How do you troubleshoot an intermittent fault?

A fault that comes and goes cannot be measured while it is absent, so the work is to record when it appears, repeat the tests and trace it to the joint, connector or cable that only misbehaves in some conditions.

INTERMITTENT-FAULT TROUBLESHOOTING · RECORD, REPEAT, TRACELIGHTS NORMALFAULT APPEARSTHEN CLEARSAGAINAGAINTIME →LOG EACH EVENT: TIME · WEATHER · BRIGHTNESS STEP · CCR CODE1SYMPTOMFLICKERING LIGHTCause: loose or wetconnection or jointCheck: connectors, joints2SYMPTOMALARM COMES, CLEARSCause: fault that onlyshows in some conditionsCheck: event log, alarm history3SYMPTOMREADINGS WANDERCause: intermittent jointor poor test connectionCheck: test lead, repeat4SYMPTOMWORSE WET OR HOTCause: moisture, corrosion,ageing insulationCheck: IR trend vs baseline5SYMPTOMNORMAL ON ARRIVALCause: fault not presentto be measuredCheck: records, no blind resetTELL ATC · TEST DE-ENERGISED · ISOLATE, LOCK OFF, PROVE DEAD · NEVER SEPARATE A LIVE PRIMARY CONNECTOR
normal operation
records / event log
fault event / safety
repeat tests / trend
The Fact Intermittent-fault tracing

An intermittent fault comes and goes: a flickering light, an alarm that clears, or a reading that wanders. It is hard to find because it often comes from a loose or wet connector, a damaged cable or a failing joint that only misbehaves in some conditions. Corrosion raises contact resistance, which can cause heating, intermittent faults or arcing in a series circuit. Because the circuit may be normal when an engineer arrives, the record is the main tool: the CCR code and readings are noted before any reset, and the event log and alarm history show when and how often the fault appears.

Each event is logged with its time, weather and brightness step so a pattern can show. Tests are made de-energised, with ATC told and the circuit isolated, locked out and proved dead, and a primary connector is never separated on a live loop. A continuity reading that will not settle points to an intermittent joint or a poor test connection, so the test lead is checked and the test repeated. Insulation resistance is taken under recorded conditions and trended against the baseline, because a value that keeps falling points to moisture, damage or ageing. Suspected sections are inspected, repaired and retested, and the result is recorded.

Flickering lightLoose or wet connection
Alarm comes and clearsCondition-dependent fault
Wandering readingJoint or test connection
Usual sitesConnector, joint, cable
Key toolRecords, event log, trend
Before any resetNote code and readings
Test conditionDe-energised, proved dead
ReferenceICAO Doc 9157 Part 5; FAA AC 150/5340-26; manufacturer manuals and airport safe-working rules
Awareness schematic only, not a fault-finding procedure. Series circuits carry high voltage and high current and can be lethal. Test methods, limits and isolation points come from the manufacturer, the standards and the airport’s safety procedures.
Entry 26 · Earth-fault troubleshooting Entry 28 · Multiple-fixture-failure troubleshooting

Frequently Asked Questions

Q1Why are intermittent faults hard to find?

They come and go. They often come from a loose or wet connector, a damaged cable or a failing joint that only misbehaves in some conditions, so the circuit can test normal when the engineer arrives.

Q2What are the usual causes of an intermittent fault?

Loose or wet connections, corroded contacts, failing joints or terminations and damaged cable. Corrosion raises contact resistance, which can cause heating, intermittent faults or arcing in a series circuit.

Q3Why record the CCR code and conditions before resetting?

A reset clears the evidence. The code, readings, time, weather and brightness step show when and under what conditions the fault appears, and the CCR event log and alarm history keep the pattern so repeat events can be compared.

Q4What does a wandering test reading mean?

If a continuity reading will not settle, look for an intermittent joint or a poor test connection. The test connection is checked and the test repeated before the circuit is blamed.

Q5How does insulation resistance help with a fault that comes and goes?

Readings change with temperature and damp, so they are taken under recorded conditions and trended against the baseline. A low value, or one that keeps falling from test to test, points to moisture, damage or ageing, often before a hard fault appears.

Q6Can an intermittent fault be tested on a live circuit?

No. Tests are made de-energised, with the circuit isolated, locked out and proved dead. ATC is told first, and a primary connector is never separated on an energised loop. Once the suspected section is repaired it is retested and the result recorded.

Precision AGL Academy

See It. Understand It. Then Learn How to Engineer It.

Recognising an AGL system visually is the first step. The next step is knowing how to design, install, test, commission and maintain them correctly.

Build Practical AGL Engineering Skills

Go deeper with structured training from Precision AGL Academy, covering:

AGL Fundamentals Design & Electrical Engineering Approach Lighting Photometry Installation & Commissioning Maintenance & Troubleshooting

Learn how each light, sign and circuit works as part of a complete airport lighting system, not just as an isolated diagram.

See. Understand. Apply. Engineer.