How do you troubleshoot a series circuit?

Match the symptom to the likely places in the loop, then narrow the fault down by section with the circuit isolated.

SERIES-CIRCUIT TROUBLESHOOTING · SYMPTOM TO LIKELY PLACECCRABCDESERIES LOOPsame current through every lightA CABLE · B JOINT · C CONNECTOR · D ISOLATION TRANSFORMER · E FIXTUREALL LIGHTS OUTA B C · open circuit · continuity by sectionCCR TRIPS, EARTH FAULTA B C D · low insulation · IR by sectionSOME LIGHTS OUTD E C · local fault · test that deviceDIM, LOW CURRENTA B C D · leakage or load · compare with stepFLICKERING, INTERMITTENTB C A · loose or wet · inspect when isolatedALWAYSTELL ATC · ISOLATE AND LOCK OFF THE CCR · AUTHORISED PERSONNEL ONLYSeries circuits run at high voltage. Use the fault-isolation flowchart to narrow the fault to one section.
open loop / circuit
earth fault / safety
local fault
dim / low current
The Fact Circuit fault tracing

In a series circuit the same current flows through every light, so the symptom shows how far a fault reaches. All lights out usually means the loop is open: a break in a cable, joint or connector, tested with continuity checks. An earth-fault alarm, or a CCR trip caused by an earth fault, means current is leaking to earth, tested with insulation resistance by section; a trip can also come from an open circuit, overload or overcurrent, which is why the CCR is read first. Some lights out with the loop still complete suggests a local fault at the fixture, connector or isolation transformer. Dim lights point to the step setting, or to leakage or heavy loading that stops the CCR delivering its current, and flickering suggests a loose or wet connection.

The map shows where in the loop each symptom is likely to start, but it only suggests where to look. The CCR is read first, because it is often reporting the circuit problem, and the fault-isolation flowchart narrows the fault to one section by half-split. ATC is told, the CCR is isolated and locked off, and only authorised personnel work on the circuit. Test methods and limits come from the manufacturer, the standards and the airport’s safe-working rules.

All lights outOpen loop: cable, joint, connector
CCR tripEarth fault, low insulation
Some lights outLocal: fixture, transformer
Dim, low currentStep, leakage, heavy load
FlickeringLoose or wet connection
Open testsContinuity by section
Earth testsInsulation resistance
ReferenceICAO Doc 9157 Part 5; FAA AC 150/5340-26 (maintenance of airport visual aid facilities); manufacturer manuals and airport safe-working rules
Awareness schematic only, not a fault-finding procedure. Series circuits run at high voltage and can be lethal. Isolation, lock-off, test methods and limits come from the manufacturer, the standards and the airport’s own safe-working rules, and only trained and authorised personnel work on them.
Entry 17 · CCR troubleshooting Entry 19 · Transformer troubleshooting

Frequently Asked Questions

Q1Why is a series circuit troubleshot differently from a parallel one?

In a series circuit the same current flows through every light, so one break stops the whole loop and one leak to earth affects the whole circuit. The symptom shows how far the fault reaches, which helps decide where in the loop to look.

Q2What does it mean when all the lights on a circuit are out?

First confirm the CCR is on, has its supply and has not tripped or been locked out. If it is running and reports an open circuit, the loop is broken somewhere: a cable, joint or connector, or less often a transformer primary. The break is located by testing continuity section by section with the circuit isolated.

Q3What does a CCR trip or earth-fault alarm point to?

An earth-fault alarm, or a trip caused by an earth fault, points to current leaking from the circuit to earth, often through damaged cable insulation or a wet joint or connector. Insulation resistance is tested section by section to find the section with the low reading. A CCR trip can also be caused by an open circuit, overload or overcurrent, so the CCR's fault indication is read first.

Q4Why can some lights be out while the rest stay on?

Each light is fed through its own isolation transformer, so a failed lamp, fixture, secondary connector or transformer secondary can affect one light while the loop stays complete. The fault is then local, and that device is checked. A break in a transformer primary is different: it opens the loop and puts out the whole circuit.

Q5Why would lights be dim if the CCR holds constant current?

The CCR is designed to hold the set current for each step. Dim lights can mean the step is set lower than expected, or that leakage or an unusually heavy circuit load stops the CCR delivering the right current. The measured current is compared with the step.

Q6Why are flickering or intermittent faults hard to find?

They come and go, often from a loose or wet connector, a damaged cable or a failing joint that only misbehaves in some conditions. Connections are inspected with the circuit isolated, and the conditions when it happens are recorded.

Precision AGL Academy

See It. Understand It. Then Learn How to Engineer It.

Recognising an AGL system visually is the first step. The next step is knowing how to design, install, test, commission and maintain them correctly.

Build Practical AGL Engineering Skills

Go deeper with structured training from Precision AGL Academy, covering:

AGL Fundamentals Design & Electrical Engineering Approach Lighting Photometry Installation & Commissioning Maintenance & Troubleshooting

Learn how each light, sign and circuit works as part of a complete airport lighting system, not just as an isolated diagram.

See. Understand. Apply. Engineer.