How is a series circuit routed?

A series circuit is one closed loop. The primary cable leaves its CCR, passes through the isolation transformer at every light and comes back to the same CCR, carrying the same current all the way round.

RUNWAY OUT ALONG ONE EDGE, BACK ALONG THE OTHER CIRCUIT ACIRCUIT Blights alternate A / B (interleaved) LIGHTING VAULT CCR B CCR A loop starts and ends here ONE LIGHT, ENLARGED (SCHEMATIC) PRIMARY LOOP (SERIES, THROUGH THE PRIMARY) ISOLATION TRANSFORMER lamp / LED load on secondary Same current through every transformer primary.A failed lamp does not open the loop.A cut primary cable puts the whole circuit out. 1 2 3 4 5
circuit A primary cable
circuit B primary cable
isolation transformer at each light
light (secondary side)
The Fact Circuit practice

In a series circuit the lights are not wired in parallel across a voltage. Instead one primary cable forms a loop that starts and ends at a constant current regulator, and the CCR holds the loop current at the selected brightness step. Every light connects to the loop through an isolation transformer, so the same current flows through every transformer primary whatever the length of the loop.

On the airfield the loop is routed along the edge of the pavement, usually in duct banks or direct-buried cable. It goes out past the lights, then returns to the vault, either beside the outgoing run or around the opposite edge. Where the design needs resilience, lights are interleaved between two circuits, so a cable fault on one circuit leaves every second light lit. A cut primary cable opens the loop and puts the whole circuit out, which is why the loop must be treated as live until its CCR has been isolated and made safe.

1 · Start and End at the CCR
Each loop leaves one CCR output terminal and returns to the other, so it is a closed circuit with one regulated current.
2 · Out and Back Routing
The primary cable follows the pavement edge to the farthest light, then returns, either alongside the outgoing run or around the other side.
3 · Isolation Transformer per Light
The primary cable passes through each transformer’s primary connection; the lamp is on the secondary side.
4 · Interleaved Circuits
Alternate lights are on two circuits so that losing one circuit leaves half the pattern lit.
5 · Cable Corridor
Duct banks or direct-buried cable along the edge of the pavement, with protection and spare capacity set by the design.
Circuit typeSingle closed loop, constant current
Lights per loopEach through its own isolation transformer
Start / endSame CCR in the vault
ReferenceFAA AC 150/5340-30 · AC 150/5345-10 · ICAO Annex 14 Ch. 8 · Doc 9157 Part 5
Diagram is a schematic plan, not to scale. The alternating A/B lights on the runway edge are illustrative: interleaving is normally specified for CAT II/III centreline, touchdown-zone and approach lighting. Arrows and moving pulses mark the route of the loop; the current is alternating, so it has no single direction of flow. Circuit count, loop length, routing and interleaving depend on the airfield design, the load calculation and the applicable standard; follow the design drawings. Never open an energised series circuit.
Entry 22 · CCR location Entry 24 · Transformer locations

Frequently Asked Questions

Q1What is a series circuit in airfield lighting?

A series circuit is a single closed loop of primary cable that starts and ends at a constant current regulator (CCR). The same current flows through every part of the loop, and each light takes its power through an isolation transformer connected in that loop.

Q2How is a series circuit routed on the airfield?

The primary cable leaves the CCR in the airfield lighting vault, runs along the pavement edge through each light’s transformer connection, and returns to the same CCR. Depending on the layout it goes out and back along the same corridor or around both sides of the pavement, in duct banks or direct-buried cable with the design’s protection.

Q3Why does each light use an isolation transformer?

The transformer couples the light to the primary loop without a direct electrical connection. If a lamp fails, the transformer lets the loop current keep flowing, so one failed lamp does not put out the whole circuit. It also keeps the primary circuit isolated from the lamp and its wiring.

Q4What is interleaving of series circuits?

Interleaving alternates the lights of a pattern between two circuits so that one circuit failure leaves every second light on instead of a dark gap. It is used where the design calls for it, for example on CAT II/III runway centreline, touchdown zone and approach lighting, following FAA AC 150/5340-30 and ICAO Annex 14.

Q5What happens if a series circuit cable is cut?

The loop opens, current stops and every light on that circuit goes out. Treat a series circuit as live until the CCR has been isolated and locked out under site procedures; never break an energised loop, because the CCR will try to hold its current.

Precision AGL Academy

See It. Understand It. Then Learn How to Engineer It.

Recognising an AGL system visually is the first step. The next step is knowing how to design, install, test, commission and maintain them correctly.