What is transformer voltage?

A series transformer’s voltage is not fixed. With the current held constant by the CCR, the voltage across each transformer follows its load, and the voltages along the loop add up to what the CCR must supply.

LIGHT FITTING FITTING 45 W SECONDARY ≈ 6.8 V ISOLATION TRANSFORMER 6.6 A : 6.6 A PRIMARY DROP ≈ SECONDARY SERIES CIRCUIT VOLTAGES ADD ALONG THE LOOP THE CCR SUPPLIES THE SUM SECONDARY VOLTAGE AT 6.6 A  ·  VOLTAGE ≈ POWER ÷ CURRENT 0 V 10 V 20 V ≈ 6.8 V = 45 W ÷ 6.6 A ILLUSTRATIVE VALUES · LOSSES IGNORED · NOT TO SCALE

Swipe to see the full diagram

secondary (fitting voltage)
primary (series circuit)
loop total
The Fact Circuit practice

Transformer voltage is the voltage across a series isolation transformer. The CCR holds the loop current constant, so the voltage is not fixed: it follows the load. Roughly, voltage = power ÷ current, so a 45 W fitting at 6.6 A has about 6.8 V across its secondary, and on a 1:1 unit the primary drops a similar amount, a little more for the transformer’s own losses (about a third as much on a 20 : 6.6 A unit).

Every primary is in series, so the voltages add along the loop. The CCR must supply the sum of all the primary drops plus the voltage lost in the cable, which on a long circuit can reach thousands of volts even though each transformer only sees a few. Brightness is set by the loop current, not the voltage. Because the loop is high voltage, treat every primary and secondary lead as live and isolate and make the circuit safe under site procedures before any work.

Secondary Voltage
The voltage across the secondary, delivered to the fitting. At constant current it follows the fitting’s power, roughly power ÷ current.
Primary Voltage Drop
The drop across the primary winding in the loop. On a 1:1 unit it is close to the secondary voltage, plus a little for the transformer’s losses; on a 20 : 6.6 A unit it is about a third of it.
Loop Voltage
The sum of every primary drop plus the cable drop is what the CCR must supply. Power adds up the same way; see Transformer Load.
Insulation Rating
Primary leads, connectors, cable and transformer insulation are rated for the circuit’s high voltage, not only the few volts at the fitting. See Insulation Testing.
Across a transformerFollows load: about power ÷ current
CurrentConstant, set by the CCR (commonly 6.6 A, or 20 A on some circuits)
Loop voltageSum of primary drops plus cable drop
ReferenceFAA AC 150/5345-47 · ICAO Doc 9157 Part 5
Voltages in the diagram are illustrative (power ÷ current, losses ignored). Power ÷ current is exact for a lamp load; for an LED fitting with a driver, use its apparent power in VA, so the voltage is a little higher than the watts alone suggest. Actual values depend on the fitting, the brightness step, the transformer and the cable; follow the design drawings and the applicable specification.
Entry 18 · Transformer load Entry 20 · Transformer current

Frequently Asked Questions

Q1What is transformer voltage in AGL?

The voltage across a series isolation transformer’s windings. The CCR holds the loop current constant, so this voltage is not fixed: it follows the load the transformer supplies, and, on a 1:1 unit, the primary drop is close to the secondary voltage plus a little for losses.

Q2Why does the voltage change when the current is constant?

Voltage is roughly power divided by current. With the current held constant by the CCR, a higher-power fitting has a higher voltage across its secondary and a lower-power one has less. For example, 45 W at 6.6 A is about 6.8 V.

Q3How do the voltages along the loop add up?

Every transformer’s primary is in series, so the CCR must supply the sum of all the primary drops plus the voltage lost in the cable. A long circuit with many lights can reach thousands of volts, even though each transformer only sees a few volts.

Q4Does voltage set how bright the lights are?

No. Brightness is set by the loop current, which the CCR changes in steps. The voltage follows from that current and the load.

Q5Why is the circuit hazardous if each fitting runs at a few volts?

Because the loop as a whole carries a high voltage, and the primary leads, connectors and cable are insulated for it. An open secondary can also show a higher voltage than normal. Treat every lead as live and isolate the circuit under site procedures before work.

Precision AGL Academy

See It. Understand It. Then Learn How to Engineer It.

Recognising an AGL system visually is the first step. The next step is knowing how to design, install, test, commission and maintain them correctly.

Build Practical AGL Engineering Skills

Go deeper with structured training from Precision AGL Academy, covering:

AGL Fundamentals Design & Electrical Engineering Approach Lighting Photometry Installation & Commissioning Maintenance & Troubleshooting

Learn how each light, sign and circuit works as part of a complete airport lighting system, not just as an isolated diagram.

See. Understand. Apply. Engineer.