The CCR fault indication

When a CCR cannot do its job it tells you in a few ways. Read the indication first, then use it to decide where to look.

CCR FAULT INDICATION FROM INDICATION TO FIRST CHECK SYMPTOM What is seen INDICATION Lamp, code, relay FIRST CHECK Supply, output, circuit CAUSE Located and fixed NO OUTPUT Check supply and trips OPEN CIRCUIT Break in the loop EARTH FAULT Insulation breakdown
symptom
indication
first check
cause located
circuit fault
The Fact Fault indication

1Read before you touch

Note the indicator lamps, the display code and the state of the output before resetting or changing anything. This is the only record of what the CCR saw at the moment of the fault.

2Match the indication to the zone

No output points to the supply, breaker or a trip. An open-circuit indication points to a break in the series loop. A low-insulation or earth-fault indication points to the circuit cable, joint, connector or transformer, not usually the CCR itself.

3Then isolate safely

Before testing the circuit, isolate and lock out. Work from the CCR outward, section by section (half-split the loop at accessible points), using the fault flowchart and the insulation test, rather than guessing. Discharge the cable after any insulation test before touching the conductors.

ElementDetail
No outputCheck supply, input breaker, trip indication, local or remote state
Open-circuit indicationLook for a break in the loop: connector, cut cable, open primary winding of an isolating transformer. A failed lamp alone does not open the loop when an isolating transformer is used
Overload, overcurrent or over-temperatureCheck circuit load against the CCR rating, cooling and ventilation
Low insulation or earth faultTest the circuit insulation and locate the leakage
Supply alarmCheck incoming supply and surge protection
AlwaysRecord the indication before resetting
ReferenceIEC 61822 · FAA AC 150/5345-10 · FAA AC 150/5340-26
Teaching diagram: Indication types and codes are model specific. Use the manufacturer manual to decode them. Isolate, lock out and prove dead before opening the cabinet. Never open or touch an energised series circuit. Once it is isolated and proved dead, earth it as the site procedure requires before working on it: a series circuit can carry lethal voltage even at low current.
Entry 25 · CCR alarm system Entry 27 · CCR failure modes

Frequently Asked Questions

Q1What should I check first when a CCR shows a fault?

Record the indication, then check whether the supply is present and whether the CCR has tripped. Do this before resetting anything.

Q2Is every CCR fault a CCR fault?

No. Open-circuit and earth-fault indications usually mean a fault in the series circuit that the CCR has detected, not a fault in the CCR itself.

Q3Can I just reset and see?

Reset only after finding the cause. Repeated resets on a hard fault can damage equipment and mask the real problem.

Q4Where does the CCR send fault information?

To its display and indicators, and through relay outputs or a communications link to the ALCMS where fitted.

Precision AGL Academy

See It. Understand It. Then Learn How to Engineer It.

Recognising an AGL system visually is the first step. The next step is knowing how to design, install, test, commission and maintain them correctly.

Build Practical AGL Engineering Skills

Go deeper with structured training from Precision AGL Academy, covering:

AGL Fundamentals Design & Electrical Engineering Approach Lighting Photometry Installation & Commissioning Maintenance & Troubleshooting

Learn how each light, sign and circuit works as part of a complete airport lighting system, not just as an isolated diagram.

See. Understand. Apply. Engineer.