What is circuit loading?

How full the regulator is. The same circuit can leave a CCR comfortably loaded, nearly full or barely used, and each state has its own problems.

CIRCUIT LOADING HOW FULL IS THE REGULATOR, AND WHAT CHANGES IT ONE 7.5 KW CCR · THREE STATES OF THE SAME CIRCUIT loading = circuit load ÷ CCR rating, at the top step LIGHT DESIGN LIMIT TODAY 60 fixtures, 45 W 3,671 W · 49% ADD 20 FIXTURES +1,000 W input 4,671 W · 62% LED RETROFIT 60 × 15 W, same cable 1,671 W · 22% ZONE EDGES ARE SCHEMATIC · USE THE CCR DATASHEET WHAT MOVES THE LOADING 1 ADDING FIXTURES more load, loading rises 2 EXTENDING CABLE more I²R, loading rises 3 LED RETROFIT less load, may become too light 4 FAILED FIXTURES load falls as lights go dark 5 INTENSITY STEP lower step, lower current and load 6 SPLITTING CIRCUITS shares load between regulators THE METHOD 1 LOAD AT TOP STEP 2 DIVIDE BY CCR RATING 3 COMPARE TO DESIGN RANGE 4 CHECK LIGHT LOADING 5 RE-CHECK AFTER CHANGES 6 ADJUST THE CIRCUIT SCHEMATIC · ILLUSTRATIVE VALUES · USE THE CCR DATASHEET FOR MINIMUM AND MAXIMUM LOADING
design range
load added
light loading
near the limit
The Fact Engineering concept

Load calculation finds how many watts a circuit draws. Circuit loading asks the next question: against the regulator’s rating, how much is that? It is the load as a share of what the CCR can deliver, normally checked at the highest step.

1Too light and too heavy are both problems

A regulator is built to work within a range. Very light loading can leave it with poor power factor and less accurate regulation, depending on the design. Very heavy loading leaves no margin, and a regulator pushed past its rating cannot hold the current, so the lights dim. The goal is the middle.

LoadingWhat it meansAction
LightFar below rating: power factor and regulation accuracy can suffer, depending on designCheck the manufacturer's minimum loading; consider a smaller CCR or combining circuits
Design rangeComfortably inside the rating with room to growThe aim for a new circuit
Near the limitLittle or no margin: one more fixture or longer cable can overload itPlan a larger CCR, or split the circuit

2Loading does not stay put

It rises when fixtures are added or cable is extended, and falls when fixtures fail or are replaced by lower-power types. An LED retrofit shows the catch: the fixtures draw far less, but the cable loss is unchanged at the same current, so the load does not fall in proportion. In the example, loading drops from 49% to 22% and may now be too light.

3Manage it by design and by checking

Size the CCR so the day-one loading sits in the design range with room to grow. Re-check it after every change to the circuit, including retrofits and repairs. If a circuit is too light, a smaller regulator or a combined circuit may suit; if it is too heavy, split the circuit or fit a larger regulator.

  1. Take the load. Use the circuit load at the highest step from the load calculation.
  2. Divide by the rating. Compare like with like, kW with kW or kVA with kVA, to get the loading as a percentage.
  3. Compare with the design range. Not too light, not near the limit.
  4. Check light loading. Confirm the CCR still regulates well, using the manufacturer’s minimum.
  5. Re-check after changes. Added fixtures, longer cable, retrofits, failures.
  6. Adjust. Split, combine or resize the circuit if loading has left the range.
TermMeaning
Circuit loadingCircuit load as a percentage of the CCR rating
Circuit loadTotal power the circuit draws, from the load calculation
CCR ratingkW or kVA the regulator is built to deliver at rated current
Minimum loadingLowest load at which the CCR still meets its specification
Design rangeLoading band that leaves room for growth without running too light
Circuit splittingDividing fixtures between regulators to bring loading back in range
Schematic: the 7.5 kW regulator and the three loads are illustrative, built from the Load Calculation example (the LED case assumes 15 W fixtures, 90% transformer efficiency and the same 671 W of cable loss). The zone edges are not specification limits; minimum and maximum loading come from the regulator’s datasheet and the standard it is built to. Regulators are covered in FAA AC 150/5345-10 and IEC 61822, so confirm against the editions in force.
Entry 23 · Transformer sizing Entry 25 · Reliability

Frequently Asked Questions

Q1What is circuit loading?

How much of a constant current regulator's rated capacity the series circuit actually uses, usually shown as a percentage of the regulator's kW or kVA rating at the highest step.

Q2How is it different from load calculation?

Load calculation finds how many watts the circuit draws. Circuit loading divides that figure by the regulator's rating to show how full the regulator is, and so whether it is well matched.

Q3What is wrong with a very light load?

A regulator run far below its rating can have poor power factor, more waveform distortion and less accurate current regulation, depending on its design. Check the manufacturer's stated minimum loading.

Q4What is wrong with a very heavy load?

There is no room for added fixtures, ageing or measurement error, and if the load grows past the rating the regulator cannot hold the current. The lights dim and the regulator may alarm.

Q5Why can an LED retrofit make loading worse?

LED fixtures draw far less than halogen lamps, so the load falls. But the cable loss stays the same at the same current, so the circuit may drop below the regulator's comfortable range.

Q6How does loading change over time?

It rises when fixtures are added or cable is extended, and falls when lamps are replaced by lower-power types or fixtures fail. Check it again after any change to the circuit.

Precision AGL Academy

See It. Understand It. Then Learn How to Engineer It.

Recognising an AGL system visually is the first step. The next step is knowing how to design, install, test, commission and maintain them correctly.