How is the load on a circuit calculated?

Adding up every watt a series circuit draws, from the fixtures, the transformers and the cable, so the regulator that feeds it is the right size.

LOAD CALCULATION ADD IT UP AT THE HIGHEST STEP, THEN SIZE THE CCR EXAMPLE · 60 FIXTURES · 6.6 A · 5 KM LOOP OF 6 MM² CABLE FIXTURE POWER 60 × 45 W 2,700 W TRANSFORMER LOSSES at 90% efficiency 300 W CABLE LOSS I²R 6.6² × 15.4 Ω 671 W TOTAL LOAD V ≈ P / I ≈ 556 V (PF ≈ 1) 3,671 W PICK THE CCR SIZE typical sizes: 4 · 7.5 · 10 · 15 kW ... 4 KW 92% LOADED TOO TIGHT 7.5 KW 49% LOADED NEXT SIZE UP 10 KW 37% LOADED SPARE ROOM MARGIN FOR GROWTH, AGEING, ERROR THE METHOD 1 COUNT FIXTURES 2 ADD TRANSFORMER LOSSES 3 ADD CABLE I²R 4 TOTAL AT TOP STEP 5 ADD MARGIN 6 NEXT SIZE UP SCHEMATIC · ILLUSTRATIVE VALUES · USE ACTUAL FIXTURE, TRANSFORMER, CABLE AND CCR DATA
fixture power
transformer losses
cable loss
total and CCR size
The Fact Engineering concept

A regulator can only drive so much load. Load calculation finds how much a circuit really draws, so the regulator is neither too small to hold the current nor so large that it runs poorly at light load.

1Add up what the circuit draws

The load is more than the lamps. Start with the fixture power of every light, then add the isolating transformer losses, because each transformer draws more than it delivers. Signs, other connected devices and any planned future lights go in too.

2Do not forget the cable

The same current flows through the whole series loop, so the cable wastes I²R as heat. On a long circuit that can be a large share of the load, and because it grows with the square of the current, it is largest at the top step. That is why the calculation is done at the highest step.

3Add margin, then size up

Total the load, add margin for growth, ageing and measurement error, then choose the next standard CCR size up. A regulator at its limit cannot take another fixture, and if the load outgrows it the current falls and the lights dim.

ItemHowExample
FixturesNameplate lamp or LED power × number of fixtures60 × 45 W = 2,700 W
Transformer inputFixture power ÷ transformer efficiency at that load2,700 ÷ 0.90 = 3,000 W
Cable lossI² × total series loop resistance6.6² × 15.4 = 671 W
Circuit loadTransformer input + cable loss3,000 + 671 = 3,671 W
Output voltageLoad ÷ rated current (approximate, assumes power factor near 1; otherwise use VA)3,671 ÷ 6.6 ≈ 556 V
CCR choiceLoad plus margin, then the next standard size up3.67 kW + 25% ≈ 4.6 kW, above 4 kW → 7.5 kW
  1. List the circuit. Count fixtures by type and note any signs or other devices.
  2. Get the data. Fixture power, transformer ratings and efficiency, cable resistance and length.
  3. Add transformer losses. Divide fixture power by transformer efficiency at that load.
  4. Add cable loss. Use the total loop resistance and the top-step current squared.
  5. Total and add margin. Allow for future lights, ageing and tolerance.
  6. Choose the CCR. Take the next standard size up and check it at light load.
TermMeaning
Circuit loadTotal power the circuit draws from the regulator at a given step
Transformer lossPower used in the isolating transformer, not delivered to the fixture
Cable lossI²R heating in the series cable, rising with the square of current
Loop resistanceTotal resistance of the series cable out and back
MarginSpare capacity kept for growth, ageing and error
CCR ratingOutput the regulator is built for, in kW or kVA, at its rated current
Schematic: the 60-fixture, 45 W, 90% efficiency, 15.4 Ω example is illustrative, and standard CCR sizes vary by manufacturer and standard. Real calculations use the actual fixture and transformer data, the cable resistance at operating temperature, and the regulator’s kW or kVA rating, including its behaviour at light load. Regulators are specified in FAA AC 150/5345-10 and IEC 61822, with guidance in ICAO Doc 9157, Part 5. Confirm against the editions in force.
Entry 20 · CCR step selection Entry 22 · Cable sizing

Frequently Asked Questions

Q1What is load calculation in airfield lighting?

Adding up all the power a series circuit draws, from the lamps or LED fixtures, the isolating transformers and the cable, so that a constant current regulator of the right size can be chosen.

Q2What goes into the load?

The power of every fixture on the circuit, the losses in each isolating transformer, and the I squared R loss in the series cable. Sign transformers, any other connected devices and spare capacity for future lights are added too.

Q3Why calculate at the highest step?

The highest step has the largest current, and cable loss rises with the square of current, so that is when the circuit draws the most power. If the CCR can carry that, it can carry the lower steps.

Q4Why not pick a CCR that matches the load exactly?

A regulator run at its limit has no room for added fixtures, ageing, a changed lamp type or measurement error, and loses the ability to hold current if the load grows. Designers add margin and then choose the next standard size up.

Q5Do LED fixtures change the calculation?

Yes. LED fixtures draw far less power than halogen lamps, so the load is smaller. The method is the same, but isolating-transformer efficiency and power factor are usually lower at these light loads, so check the circuit in VA as well as watts, and check the regulator's minimum-load behaviour and harmonics, using the manufacturer's data.

Q6What happens if the load is too large?

The CCR cannot reach the voltage needed to push the set current through the loop, so the current falls, the lights dim and the regulator may alarm. The cure is to reduce the load, split the circuit or fit a larger regulator.

Precision AGL Academy

See It. Understand It. Then Learn How to Engineer It.

Recognising an AGL system visually is the first step. The next step is knowing how to design, install, test, commission and maintain them correctly.

Build Practical AGL Engineering Skills

Go deeper with structured training from Precision AGL Academy, covering:

AGL Fundamentals Design & Electrical Engineering Approach Lighting Photometry Installation & Commissioning Maintenance & Troubleshooting

Learn how each light, sign and circuit works as part of a complete airport lighting system, not just as an isolated diagram.

See. Understand. Apply. Engineer.