Screen Connector
A specialised connector used to terminate and bond the metallic screen or shield of shielded AGL cables to earth, equipment chassis, or junction boxes. Provides a low‑impedance path for electromagnetic interference (EMI), reduces capacitive coupling, and ensures safety by preventing electrostatic discharge and minimising interference with sensitive AGL control and monitoring systems.
Image disclaimer: For identification and illustration only. It may show a product by another manufacturer and may not depict the exact item described; it is not a statement of any product’s quality, approval or performance. Third-party image and trademark rights belong to their owners. See full notice.
What Is It?
A Screen Connector (also known as a shield connector, screen termination, or cable screen clamp) is a specialised termination device used to connect the metallic screen (shield) of shielded AGL cables to earth, equipment chassis, or junction box earth terminals. The screen connector provides a low‑resistance, low‑inductance path to earth for induced currents and electromagnetic interference (EMI), ensuring the integrity of signal and power circuits in AGL systems.
Shielded cables are used in AGL systems where electromagnetic compatibility (EMC) is critical—such as communication links, control circuits, sensitive sensor wiring, and connections between CCRs and ALCMS systems. The screen connector:
- Terminates the cable screen: Provides a secure mechanical and electrical connection to the cable's metallic screen (braid, foil, or spiral wrap).
- Bonds to earth: Connects the screen to the earthing system, providing a low‑impedance path for interference currents.
- Reduces EMI: Prevents the cable screen from acting as an antenna, reducing radiated and conducted emissions.
- Prevents electrostatic discharge (ESD): Safely dissipates static charges that can build up on the cable screen.
Screen connectors are available in various configurations, including clamp‑on types, crimp‑on lugs, compression glands with integral screen termination, and solder‑type terminations. They are typically made of tinned copper, brass, or stainless steel for corrosion resistance and low contact resistance.
Purpose & Function
A shielded cable's screen only works if it is actually connected to earth at every termination point, and the screen connector is the component that makes that connection real rather than theoretical. Without it, the metallic screen is simply a floating conductor that can accumulate static charge or, worse, act as an unintended antenna that re-radiates the interference it was meant to block. By providing a secure, low-impedance bond from the screen to earth, the connector completes the circuit path that carries induced currents away safely, which is what allows the shielded cable elsewhere on the page to deliver its EMI protection in practice rather than only on paper.
Where Is It Used?
Screen connectors are used throughout the airfield wherever shielded cables are employed and screen termination is required, including:
- AGL Control and Monitoring Cables: Terminating the screens of control cables between CCRs, ALCMS workstations, and field equipment to prevent EMI interference.
- Communication Links: Screen termination for fibre optic cable metallic members, telephone lines, and data communication cables.
- Sensor Cables: Terminating screens on weather sensors, RVR sensors, and other sensitive instrumentation cables.
- Junction Boxes and Distribution Panels: Providing a screen termination point within junction boxes and panels for incoming shielded cables.
- CCR Output Cables: For shielded primary cables used in environments with high EMI (e.g., near radar or high‑power transmitters).
- Retrofit and Upgrades: Adding screen termination to existing installations when upgrading to shielded cables for improved EMC performance.
The connector is selected based on the cable screen type (braid, foil, or combination), the screen material (copper, tinned copper, or aluminium), the cable diameter, and the required termination method (crimp, clamp, or solder). Proper screen termination is essential for ensuring the effectiveness of the cable shielding.
Installation & Location
The connector is installed at each point along a shielded cable's run where the screen needs to be bonded to earth, typically at junction boxes, equipment enclosures, and cable termination points rather than at intermediate positions along a continuous run. The cable's outer jacket is stripped back to expose the screen (braid, foil, or combination) without damaging the underlying insulated conductors, and the connector is then clamped, crimped, or soldered onto the screen to create a secure mechanical and electrical bond. From there, a short bonding lead connects the screen connector to the local earth bar or chassis earth point, kept as short and direct as practicable, since a long or coiled bonding lead adds inductance that reduces its effectiveness at higher frequencies. Where a cable run enters multiple enclosures, the screen is typically terminated at each entry point rather than left floating partway along the route, so no section of the shield is left unbonded.
How Does It Work?
A screen connector provides a secure, low‑impedance electrical connection between the cable screen and the earthing system. Its design ensures that the screen is effectively bonded to earth, preventing the screen from becoming an antenna that radiates or picks up interference. The functional principles vary by connector type:
- Clamp‑on Screen Connectors: A split ring or clamp that wraps around the cable screen, with a tightening screw or bolt that compresses the clamp onto the screen. A tail or lug provides a connection point for the earth wire. This type is easy to install and allows for screen termination without cutting the screen.
- Crimp‑on Screen Lugs: A lug with a barrel that accepts the gathered screen braid. The braid is inserted into the barrel and crimped using a standard crimping tool. The lug is then bolted to the earth terminal. This provides a permanent, low‑resistance connection.
- Compression Glands with Screen Termination: Cable glands that incorporate a screen termination ring or spring. When the gland is tightened, the ring compresses against the cable screen, providing a 360° conductive path to the gland body, which is then earthed.
- Solder‑type Screen Terminations: The screen braid is tinned and soldered directly to a terminal or lug. This provides a very low‑resistance connection but requires skilled labour and is less common in field installations.
Key performance requirements for a screen connector include:
- Low Contact Resistance: The connection must have a resistance of a few milliohms to ensure effective EMI suppression.
- Low Inductance: A short, direct path to earth minimises the inductive impedance at high frequencies, which is critical for effective EMI suppression.
- Mechanical Integrity: The connection must withstand vibration, thermal cycling, and mechanical stress without loosening or breaking.
- Corrosion Resistance: The connector materials must resist corrosion to maintain long‑term low resistance.
The screen connector is typically connected to a dedicated earth terminal or to the equipment chassis, which is itself bonded to the main earthing system. The connection should be as short and direct as possible to minimise inductance.
System Architecture & Control Logic
The screen connector sits outside the constant current series circuit and its ALCMS/CCR control loop — it bonds a cable's screen or braid to earth for EMI suppression and carries no lighting current in normal operation. Because it plays no part in the current the CCR regulates, its condition produces no signal the loop-level fault detection can see: a loosened clamp or a degraded crimp does not register as a loop voltage anomaly or open circuit on the CCR. Its consequences are instead indirect and slow to surface — a compromised screen bond degrades EMI suppression on control and monitoring cabling, which can manifest as intermittent noise or unreliable signals on the ALCMS's own monitoring links rather than as a defined fault the system can localise. Verifying the connection therefore falls to periodic continuity and bonding-resistance checks carried out during scheduled maintenance, not to anything the lighting control system reports during normal operation.
Series Circuit Loop (ALCMS / CCR-controlled) runs independently of the Screen Connector's EMI Bonding Path
Screen-to-Earth Path Options
Cable Screen (Braid, Foil, or Spiral Wrap)
Must be bonded to earth to suppress EMI and dissipate static charge
Split Ring Compresses Onto the Screen
No cutting of the screen required
Fast, Reusable Connection
Suited to field access and temporary termination
Gathered Braid Crimped Into the Barrel
Lug then bolted to the earth terminal
Permanent, Lowest-Resistance Bond
Preferred where the termination won't be revisited
Whichever Method Is Used, the Path to Earth Must Stay Short & Direct — Inductance Rises With Any Extra Length
Physical Construction
Form follows the termination method chosen. A clamp‑on screen connector is a small split‑band or jaw of tinned copper, brass, or stainless steel that closes directly around the exposed screen (braid, foil, or spiral wrap) once the outer cable jacket has been stripped back, with a bolt or screw drawing the band tight to make solid metal‑to‑metal contact across the full circumference of the screen rather than a single point. A crimp‑on lug instead gathers the screen conductors — folded back over the jacket or twisted into a pigtail — into a barrel that is crimped in the same manner as a standard cable lug, with a tongue for bolting to the earth bar. Compression glands with an integral screen termination combine both jobs in one fitting: the gland body seals and strain‑relieves the cable entry into an enclosure while an internal cone or ring clamps the screen against the gland body itself, bonding it to the (earthed) enclosure automatically as the gland is tightened. Whichever method is used, a short, direct earth tail then runs from the connector to the local earth bar or bonding point, kept as short as practicable to preserve the low‑impedance path the screen depends on.
Technical Parameters
| Parameter | Typical Value |
|---|---|
| Material | Tinned copper, brass, bronze, or stainless steel |
| Conductor Size (screen braid) | 6mm² to 50mm² (screen cross‑section) |
| Cable Diameter Compatibility | 5mm to 50mm (clamp‑on types) |
| Contact Resistance | ≤ 1 mΩ (typical for clamp‑on types) |
| Inductance | ≤ 10 nH (for short, direct connections) |
| Operating Temperature | -40°C to +105°C (copper); up to +200°C (stainless steel) |
| Protection Class | IP68 (buried) or IP65 (above‑ground with enclosure) |
| Termination Type | Clamp‑on, crimp‑on, compression gland, or solder |
| Standards | IEC TR 61000‑5‑2, IEEE 1100, FAA AC 150/5345‑7F |
Electrical Requirements
| Requirement | Typical Value |
|---|---|
| Circuit Position | Cable screen/shield bonding point to earth (not in series power loop) |
| Contact Resistance | ≤ 1 mΩ (typical, clamp-on types) |
| Inductance | ≤ 10 nH for short, direct connections (minimises EMI/transient impedance) |
| Continuity Requirement | Verified screen-to-earth bonding continuity along the run |
| Isolation from Conductors | Screen bond kept electrically separate from primary series conductors |
| Fault Protection | Loss of screen continuity increases susceptibility to induced transients |
Applicable Standards
IEC TR 61000‑5‑2
Electromagnetic compatibility — Installation and mitigation guidelines (includes earthing and bonding)
IEEE 1100
Recommended practice for powering and grounding electronic equipment (EMC)
FAA AC 150/5345‑7F
Specification for L-824 underground electrical cable, including shielded cable and screen termination requirements
BS EN 50289
Communication cables — specifications for test methods (screen effectiveness)
Installation Requirements
Jacket Stripping Without Screen Damage
FitStrip the outer jacket back to expose the screen without damaging the underlying insulated conductors or nicking the braid or foil.
Full-Circumference Bond
FitClamp, crimp, or solder the connector onto the screen to create solid metal-to-metal contact across the full circumference, not just a single point.
Short, Direct Bonding Lead
FitRun the bonding lead to the local earth bar or chassis earth point as short and direct as practicable, since a long or coiled lead adds inductance that reduces effectiveness at higher frequencies.
Bond at Every Enclosure Entry
FitTerminate the screen at each enclosure entry point along a multi-enclosure run, so no section of the shield is left unbonded or floating.
Bond Continuity Check
ElectricalVerify continuity from the screen connector through to the earth bar before the enclosure is closed, confirming the low-impedance path is intact.
Pre-Energisation Sign-off
DocumentationRecord each termination point and continuity result before enclosures are closed, since the bond is not inspectable once the run is complete.
Testing & Commissioning
Screen Continuity Test
Pre-EnergisationVerify continuity of the cable screen through the connector end to end, ruling out a broken or unterminated drain wire.
Screen-to-Earth Bonding Resistance Test
Pre-EnergisationMeasure resistance from the screen termination to the earth bar or bonding point, confirming it meets the design threshold.
Insulation Resistance (Screen-to-Conductor) Test
Pre-EnergisationMegger-test between the screen and the inner conductors to confirm no contact or degraded insulation exists at the termination.
EMC / Shield Effectiveness Check
Final AcceptanceConfirm the screen is terminated 360° around the cable jacket where required, avoiding pigtail connections that degrade shielding performance.
Documentation & As-Built Sign-off
Final AcceptanceRecord continuity and bonding resistance readings alongside the connector's as-built location in the commissioning dossier for handover.
Inspection & Maintenance
Contact Resistance Test
AnnualMeasure screen-to-earth contact resistance at each termination and compare against the ≤1mΩ specification, flagging any rise that points to corrosion or a loosened clamp.
Corrosion Inspection
AnnualCheck the braid and connector body for surface corrosion, especially in moist or chemically aggressive locations, and re-apply anti-oxidant compound where needed.
Clamp / Crimp Torque Check
AnnualRe-torque clamp-on connectors and inspect crimped joints for looseness, since improper clamping is a leading cause of high contact resistance.
Pigtail Length Check
Semi-annualConfirm the screen termination stays short (ideally under 50mm) with no looping, since a long pigtail raises inductance and degrades high-frequency EMI suppression.
Earth Bond Verification
AnnualVerify the connection routes to the main earthing system with resistance ≤10Ω, and confirm it is not tied to a non-dedicated "dirty" earth point.
Seal Inspection
AnnualCheck heat-shrink or self-amalgamating tape seals over the connection for cracking or lifting, re-sealing to keep the joint at its rated IP class.
Braid Preparation Check
AnnualWhere accessible, verify the screen braid is still cleanly gathered and free of dirt or oxidation at the termination point.
Material Compatibility Check
AnnualConfirm connector and screen materials remain suited to the operating environment and temperature range, replacing any component showing incompatible-metal corrosion.
Common Field Issues
Corrosion of Screen and Connector
The cable screen (often tinned copper) and the connector can corrode, especially in moist or chemically aggressive environments. This increases contact resistance and reduces EMI suppression effectiveness. Use corrosion‑resistant materials (tinned copper, stainless steel) and apply anti‑oxidant compound. Seal the connection with heat‑shrink or self‑amalgamating tape.
High Contact Resistance
Improper clamping or crimping can result in high contact resistance, reducing the effectiveness of the screen termination. Use the correct tooling (crimping dies, torque wrenches) and follow the manufacturer's installation instructions. Test the continuity of the screen connection after installation.
Inadequate Screen Preparation
If the screen braid is not properly gathered, twisted, or cleaned before termination, the connection may be poor. Ensure the screen is free of dirt, oil, and oxidation, and that the braid is properly gathered to fill the connector barrel or clamp.
Long Screen Pigtails
Leaving a long pigtail (unterminated screen) before the connector increases inductance and reduces high‑frequency EMI suppression. Keep the screen termination as short as possible (ideally < 50mm) and connect directly to the earth terminal without looping.
Incorrect Earth Connection
If the screen connector is not connected to a proper earth (low‑impedance path), the screen may not provide effective shielding. Ensure the earth connection is to the main earthing system with a resistance of ≤ 10 Ω. Avoid connecting the screen to a "dirty" earth (e.g., a non‑dedicated earth point).
Mechanical Damage to Screen
During installation, the screen braid can be damaged (cut or frayed), reducing its effectiveness. Handle the cable carefully, use proper stripping tools, and avoid nicking the screen braid.
Multiple Screen Connections
When multiple shielded cables are terminated in the same junction box, ensure each screen is connected to a common earth point (star configuration) to avoid creating ground loops. Use a dedicated earth bar for screen terminations.
Troubleshooting Guide
High Resistance or Ineffective Screen Termination
EMI/Noise Reappears Despite Shielded Cable
Screen Connection Fails Continuity Test
Ground Loop Noise on Multi-Cable Runs
Screen Termination Corroded or Loose at the Connector
Failure Modes & Root Causes
Corroded or Poorly Crimped Screen Termination
Long or Floating Pigtail
Screen Braid Mechanical Damage
Multi-Point Earthing / Ground Loop
Moisture Ingress at the Termination Seal
Safety & Operational Notes
De-Energise Before Terminating
Electrical SafetyDe-energise the associated circuit and verify zero energy before opening a cable end to terminate or re-terminate the screen; a shielded control or signal cable can still share a duct with, or run near, energised power circuits.
Single-Point (Star) Earthing
WorkmanshipTerminate the screen to a single dedicated earth point per the system's star-earthing design; earthing the same screen at both ends or bonding multiple screens together in a junction box creates a ground loop that degrades signal quality.
Careful Braid Handling
WorkmanshipStrip and fold back the screen braid carefully to avoid nicking or fraying strands, and keep the pigtail short and fully bonded rather than left long or floating, which defeats the shielding effect.
Seal the Termination
WorkmanshipFully seal the finished termination with heat-shrink or self-amalgamating tape rated for the environment; an incomplete seal lets moisture corrode the connection over time.
Verify Continuity Before Closing Out
CompliancePerform an end-to-end screen continuity test and confirm the screen is genuinely bonded to the connector before closing the enclosure, since a floating or damaged screen is not always visually obvious.
PPE & Grounding
Personnel SafetyUse appropriate PPE when working in junction boxes or near energised power circuits, and confirm bonding/grounding of the enclosure itself before reconnecting the shielded cable.
Restore to Compliant State
ComplianceDo not leave a screen termination corroded, loose, unsealed, or multi-point earthed; verify and document the connection before closing out the work.
Engineering & Expert Notes
A Second Earth Point Can Be Worse Than None
ComplianceTechnicians sometimes add a "belt and braces" second earth point on a screen thinking it improves safety; in a star-earthed system this creates a ground loop that degrades signal quality without necessarily improving safety, so any second bonding point must be a deliberate design decision, not an ad hoc addition.
A Floating Screen Can Still Pass a Casual Visual Check
TroubleshootingA screen braid that's been folded back but not actually bonded to the connector can look correctly terminated at a glance; only an end-to-end continuity test confirms genuine bonding, since a floating screen is not visually distinguishable from a properly terminated one.
Braid Fraying During Strip-Back Reduces Shield Effectiveness Gradually
WorkmanshipA few broken strands lost during a rushed strip-back won't cause an immediate fault, but shield effectiveness degrades incrementally as more strands are lost across repeated re-terminations at the same cable end; handle the braid carefully every time, not just when it matters most.
An Incomplete Heat-Shrink Seal on a Screen Termination Fails Slowly
DurabilityMoisture wicking into a partially sealed screen termination corrodes the braid gradually rather than causing an immediate signal fault, so a termination can appear to work for a long time before failing; verify full, even shrinkage and a visible adhesive bead at every service.
Screened Cable Routing Near Power Circuits Still Needs Separation
DesignEven a well-terminated screen can't fully compensate for a signal cable routed in close, sustained parallel with a high-current power circuit; maintain designed separation distances during any re-routing rather than relying on the screen alone to reject interference.
Document Which End of a Screen Is the Designated Earth Point
ComplianceBecause star-earthing requires exactly one bonding point per screen, clear documentation of which end is designated prevents a well-meaning technician at the other end from adding a second bond during unrelated work.
Frequently Asked Questions
Short answers about the screen connector: what it is, how it works, specifications, standards, maintenance and common faults.
Q1What is a screen connector?
A screen connector (also called a shield connector, screen termination or cable screen clamp) connects the metallic screen of a shielded AGL cable to earth, equipment chassis or a junction box earth terminal. It gives induced currents and electromagnetic interference a low-resistance, low-inductance path to earth.
Q2Why do shielded AGL cables need screen connectors?
Without a proper termination the screen can act as an antenna that radiates or picks up interference. Screen connectors protect the integrity of signal and power circuits where electromagnetic compatibility is critical, such as communication links, control circuits and sensor wiring.
Q3Where are screen connectors used?
On AGL control and monitoring cables between CCRs, ALCMS workstations and field equipment, on communication links, and on sensor cables, wherever shielded cable is used and the screen must be terminated.
Q4What types of screen connector are there?
Termination types are clamp-on, crimp-on, compression gland and solder. A clamp-on connector wraps a split ring around the screen and tightens on it without cutting the screen, while crimp-on lugs use a barrel crimped onto the screen.
Q5What are the typical specifications?
Contact resistance is typically 1 mΩ or less for clamp-on types and inductance 10 nH or less for short direct connections. Cable diameter compatibility is 5 mm to 50 mm and screen cross-section 6 mm² to 50 mm². Ratings are IP68 buried or IP65 above ground with an enclosure.
Q6Is a screen connector part of the series lighting circuit?
No. It is a bonding point from the cable screen to earth, not part of the series power loop, and the screen bond is kept electrically separate from the primary series conductors.
Q7Which standards apply to screen connectors?
The main references are IEC TR 61000-5-2 (EMC installation and mitigation), IEEE 1100, FAA AC 150/5345-7F (L-824 cable including screen termination) and BS EN 50289. Always verify the current edition and your aerodrome's approved requirements.
Q8How often should a screen connector be inspected?
Typical annual checks cover contact resistance, corrosion, clamp or crimp torque, earth bond, seals, braid preparation and material compatibility, with a semi-annual pigtail length check. Your airport's approved maintenance programme takes precedence.
Q9Why does interference persist despite a shielded cable?
Likely causes are a long or floating screen pigtail, poor or corroded screen termination, or multi-point earthing that creates ground loops. Check continuity from screen to earth, pigtail length and earthing arrangement.
Q10What are the common problems with screen connectors?
Common problems are corrosion of the screen and connector, high contact resistance, inadequate screen preparation, long screen pigtails, incorrect earth connection, mechanical damage to the screen and multiple screen connections.
Related Components
Go Beyond the Component. Understand the Complete AGL System.
You have explored the component. Now understand how it works within the complete Airfield Ground Lighting system.
Learn AGL from fundamentals to design, installation, testing, photometry, commissioning, maintenance and troubleshooting through structured technical training at Precision AGL Academy.
Build practical knowledge. Understand the circuit. Read the standards. Troubleshoot with confidence.
Your next step in AGL starts here.
Need expert guidance on screen connectors and EMC for your AGL project?
Precision AGL Academy provides advice on screen termination techniques, cable selection, and earthing for reliable electromagnetic compatibility in AGL systems.
Follow the Academy
Important Notice, Disclaimer & Limitation of Liability
Please read before relying on any content on this page.
- Purpose and intended users. This page on Screen Connector is an independent educational and informational reference for competent, suitably trained and authorised airfield ground lighting (AGL) and aerodrome electrical personnel. It is not professional engineering, legal or regulatory advice, and using it does not create any professional or client relationship.
- Safety. Work on series circuits, constant current regulators (CCRs), isolating transformers, cables, connectors and lighting equipment can be fatal. Always apply the aerodrome’s permit-to-work and isolation/LOTO procedures, prove dead, use correctly rated instruments and PPE, and follow the manufacturer’s instructions. Nothing here authorises work on live equipment or the bypassing of any safety device or interlock.
- Aviation operations. Nothing here authorises installation, modification, energisation, adjustment, return to service, a change of operating category (CAT I/II/III), a NOTAM or any aerodrome certification or approval decision. These rest with the aerodrome operator, the air navigation service provider and the competent regulator.
- Specifications, ratings and typical values. Descriptions, parameters, ratings, dimensions, photometric values, wattages, service lives, maintenance tasks and intervals, failure modes, certifications (for example CE, FCC, UL or IEC marks) and part or type designations are general, typical and indicative. They may not match any particular product, make, model or version, and they are not a datasheet, design, specification, selection, sizing, procurement or acceptance criterion. The manufacturer’s current documents, the approved design and the project specification prevail.
- Standards and regulations. References to ICAO, FAA, IEC, IEEE, ISO, BIS, DGCA and other standards are paraphrased summaries for orientation only. They may be incomplete or out of date, and standards are revised from time to time. Consult the current official editions. Following this content does not guarantee compliance with any law, standard or regulatory approval, and the regulator’s requirements always prevail.
- No warranty. Content is provided “as is” and “as available”, without warranty of any kind, express or implied, including accuracy, completeness, currency or fitness for a particular purpose. Real installations differ in design, equipment make and model, age and condition.
- Limitation of liability. To the fullest extent permitted by applicable law, Precision AGL Academy, Precision AGL Solutions and their owners, authors and contributors are not liable for any injury, death, loss, damage, downtime, penalty or regulatory consequence, whether direct or indirect, arising from the use of, reliance on, or inability to use this content. Nothing in this notice excludes or limits any liability that cannot lawfully be excluded or limited.
- Independence, brands and no endorsement. This is an independent publication. It is not affiliated with, sponsored by or endorsed by ICAO, the FAA, the IEC, DGCA, AAI, any airport, regulator, supplier or equipment manufacturer. Third-party names, product designations, standard designations and trademarks (including Megger®, Siemens, Eaton, Crouse-Hinds, ADB SAFEGATE, Fluke, ABB and Honeywell) belong to their respective owners and are used only for identification and description. Mention of a brand, product or supplier is not a recommendation, and we do not sell, supply or quote for any component described.
- Images and third-party content. Images and illustrations are shown to help identify the type of component. They may show products of various manufacturers, may not depict the exact item described, and are not a statement about any product’s quality, approval or performance. Copyright and trademarks in third-party images, logos and photographs belong to their respective owners and are not claimed as ours. If you are a rights holder and want an image removed, replaced or credited, email precisionaglsolutions@gmail.com with the page address and we will act promptly.
- Training and services. Mentions of training, courses, consultation, advice, selection, installation, calibration or other support, including the “Learn…Certify” pathway, describe learning stages and are not an offer, quotation, tender or promise of any result. Contacting us or our replying creates no engagement or duty of care; an engagement exists only under a written agreement. We are not a regulator or certification body, and completing any course or reading this content is not a certification, accreditation or authorisation to work on any aerodrome.
- Copyright, privacy and corrections. © 2026 Precision AGL Academy. All rights reserved. Text, structure, compilations and diagrams may be viewed for personal reference and internal training only; any other copying, republication or commercial use needs our written permission. If you email, telephone or message us, we use your details only to respond and handle your matter, in line with applicable Indian law including the Digital Personal Data Protection Act, 2023; please do not send confidential or security-sensitive information. To display this page your browser requests fonts, icons and images from third-party servers, which receive your IP address and browser details under their own policies. Content is reviewed periodically with no obligation to update. To report an error, safety concern or rights issue, write to precisionaglsolutions@gmail.com.