNT-FIX-008Fixture Alignment
Check
  • Horizontal orientation
  • Longitudinal / transverse orientation as applicable
  • Reference marks
  • Mounting position
Acceptance / Record

Re-check: alignment after any activity that could disturb the fixture.

MNT-FIX-009Fixture Elevation Verification
Look For
  • Settlement
  • Raised fixture
  • Damaged base
  • Mounting displacement
  • Pavement / interface changes
Acceptance / Record

Impact: incorrect elevation can affect both operational performance and mechanical protection.

MNT-FIX-010Fixture Orientation Verification
Confirm
  • Optical orientation matches intended application
  • Particularly critical for directional optical output
B

Optical Maintenance

7 topics
MNT-FIX-011Lens Cleaning
Method Must Not
  • Scratch the surface
  • Damage optical coatings
  • Leave residue
  • Reduce optical performance
Acceptance / Record

After cleaning: inspect the lens.

MNT-FIX-012Prism Cleaning
Check For
  • Dust
  • Oil
  • Mud
  • Water marks
  • Discolouration
  • Scratches
  • Cracks
Acceptance / Record

Handle: carefully — prisms are optical-critical components.

MNT-FIX-013Optical Contamination Removal
Possible Contamination
  • Dust
  • Mud
  • Oil
  • Water deposits
  • Insects
  • Vegetation
  • Foreign material
MNT-FIX-014Damaged Lens Replacement
Replace When Exhibiting
  • Cracks
  • Breakage
  • Severe scratches
  • Optical degradation
  • Discolouration
  • Other performance-affecting damage
Acceptance / Record

Sequence: Inspect → Clean → Secure → Verify optical condition → Functional test.

MNT-FIX-015Damaged Prism Replacement
Replace When Exhibiting
  • Cracks
  • Breakage
  • Severe contamination that cannot be removed
  • Optical degradation
  • Mechanical damage
Acceptance / Record

Critical: correct installation — prism orientation can affect optical performance.

MNT-FIX-016Optical-Component Inspection
Inspect
  • Lens
  • Prism
  • Reflector where applicable
  • Optical chamber
  • Optical seals
  • Internal contamination
  • Optical mounting
MNT-FIX-017Optical-Alignment Verification
Consider
  • Fixture orientation
  • Optical component position
  • Installation geometry
  • Intended light distribution
Acceptance / Record

Formal verification: use the applicable approved photometric test method where required, rather than relying on visual observation alone.

C

Electrical Maintenance

8 topics
MNT-FIX-018Lamp Inspection
Inspect
  • Lamp condition
  • Lamp seating
  • Contacts
  • Filament condition where applicable
  • Discolouration
  • Signs of overheating
  • Correct lamp type
MNT-FIX-019Lamp Replacement
Before Replacement
  • Isolate the equipment as required
  • Confirm correct lamp type / rating
  • Inspect lamp holder
  • Inspect contacts
Acceptance / Record

After installation: functional test → illumination verification → record replacement.

MNT-FIX-020LED-Module Inspection
Inspect For
  • Physical damage
  • Discolouration
  • Overheating
  • Loose connections
  • Moisture
  • Abnormal illumination
  • Driver / interface issues
MNT-FIX-021LED-Module Replacement
Before Replacement
  • Confirm correct module
  • Confirm compatibility
  • Inspect electrical connections
  • Inspect sealing surfaces
Acceptance / Record

After replacement: secure module, restore sealing, verify illumination, verify optical orientation where applicable.

MNT-FIX-022Secondary-Lead Inspection
Inspect For
  • Cuts
  • Cracks
  • Abrasion
  • Damaged insulation
  • Loose connections
  • Water exposure
  • Mechanical stress
  • Incorrect routing
MNT-FIX-023Secondary-Lead Replacement
Verify
  • Correct termination
  • Secure connection
  • Insulation integrity
  • Mechanical protection
  • Proper routing
Acceptance / Record

Use: correct approved components only.

MNT-FIX-024Connector Inspection
Inspect For
  • Moisture
  • Corrosion
  • Damage
  • Loose connection
  • Seal condition
  • Mechanical damage
  • Overheating evidence
Acceptance / Record

Note: a connector defect can present as a fixture failure.

MNT-FIX-025Connector Replacement
Sequence
  • Isolate the relevant circuit
  • Confirm correct connector
  • Remove defective connector
  • Inspect cable / lead
  • Install replacement
  • Verify connection
  • Restore sealing
  • Perform required electrical / functional checks
D

Environmental Protection

6 topics
MNT-FIX-026Gasket Inspection
Inspect For
  • Cracking
  • Hardening
  • Flattening
  • Deformation
  • Missing sections
  • Incorrect seating
  • Evidence of water ingress
MNT-FIX-027Gasket Replacement
Ensure
  • Correct gasket
  • Correct seating
  • Clean mating surfaces
  • Proper closure
  • No pinching
  • Proper sealing
MNT-FIX-028Seal Inspection
Inspect All Relevant Interfaces
  • Housing
  • Lens
  • Optical chamber
  • Cable entry
  • Connector interface
  • Access covers
MNT-FIX-029Water-Ingress Correction
Determine Probable Source
  • Failed gasket
  • Damaged seal
  • Cracked housing
  • Cable entry
  • Connector
  • Condensation
  • Poor installation
Acceptance / Record

Do not: simply remove water — correct the underlying condition.

MNT-FIX-030Corrosion Treatment
Assess
  • Location
  • Extent
  • Depth
  • Structural significance
Acceptance / Record

Threshold: minor surface corrosion may be treated per approved procedures; advanced or structural corrosion triggers a repair/replacement decision.

MNT-FIX-031Moisture Removal
Then Investigate
  • Why did moisture enter the fixture?
Acceptance / Record

Otherwise: moisture may return and produce repeated failures.

E

Restoration

4 topics
MNT-FIX-032Fixture Functional Check
Verify
  • Fixture operates
  • Correct intensity / function achieved where applicable
  • No abnormal behaviour exists
  • Connections are secure
  • Fixture is mechanically secure
MNT-FIX-033Fixture Illumination Verification
Check
  • ON / OFF operation
  • Correct colour where applicable
  • Correct optical output
  • No obvious abnormal dimming
  • No abnormal flickering
Acceptance / Record

Formal verification: photometric verification performed where required by the applicable inspection/testing program.

MNT-FIX-034Post-Maintenance Inspection
Final Check For
  • Loose hardware
  • Missing components
  • Open covers
  • Incorrect alignment
  • Cable / lead condition
  • Connector condition
  • Sealing
  • FOD
  • Tools / materials left behind
  • Overall fixture condition
MNT-FIX-035Maintenance Record
Record
  • Date
  • Location
  • Fixture ID
  • Fixture type
  • Maintenance activity
  • Defect
  • Component replaced
  • Part number where applicable
  • Technician / engineer
  • Test performed
  • Test result
  • Final condition
  • Remarks

Integration With Divisions 01–05

Division 06 does not replace the maintenance-management divisions — it is the fixture-level technical reference they invoke.

01
Preventive

Routine fixture cleaning, tightening, alignment and inspection.

02
Corrective

Failed fixture / component repair and replacement.

03
Predictive

Fixture failure-rate and performance trending.

04
Condition-Based

Fixture condition assessment and maintenance decision.

05
Emergency

Emergency fixture restoration after critical failure or damage.

Frequently Asked Questions

Quick answers about lighting fixture maintenance, based on the topics in this division.

7 QUESTIONS
Q1What is Lighting Fixture Maintenance in the AGL Maintenance Handbook?

It is the dedicated division for the physical AGL light fixture itself, covering every fixture type regardless of where it sits on the airfield. It does not replace the maintenance-management divisions; it is the fixture-level technical reference they invoke.

Q2What does Division 06 of the AGL Maintenance Handbook cover?

Division 06 (Lighting Fixture Maintenance) contains 35 topics in five groups: Group A Mechanical Maintenance (10 topics), Group B Optical Maintenance (7 topics), Group C Electrical Maintenance (8 topics), Group D Environmental Protection (6 topics) and Group E Restoration (4 topics).

Q3Is a fixture properly maintained just because it turns on?

No. Its mechanical, optical, electrical, environmental and functional condition, including alignment, must all remain acceptable together.

Q4Which fixture types does this division apply to?

Runway, taxiway, centreline, threshold and end, touchdown-zone, runway guard-light, approach-light and stop-bar fixtures, and other AGL light fixtures. The same mechanical, optical, electrical and environmental procedures apply wherever the fixture is installed.

Q5What is the core fixture maintenance sequence?

Seven steps: Inspect, Clean, Repair/Replace, Align, Seal/Protect, Test and Record.

Q6What questions guide fixture maintenance decisions?

Technicians work through a decision logic: what is physically wrong, is contamination causing the condition, is the component damaged or deteriorated, can it be restored, is the fixture correctly positioned, is it protected against environmental ingress, does it function correctly, is the final condition acceptable, and has the maintenance history been updated.

Q7How does Division 06 connect to Divisions 01 to 05?

Division 01 uses it for routine fixture cleaning, tightening, alignment and inspection; Division 02 for failed fixture and component repair; Division 03 for fixture failure-rate and performance trending; Division 04 for fixture condition assessment and maintenance decisions; and Division 05 for emergency fixture restoration after critical failure or damage.

Go Further

Don't Just Service the Fixture. Understand Its Performance.

Lighting fixture maintenance is more than cleaning a lens and checking a bulb.

Build the technical knowledge to understand photometric performance, optical degradation, mounting integrity, and how fixture condition affects the wider AGL system.

Maintain the fixture. Protect the photometrics. Understand the system.