What is a standby CCR and changeover arrangement?

A spare regulator and a changeover switch, so a failed CCR costs a short interruption instead of a dark circuit until the repair.

DUTY CCR · STANDBY CCR · ONE CHANGEOVER SWITCH 1 · DUTY CCR HEALTHY SWITCH ON A · STANDBY IDLE CCR A STANDBY CHANGEOVER SWITCH SERIES CIRCUIT 2 · DUTY CCR FAILED CIRCUIT DARK UNTIL CHANGEOVER CCR A STANDBY CHANGEOVER SWITCH SERIES CIRCUIT 3 · ON STANDBY A ISOLATED · STANDBY CARRIES CIRCUIT CCR A STANDBY CHANGEOVER SWITCH SERIES CIRCUIT WHAT TO CHECK 1 SAME RATING same power, same brightness steps 2 BREAK BEFORE MAKE never two CCRs on one circuit 3 DE-ENERGISE FIRST switch only with the circuit off 4 TEST THE STANDBY run it on a circuit, not just on paper SCHEMATIC · ONE CIRCUIT SHOWN · NOT A SWITCHING PROCEDURE
duty CCR path
standby CCR path
failed CCR
supply lost
The Fact Redundant architecture

A series circuit has one regulator. If that CCR fails, every light on the circuit goes out until it is repaired or replaced. A standby CCR removes the wait: a spare of the same rating sits beside the duty CCR, and a changeover switch connects the circuit to one of the two, never both.

When the duty CCR fails, it is isolated, the switch is moved to the standby, and the circuit lights again. The circuit stays dark for the time that takes, because the output is changed only with the circuit de-energised. The standby must be the same rating and the same steps as the duty CCR, or the lights come back at the wrong brightness. A standby can be dedicated to one circuit or shared across several through selector switches, but a shared standby covers one failure at a time.

Each layer protects something different: dual feeders protect the supply into the CCR, the standby CCR protects the regulator itself, and interleaved circuits protect the pattern of lights if a whole circuit is lost.

With a standby CCR

Duty CCR fails, circuit moves to the spare after a short interruption.

No standby

Duty CCR fails, circuit stays dark until the repair or a replacement arrives.

SituationSwitch and CCR stateEffect on the circuit
Duty CCR healthySwitch on duty CCR, standby idleNormal operation
Duty CCR failsSwitch still on the failed CCRCircuit dark until the changeover
Changeover to standbyFailed CCR isolated, switch on standbyCircuit lit again, no spare left for it
Standby of a lower ratingStandby cannot reach every stepWrong brightness, or standby trips
Standby never testedFault found only when neededNo cover when the duty CCR fails
Second CCR fails on a shared standbyStandby already in useSecond circuit stays dark
Principle A spare CCR that a circuit can be moved onto if the duty CCR fails
Arrangement Duty and standby CCR outputs to one changeover switch, one circuit
Equipment Duty CCR, standby CCR, changeover or selector switch, interlocks, status monitoring
Changeover Break before make, circuit de-energised; manual or remote
Cover One standby per circuit, or one shared standby (N+1) for several
Reference ICAO Doc 9157 Pt 5 · Annex 14 Ch. 8 · FAA AC 150/5340-30
Schematic, not a switching procedure. The switching sequence, interlocks and lockout rules depend on the equipment and the site. Follow the manufacturer's instructions and the site procedure, and confirm the arrangement against the design basis.
Entry 41 · Dual feeders and incoming supply redundancy Entry 43 · Ring and loop cable arrangement

Frequently Asked Questions

Q1What is a standby CCR?

A standby CCR is a spare constant current regulator of the same rating as the duty one, kept ready so a series circuit can be moved onto it if the duty CCR fails. A changeover switch connects the circuit to one regulator at a time, so the duty CCR can be isolated for repair while the lights run from the standby.

Q2What does the changeover arrangement do?

It connects the output of the series circuit to either the duty CCR or the standby CCR, never both. The unselected regulator is disconnected from the circuit and its output is isolated, which is what makes it safe to work on. Circuit selector switches such as the L-847 type are commonly used for this.

Q3Is the changeover manual or automatic?

Both exist. A manual changeover needs someone on site to isolate the failed CCR and operate the switch, so the circuit is dark for the time that takes. An automatic or remotely operated arrangement shortens that, but still moves the circuit only after it is de-energised, so there is always a short interruption. Follow the site switching procedure and lockout rules either way.

Q4Why must the CCR be off when the changeover is made?

A series circuit is a single loop carrying constant current. Opening the loop while a CCR is driving it can produce a dangerous voltage, and connecting two regulators to one loop makes them fight over the current. The switching sequence is therefore break before make, with the circuit de-energised, and interlocks stop an unsafe selection.

Q5One standby per circuit or one shared standby?

A dedicated standby for each circuit gives full cover but doubles the regulators. A shared standby, often called N+1, serves several circuits through selector switches and costs less, but it can cover only one failed CCR at a time. If a second CCR fails while the standby is already in use, that circuit stays dark.

Q6How do I know the standby will work when needed?

Run it. A standby that has sat idle for years may not start, may be set to the wrong step or may have a fault nobody has seen. Test it periodically by putting it onto a circuit, check that it reaches every brightness step at the same current as the duty CCR, and confirm monitoring shows its status. Whether a standby is required depends on the standard and the operation; confirm against your design basis.

Precision AGL Academy

See It. Understand It. Then Learn How to Engineer It.

Recognising how lights are laid out is the first step. The next step is knowing how to design, install, test, commission and maintain them correctly.