How is a series cable sized?

Choosing the conductor for the primary loop: strong enough to install, insulated for the voltage, and large enough that it wastes little power and leaves the regulator headroom.

CABLE SIZING THE SMALLEST STANDARD SIZE THAT PASSES EVERY CHECK SAME CIRCUIT · 6.6 A · 5 KM LOOP · COPPER loss = I² × R · drop = I × R 6 MM² 15.4 Ω 671 W lost voltage drop 102 V 10 MM² 9.2 Ω 399 W lost voltage drop 60 V 16 MM² 5.8 Ω 250 W lost voltage drop 38 V LARGER CONDUCTOR = LESS LOSS, MORE COST AND WEIGHT WHAT THE CABLE MUST PASS 1 INSULATION RATING 5 kV class for series circuits 2 LOSS AND DROP I²R and I×R within limits 3 REGULATOR HEADROOM total volts under CCR rating 4 MECHANICAL STRENGTH pulling, handling, minimum size 5 INSTALLATION duct or buried, ground temperature 6 FUTURE GROWTH room for added lights or repairs THE METHOD 1 FIND LOOP LENGTH 2 PICK A TRIAL SIZE 3 CALCULATE R, LOSS, DROP 4 CHECK CCR VOLTAGE 5 CHECK INSTALLATION 6 STEP UP IF IT FAILS SCHEMATIC · ILLUSTRATIVE VALUES AT 20°C · USE THE CABLE DATASHEET AND THE APPLICABLE STANDARD
6 mm² (most loss)
10 mm²
16 mm² (least loss)
checks the cable must pass
The Fact Engineering concept

The current in a series circuit is only a few amperes, so a thin conductor can carry it. Yet cable size still matters, because the same current flows through kilometres of cable. Cable sizing balances loss, voltage and cost over that whole loop.

1Start with the loop length

Resistance depends on the total length of the series loop, out and back, and on the conductor size. For copper, about 3.08 Ω per km at 6 mm² falls to about 1.15 Ω per km at 16 mm². That resistance sets the I²R loss and the voltage drop, and both feed straight into the load calculation.

ConductorResistance per km (copper, 20°C)Loss at 6.6 A, 5 km loopVoltage drop
6 mm²3.08 Ω/km671 W102 V
10 mm²1.83 Ω/km399 W60 V
16 mm²1.15 Ω/km250 W38 V

2Check it against the regulator

Cable loss and drop add to the voltage the CCR must supply. The total must stay under the regulator’s rated output voltage at the top step, with margin. A larger cable can bring a marginal circuit back inside the limit, and sometimes lets a smaller regulator do the job.

3Insulation, strength and installation

Primary series cable is rated for 5 kV class insulation, because the circuit voltage and fault voltage are high. The conductor must also be strong enough to pull into duct or lay direct, so very small sizes are ruled out whatever the current. Ground temperature and the method of installation raise resistance in service, so allow for a warm cable, not the 20°C figure.

  1. Find the loop length. Add the outgoing and returning runs of the whole series circuit.
  2. Pick a trial size. Start from the minimum size the standard and the installer allow.
  3. Calculate. Resistance, I²R loss at the top-step current, and voltage drop.
  4. Check the regulator. Total circuit voltage, with the extra loss, under the CCR rating.
  5. Check strength and installation. Pulling tension, duct or burial, temperature.
  6. Step up if it fails. Take the next standard size and repeat, then stop at the smallest that passes.
TermMeaning
Conductor sizeCross-section of the copper, in mm² or AWG
Loop lengthTotal cable length in the series circuit, out and back
I²R lossPower wasted as heat in the cable
Voltage dropVoltage used up in the cable, current × resistance
Insulation ratingVoltage class the cable insulation is built for, 5 kV for series circuits
Operating temperatureCable temperature in service, which raises resistance
Schematic: resistances are standard copper values at 20°C and the 5 km, 6.6 A circuit is an illustrative example. Minimum conductor sizes, insulation classes and allowable loss are set by the applicable standard, the cable datasheet and the airport’s design basis. Cable requirements are covered in FAA AC 150/5345-7 (L-824, specified in AWG, commonly No. 8 AWG, about 8.4 mm²) and circuit design guidance in ICAO Doc 9157, Part 5. Regulator requirements sit in IEC 61820-3-2, which replaced IEC 61822. Confirm against the editions in force.
Entry 21 · Load calculation Entry 23 · Transformer sizing

Frequently Asked Questions

Q1What is cable sizing in airfield lighting?

Choosing the conductor size of the primary series cable so that it carries the circuit current safely, wastes little power, keeps the regulator inside its voltage limit, and is strong enough to install and last.

Q2Why is the current rarely the limit?

Series circuits run at a few amperes, so even a small conductor can carry the current without overheating. Loss, voltage drop and mechanical strength usually decide the size, not the current rating.

Q3How does cable size affect the load?

A larger conductor has lower resistance, so less I squared R power is wasted and less regulator voltage is used up. On a long circuit that can reduce the load and the regulator size needed.

Q4Why must the cable have a high insulation rating?

At full brightness a series circuit can run anywhere from several hundred volts to a few kilovolts, depending on its length and load, and a fault or surge can push the voltage on the cable well above that. Primary cable is therefore rated for 5 kV class insulation, to suit the circuit and the standard in use.

Q5Is a bigger cable always better?

No. Larger conductors cost more, are harder to pull and terminate, and past a point save little. The aim is the smallest standard size that meets loss, voltage and strength limits, with some room for growth.

Q6Does temperature matter?

Yes. Copper resistance rises as the cable warms, so loss and voltage drop are higher in service than the tabulated 20 degree figure. Duct or direct burial and the surrounding temperature feed into the calculation.

Precision AGL Academy

See It. Understand It. Then Learn How to Engineer It.

Recognising an AGL system visually is the first step. The next step is knowing how to design, install, test, commission and maintain them correctly.

Build Practical AGL Engineering Skills

Go deeper with structured training from Precision AGL Academy, covering:

AGL Fundamentals Design & Electrical Engineering Approach Lighting Photometry Installation & Commissioning Maintenance & Troubleshooting

Learn how each light, sign and circuit works as part of a complete airport lighting system, not just as an isolated diagram.

See. Understand. Apply. Engineer.