What is a ring and loop cable arrangement?

A cable run that returns to its source, so one faulted section can be cut out and the substations beyond it fed the other way round.

ONE SOURCE · THREE SUBSTATIONS · ONE NORMALLY OPEN POINT 1 · RING HEALTHY, OPEN AT ONE POINT EVERY SUBSTATION FED SOURCE S1 S2 S3 2 · FAULT, SECTION ISOLATED OPEN POINT CLOSES · ALL STILL FED FAULT SOURCE S1 S2 S3 3 · FOR COMPARISON: RADIAL, SAME FAULT S2 AND S3 DARK FAULT SOURCE S1 S2 S3 NO RETURN PATH WHAT TO CHECK 1 TWO WAYS ROUND every point fed from either direction 2 RATED BOTH WAYS cable and switches take either way 3 SWITCH EACH END isolate a section at both ends 4 SEPARATE ROUTES two legs in one trench share one risk SCHEMATIC · SQUARES ARE SWITCHES · NOT A DISTRIBUTION DESIGN
feed from one direction
feed from the other direction
faulted section
not supplied
The Fact Redundant architecture

A radial cable feed is one path from the source to the loads, so a cable fault darkens everything beyond it until the cable is repaired. A ring cable leaves the source, passes through each substation or CCR room, and returns to the source, so every point can be fed from either direction. Switches at both ends of each section let a faulted section be isolated while the rest is supplied the other way.

Rings are usually run open, with one normally open point so power flows one way round. When a section faults, its switches open and the open point closes, and the loads beyond the fault come back. For that to work every cable and switch must be rated for the reversed load, not just the normal one, and the two directions must not share one trench, or a single dig takes out both.

A series lighting circuit is also a loop, out through the lights and back to the CCR, but it is one path: a break anywhere opens it, as the open circuit entry shows. Ring redundancy belongs to the power cables feeding the substations, alongside dual feeders and network redundancy for control.

Ring

Two paths round. A fault is cut out and the rest re-fed.

Radial

One path. Everything beyond the fault is dark until repaired.

SituationRing stateEffect
Ring healthyRun open at one pointEvery substation fed, power flowing one way
Fault on one sectionSection isolated, open point closesLoads re-fed the other way after a short interruption
Cable sized for normal load onlyReversed load too highOverload or trip after reconfiguration
Isolating switch fails to openFault not isolatedWider outage than the fault needs
Both directions in one trenchOne dig cuts both pathsRing gives no protection
Second fault before the first is repairedRing already openPart of the ring dark
Radial feed, same faultSingle pathEverything beyond the fault is dark
Principle A cable run that returns to its source, so each point has two ways to be fed
Arrangement Source and substations in a ring, one normally open point
Equipment Ring cable, switchgear or breakers at both ends of each section, protection
Fault response Isolate the section, close the open point; short interruption unless automated
Limit Survives one fault; a second before repair leaves part of the ring dark
Reference ICAO Doc 9157 Pt 5 · Annex 14 Ch. 8 · FAA AC 150/5340-30
Schematic, not a distribution design. Ring voltage, switchgear, protection and the position of the open point depend on the network and the utility. Confirm against the design basis and the single-line diagram.
Entry 42 · Standby CCR and changeover arrangement Entry 44 · Single point of failure analysis

Frequently Asked Questions

Q1What is a ring cable arrangement?

A ring is a distribution cable run that leaves a source, passes through each substation or CCR room, and returns to the same source or to a second one. Every point can then be fed from either direction. Switches at both ends of each cable section let a faulted section be isolated while the rest of the ring is supplied the other way round.

Q2How is a ring different from a radial feed?

A radial feed is a single path from the source out to the loads, so a cable fault leaves everything beyond it dark until the cable is repaired. A ring gives a second path, so after a fault the faulted section is isolated and the loads beyond it are re-fed the other way. There is usually a short interruption while the switching is done, unless the ring is automated.

Q3Is a series lighting circuit already a loop?

Yes. A series circuit runs from the CCR out through the lights and back to the CCR, so it is a loop in the electrical sense. But it is one path: a break anywhere opens the whole circuit, as the open circuit entry explains. A ring arrangement is about the power cables that feed substations and CCR rooms, where a second path is possible, not about the series loop itself.

Q4Why is a ring usually run open?

A ring normally has one open point, so power flows one way round and protection stays simple. When a section faults, that section is isolated and the open point is closed to feed the loads from the other side. A closed ring keeps both paths live and can restore faster, but needs protection that can tell which section has faulted, which is more complex.

Q5What defeats a ring?

Both directions sharing one trench or duct, so a single dig removes both. Cables or switches sized only for their normal load, which overload when the load reverses. A switch that fails to open, so the fault is not isolated. And a second fault before the first is repaired, since a ring is built to survive one fault, not two.

Q6Is a ring arrangement required?

It is design practice, not a rule for every airfield. Whether a ring is needed, and how fast the supply must be restored, depends on the standard, the size of the airfield and the operation. See ICAO Annex 14 Vol I Chapter 8, Doc 9157 Part 5 and FAA AC 150/5340-30, and confirm against your design basis.

Precision AGL Academy

See It. Understand It. Then Learn How to Engineer It.

Recognising how lights are laid out is the first step. The next step is knowing how to design, install, test, commission and maintain them correctly.

Build Practical AGL Engineering Skills

Go deeper with structured training from Precision AGL Academy, covering:

AGL Fundamentals Design & Electrical Engineering Approach Lighting Photometry Installation & Commissioning Maintenance & Troubleshooting

Learn how each light, sign and circuit works as part of a complete airport lighting system, not just as an isolated diagram.

See. Understand. Apply. Engineer.