THE AGL ENGINEERING CENTRE by Precision AGL Academy · Design & Electrical Engineering

Airfield Ground Lighting Design & Electrical Engineering

Designing the electrical system behind safe and reliable Airfield Ground Lighting. AGL design is more than selecting fixtures — it's a coordinated engineering process spanning runway and taxiway layout, series circuits, Constant Current Regulators, isolating transformers, cable, connectors, earthing, control, monitoring, loading and reliability.

Overview

What Is AGL Design?

AGL design is the engineering process of converting an airport's operational and lighting requirements into a complete, coordinated airfield lighting system.

A typical design considers the aerodrome layout, runway and taxiway configuration, approach requirements, the lighting systems required, fixture locations, circuit configuration, CCR selection, series-circuit cable, isolating transformers, connectors, control and monitoring, earthing and bonding, electrical loading, installation requirements, and testing and commissioning.

Not a Drawing Exercise

AGL design should not be treated as producing a set of drawings — it is a complete engineering process from layout through commissioning.

Electrically Coordinated

The objective is a system that is technically appropriate, electrically coordinated, maintainable and compliant with the applicable requirements and standards.

Serves the Pilot

Every design decision ultimately supports the same purpose: giving pilots reliable, correctly performing visual guidance.

The Complete Sequence

The AGL Design Process

A complete AGL design can be understood as a connected sequence, from the airport layout through to photometric verification of the installed system.

AIRPORT LAYOUT
OPERATIONAL REQUIREMENTS
LIGHTING SYSTEM SELECTION
FIXTURE LAYOUT
CIRCUIT PLANNING
ELECTRICAL LOAD CALCULATION
CCR SELECTION
TRANSFORMER & CONNECTOR SELECTION
CABLE DESIGN
EARTHING & PROTECTION
CONTROL & MONITORING
DRAWINGS & BOQ
INSTALLATION
TESTING & COMMISSIONING
PHOTOMETRIC VERIFICATION

This connection between design, installation, testing and photometry is important. AGL design should not be treated as a drawing exercise — it is a complete engineering process that only finishes once the installed system has been verified against the design.

Start from how the aerodrome will operate and which documents govern, then carry every requirement into layout, circuits, equipment and review.

HOW REQUIREMENTS TRAVEL THROUGH AGL DESIGN 1 OPERATIONAL BASIS Runway use, category, code and aerodrome data OUTPUT: LIGHTING NEEDS 2 GOVERNING DOCUMENTS Regulation and contract call-up, editions fixed OUTPUT: REQUIREMENT LIST 3 LIGHTING LAYOUT Light types, patterns and positions OUTPUT: LAYOUT DRAWINGS 4 CIRCUITS & POWER Series circuits, loads, CCR and transformer sizing, cables, earthing OUTPUT: CIRCUIT DESIGN 5 EQUIPMENT & SPEC Fixtures, CCRs and transformers named to their standards OUTPUT: SPECIFICATION, MATRIX STARTED 6 DESIGN REVIEW Check against the requirement list; approve deviations OUTPUT: DESIGN ISSUED FEEDBACK LOOP A change in operations, a clarification or a rejected deviation goes back to step 2, and the requirement list is updated. REQUIREMENTS FIRST · THEN LAYOUT, CIRCUITS AND EQUIPMENT · THEN REVIEW SIMPLIFIED SEQUENCE · REAL PROJECTS OVERLAP STAGES AND ITERATE
Figure 1. Start from how the aerodrome will operate and which documents govern, then carry every requirement into layout, circuits, equipment and review.
AGL Visual Encyclopedia: How do requirements flow through AGL design Design
Core Concept

Understanding the AGL Series Circuit

One of the fundamental concepts in AGL electrical engineering is the series circuit. The system is designed so that the required current is maintained through the circuit while individual fixtures remain electrically isolated from the high-voltage primary circuit.

CCR
Series Cable
Isolation Transformer
AGL Fixture
Isolation Transformer
AGL Fixture
Return to Circuit
Series Circuit Schematic — With Earthing

A constant current loop out from the CCR, through each isolating transformer and fixture, and back — enclosure and structure bonded to earth throughout

CCR Constant current IT Fixture IT Fixture ... N fixtures on the loop ... EQUIPMENT EARTH / BONDING Fixed current — same on every fixture
Interactive

CCR & Circuit Load Estimator

CCR selection should be based on the actual system design rather than simply the number of lights. Adjust the sliders to see how fixture count, unit load and estimated losses combine into a total circuit requirement.

60 fixtures
45 VA
8 % (transformer + cable)
Fixture Load
2.70 kVA
Estimated Losses
0.22 kVA
Total Circuit Requirement
2.92 kVA

This is an illustrative estimator, not a design calculation. A real AGL load calculation must use the actual manufacturer transformer and CCR data, cable characteristics, circuit length and applicable spare-capacity margin for the specific project.

Component Selection

CCR, Transformer & Cable Engineering

These three components sit at the electrical heart of the series circuit and must be selected together, not independently.

CCR Design

Selection requires consideration of required circuit current, number of fixtures, transformer ratings, circuit load, CCR capacity, intensity steps, cable characteristics, circuit length, control and monitoring requirements.

Isolating Transformers

Selection may involve fixture wattage, primary current, secondary requirements, transformer rating, connector configuration, installation environment, applicable specification and system compatibility.

Series-Circuit Cable

Considerations include cable voltage rating, conductor size, circuit length, installation method, insulation characteristics, environmental conditions, cable joints, connector compatibility and insulation resistance.

Considered as an Integrated System

FixtureTransformerConnectorCableCCR

A change in one component can affect the overall system — component compatibility should be checked during the design stage rather than discovered during installation.

Four decisions, taken in order, that narrow the choice to the right constant current regulator for a series circuit.

SELECTION FLOWCHART · FOUR DECISIONS IN ORDER 1LOAD How big is the circuit? Lamps, transformers, cable → Total kW at top step Room to grow → Next standard size up 2OUTPUT What current and steps? 6.6 A series circuit → Rated output 6.6 A 3-step or 5-step → Steps match the design 3SUPPLY What feeds it? Single- or three-phase → Input matches supply Voltage and frequency → As on rating plate 4CONTROL How is it run and housed? Tower or ALCMS control → Remote interface fitted Indoor vault → Cooling suits the vault CONFIRM BEFORE ORDERING kW rating · output current and steps · input supply · control interface · cooling · standard compliance FLOWCHART · THE MANUFACTURER DATA SHEET AND STANDARD DECIDE THE FINAL CHOICE
Figure 2. Four decisions, taken in order, that narrow the choice to the right constant current regulator for a series circuit.
AGL Visual Encyclopedia: A CCR selected Transformer selection Cable selection
Electrical Checks

Voltage Drop & Circuit Performance

Electrical calculations should consider the complete circuit rather than only individual components. Depending on circuit arrangement and design methodology, checks may include:

Cable Losses

Conductor resistance and circuit length effects.

Transformer Characteristics

Losses and performance under load.

Circuit Loading

Total connected load versus rated capacity.

CCR Operating Conditions

Output current, voltage headroom and step behaviour.

The objective is to ensure that the complete system operates within the required electrical and operational parameters — not simply that each component individually meets its own rating.

Why Loop Voltage Rises With Every Transformer

In a constant-current loop, current stays fixed — so the CCR must raise its output voltage to overcome the accumulated impedance of cable and transformers

V Distance along loop IT 1 IT 2 IT 3 IT 4 IT 5 CCR output voltage Each transformer adds impedance
This is why CCR sizing considers rated output voltage, not just current — enough headroom must exist to drive the fully-loaded loop, including cable and every transformer on it.
Capacity Planning

AGL Circuit Loading

A series circuit may contain a significant number of lighting fixtures. The design needs to establish clear answers to a small set of recurring questions — particularly important when adding or replacing fixtures during airport modifications.

Questions the Design Must Answer

  • How many fixtures?
  • What is the load of each fixture?
  • What transformer is required?
  • What is the total circuit requirement?
  • What CCR capacity is required?
  • What happens if the circuit configuration changes?

A Change Cascades

A seemingly simple change — such as adding fixtures — can ripple through the entire circuit design:

  • Circuit load
  • Transformer requirement
  • CCR capacity
  • Cable performance
  • Control configuration

How full the regulator is. The same circuit can leave a CCR comfortably loaded, nearly full or barely used, and each state has its own problems.

CIRCUIT LOADING HOW FULL IS THE REGULATOR, AND WHAT CHANGES IT ONE 7.5 KW CCR · THREE STATES OF THE SAME CIRCUIT loading = circuit load ÷ CCR rating, at the top step LIGHT DESIGN LIMIT TODAY 60 fixtures, 45 W 3,671 W · 49% ADD 20 FIXTURES +1,000 W input 4,671 W · 62% LED RETROFIT 60 × 15 W, same cable 1,671 W · 22% ZONE EDGES ARE SCHEMATIC · USE THE CCR DATASHEET WHAT MOVES THE LOADING 1 ADDING FIXTURES more load, loading rises 2 EXTENDING CABLE more I²R, loading rises 3 LED RETROFIT less load, may become too light 4 FAILED FIXTURES load falls as lights go dark 5 INTENSITY STEP lower step, lower current and load 6 SPLITTING CIRCUITS shares load between regulators THE METHOD 1 LOAD AT TOP STEP 2 DIVIDE BY CCR RATING 3 COMPARE TO DESIGN RANGE 4 CHECK LIGHT LOADING 5 RE-CHECK AFTER CHANGES 6 ADJUST THE CIRCUIT SCHEMATIC · ILLUSTRATIVE VALUES · USE THE CCR DATASHEET FOR MINIMUM AND MAXIMUM LOADING
Figure 3. How full the regulator is. The same circuit can leave a CCR comfortably loaded, nearly full or barely used, and each state has its own problems.
AGL Visual Encyclopedia: Circuit loading Circuit load
Beyond the Series Circuit

Control, Earthing & Protection

A complete electrical design also has to coordinate the control architecture, the earthing and bonding arrangement, and the protection philosophy with the series circuit and airport electrical system.

Control & Monitoring

CCR control, intensity selection, local and remote control, airport lighting control systems, fault monitoring, circuit status, CCR alarms, emergency operation and interface with airport systems.

Earthing & Bonding

Equipment earthing, metallic structure bonding, electrical equipment bonding, transformer and CCR installation, cable-related considerations and lightning protection interfaces where applicable.

Protection

Overcurrent protection, surge protection, equipment protection, lightning-related protection, insulation monitoring, earth-fault monitoring, emergency isolation and equipment interlocking.

The exact arrangement must be designed according to the applicable electrical standards, airport requirements and project specifications — protection philosophy should always be coordinated with the CCR, series circuit and airport electrical system as a whole.

The monitors and trips that guard a constant current regulator and its series circuit. Pick a fault, move the slider and see which device sees it, whether the CCR warns or shuts down, and what to check before any reset.

TRIP SIGNAL AC SUPPLY INPUT BREAKERoverload / shortCONTACTORCLOSEDTHYRISTOR STAGEpower controlTRANSFORMERisolationOUTPUT SENSINGcurrent (CT)SERIES CIRCUITfloating loop SURGE PROTECTIONdiverts surges to earthSUPPLY MONITORover / under-voltageTEMPERATURE SENSORwarn, then tripCONTROL BOARDopens contactor on tripINSULATION / EARTH MONITORwarning only
Figure 4. The monitors and trips that guard a constant current regulator and its series circuit. Pick a fault, move the slider and see which device sees it, whether the CCR warns or shuts down, and what to check before any reset.
AGL Visual Encyclopedia: The CCR protection Control system architecture
Layout & Zoning

Lighting Layout, Circuit Zoning & Segmentation

Electrical engineering cannot be separated from the physical AGL layout. Large systems often require multiple circuits or functional zones — good zoning makes troubleshooting and maintenance significantly easier.

Physical Layout Considers

  • Runway lights
  • Taxiway lights
  • Centreline lights
  • Approach lights
  • PAPI
  • Airfield signs
  • Stop bars
  • Runway guard lights

Circuit Zoning Considers

  • Runway sections
  • Taxiway sections
  • Approach systems
  • Operational requirements
  • Maintenance requirements
  • CCR allocation
  • Redundancy
  • Future expansion

The airfield is divided by area into approach, runway, taxiway and apron zones, so each can be switched, dimmed or closed on its own.

Z1APPROACHACTIVEZ2RUNWAYACTIVEZ3TAXIWAY WESTROUTE LITZ4TAXIWAY EASTCLOSED · LIGHTS OFFZ5APRONON · FLOODLITACTIVE RUNWAY DIRECTIONPLAN VIEW · ILLUSTRATIVE, NOT TO SCALE · OPPOSITE-DIRECTION APPROACH LIGHTS NOT SHOWN
Figure 5. The airfield is divided by area into approach, runway, taxiway and apron zones, so each can be switched, dimmed or closed on its own.
AGL Visual Encyclopedia: Airfield lighting zoning Circuit zoning
Documentation

AGL Drawings & Engineering Documentation

A complete AGL design package can include several types of engineering drawings and schedules, each serving a distinct purpose.

AGL Layout Drawing

Shows the physical location of AGL equipment.

Series Circuit Diagram

Shows the electrical connection of the lighting circuit.

CCR Schematic

Shows the CCR and associated electrical/control interfaces.

Transformer Schedule

Lists transformer locations, ratings and associated fixtures.

Cable Schedule

Provides cable identification, route and circuit information.

Sign Schedule

Provides sign identification, type and electrical requirements.

Equipment Layout

Shows equipment locations and interfaces.

Earthing Layout

Shows relevant earthing and bonding arrangements.

Single-Line Diagram

Provides an overall representation of the electrical system.

Simplified Single-Line Diagram — Typical Structure

One-line representation from incoming supply to the series circuit — actual drawings show all circuits, ratings and protective devices

INCOMING SUPPLY Main breaker AGL CONTROL & DISTRIBUTION PANEL CCR — CIRCUIT A e.g. Runway edge CCR — CIRCUIT B e.g. Taxiway edge Each CCR feeds one series circuit loop — shown as a separate branch on the SLD
From Design to Procurement

AGL BOQ, Equipment Schedule & Design Calculations

Design information must ultimately translate into procurement and construction information, and every calculation should be traceable to the actual project configuration.

A Typical AGL BOQ Includes

AGL fixturesCCRsIsolation transformersPrimary connectorsSecondary connectorsSeries-circuit cablesAirfield signsPAPI systemsControl equipmentMonitoring equipmentEarthing materialsInstallation accessories

Typical Design Calculations

Circuit loadingTransformer loadingCCR sizingCable selectionVoltage dropPower requirementsEquipment capacityCircuit lengthSpare capacity

Adding up every watt a series circuit draws, from the fixtures, the transformers and the cable, so the regulator that feeds it is the right size.

LOAD CALCULATION ADD IT UP AT THE HIGHEST STEP, THEN SIZE THE CCR EXAMPLE · 60 FIXTURES · 6.6 A · 5 KM LOOP OF 6 MM² CABLE FIXTURE POWER 60 × 45 W 2,700 W TRANSFORMER LOSSES at 90% efficiency 300 W CABLE LOSS I²R 6.6² × 15.4 Ω 671 W TOTAL LOAD V = P / I ≈ 556 V output 3,671 W PICK THE CCR SIZE typical sizes: 4 · 7.5 · 10 · 15 kW ... 4 KW 92% LOADED TOO TIGHT 7.5 KW 49% LOADED NEXT SIZE UP 10 KW 37% LOADED SPARE ROOM MARGIN FOR GROWTH, AGEING, ERROR THE METHOD 1 COUNT FIXTURES 2 ADD TRANSFORMER LOSSES 3 ADD CABLE I²R 4 TOTAL AT TOP STEP 5 ADD MARGIN 6 NEXT SIZE UP SCHEMATIC · ILLUSTRATIVE VALUES · USE ACTUAL FIXTURE, TRANSFORMER, CABLE AND CCR DATA
Figure 6. Adding up every watt a series circuit draws, from the fixtures, the transformers and the cable, so the regulator that feeds it is the right size.
AGL Visual Encyclopedia: The load on a circuit calculated
Keyword Reference

Airfield Lighting Design Basics & Layout Design

The starting principles of airfield lighting design and how the layout is set out.

Airfield lighting design

Airfield lighting design is the process of deciding what lighting a runway, taxiway or apron needs and how it will be powered, controlled and maintained. It covers the lighting layout, series circuits, CCR sizing, transformers, cables, control and documentation, all checked against the standard the aerodrome follows. See The AGL Design Process section above.

Airfield lighting design basics

The basics are few. Lighting is fed from constant-current series circuits, each light has its own isolating transformer, a CCR sets the circuit brightness, and the layout, intensity and colour of each lighting system follow ICAO Annex 14 or the national equivalent. Everything else in the design builds on these points. See Understanding the AGL Series Circuit above.

Airfield lighting layout design

Airfield lighting layout design places each light in the correct position, spacing and orientation relative to the runway, taxiway or approach geometry. It also splits the lights into circuits so the failure of one circuit does not leave the airfield without guidance. Spacings and patterns come from the standard, so none are given here. See Lighting Layout, Circuit Zoning & Segmentation above.

Edge, threshold, touchdown zone, centreline and end lights each have a fixed place, spacing and colour along the runway.

LANDING DIRECTIONTHRESHOLD LIGHTS+ WING BARSRUNWAY END LIGHTSEDGE LIGHTS · 60 m MAX SPACINGRUNWAY CENTRELINE LIGHTSTOUCHDOWN ZONE LIGHTSTOUCHDOWN ZONE · FIRST 900 mCENTRELINE LIGHT COLOUR · RED/WHITE 900–300 m, RED LAST 300 mWHITERED / WHITEREDEDGE LIGHT COLOUR (SEEN FROM THE APPROACH)WHITEYELLOW · LAST 600 mPLAN VIEW · ILLUSTRATIVE, NOT TO SCALE · 3000 m RUNWAY SHOWN
Figure 7. Edge, threshold, touchdown zone, centreline and end lights each have a fixed place, spacing and colour along the runway.
AGL Visual Encyclopedia: How are runway lights laid out Taxiway lighting layout Approach light layout
Medium-intensity approach lighting system with runway alignment indicator lights, shown on an FAA page
Photo 1. A medium-intensity approach lighting system (MALSR) as published by the FAA: white light bars and flashers on the extended centreline, with a green threshold line.Credit: Federal Aviation Administration. US Government work, public domain. Source page
PAPI light boxes beside a runway at Washington Dulles, showing a red and white pattern
Photo 2. A PAPI installation at Washington Dulles, from the FAA. The red and white pattern the pilot sees depends on siting and aim.Credit: Federal Aviation Administration. US Government work, public domain. Source page
Keyword Reference

Design Drawings, Bill of Quantities, Design Review & Rehabilitation Design

The documents that carry the design and the checks that prove it, including work on existing airfields.

Airfield lighting design drawings

Airfield lighting design drawings show light positions, circuits, cable routes, ducts, CCR and equipment room layouts, and the single line diagram. They are the main reference for construction, testing and later maintenance, so they must be complete, consistent and kept as-built. See AGL Drawings & Engineering Documentation above.

AGL bill of quantities

An AGL bill of quantities lists the fixtures, transformers, cables, connectors, CCRs, civil items and other work in a project, with descriptions, units and quantities. It is derived from the drawings and equipment schedule and should be cross-checked against design calculations. A clear bill of quantities helps tendering, cost control and ordering. See AGL BOQ, Equipment Schedule & Design Calculations above.

Airfield lighting design review

An airfield lighting design review checks the design before it is built. A typical review tests the layout against the standard, the circuit loading and voltage drop calculations, CCR and transformer selection, earthing, control, drawing consistency and maintainability. Reviews are often done at set stages, such as concept, detailed design and pre-construction. See the AGL Design Checklist below.

Airfield lighting rehabilitation design

Airfield lighting rehabilitation design covers upgrading or replacing lighting on an existing airfield. It starts with a survey of existing cables, ducts, circuits and equipment, then decides what can be reused and what must be replaced. It must also plan how work will be phased so the airfield stays operational, and how new equipment will work with existing CCRs and circuits.

Interactive

AGL Design Checklist

Before construction, the design should be systematically checked across four areas. Tick items off as you review a project — this resets on reload.

Airport Layout

Runway configuration checked
Taxiway configuration checked
Required lighting systems identified
0 / 3 complete

Electrical

Circuit configuration checked
CCR capacity checked
Transformer ratings checked
Cable selection checked
Loading checked
0 / 5 complete

Equipment

Fixture compatibility checked
Connector compatibility checked
Sign requirements checked
Control interfaces checked
0 / 4 complete

Documentation

Drawings coordinated
Cable schedule checked
Transformer schedule checked
BOQ coordinated
Design revisions controlled
0 / 5 complete

Define the item, gather the sources, follow every reference, fix the editions, test each standard against its scope, and record the list.

HOW THE APPLICABLE STANDARDS ARE FOUND 1 DEFINE THE ITEM Product, circuit, location, use and project stage OUTPUT: SCOPE STATEMENT 2 GATHER SOURCES Regulator rules, contract, spec, design basis and maker data OUTPUT: SOURCE DOCUMENTS 3 LIST STANDARDS Every standard named, and every one those standards refer to OUTPUT: CANDIDATE LIST 4 FIX THE EDITION Issue, amendments and any national differences OUTPUT: EDITION-CONTROLLED LIST 5 TEST APPLICABILITY Scope clause against the item; mandatory or advisory OUTPUT: APPLICABLE STANDARDS 6 RECORD & MAINTAIN Register kept with the matrix, updated when sources change OUTPUT: STANDARDS REGISTER FEEDBACK LOOP A newly found or referenced standard goes back to the list; repeat until no new standard appears, then record the result. IDENTIFY FIRST · THEN SELECT, DESIGN AND PROVE COMPLIANCE SIMPLIFIED SEQUENCE · CONFIRM CURRENT RULES WITH THE REGULATOR AND CLIENT
Figure 8. Define the item, gather the sources, follow every reference, fix the editions, test each standard against its scope, and record the list.
AGL Visual Encyclopedia: How do you identify the applicable standards for an AGL item Standard selection flowchart
Ongoing Engineering

Design Changes & Modifications

Airport lighting systems are frequently modified — new taxiway construction, runway extension, fixture replacement, LED upgrades, CCR replacement, circuit modification, new signs, PAPI modification, new approach lighting or circuit expansion. Every modification should be evaluated against the existing electrical system.

Circuit Load
Transformer Requirement
CCR Capacity
Cable Performance
Control Configuration
Connected Disciplines

AGL Design, Photometry, Commissioning & Maintainability

Design & Photometry

The designer establishes where the light is installed, what type of light is installed, how it is powered, how it is controlled and how it is aligned. Photometry then verifies how the installed light actually performs.

Design & Commissioning

A good design should make commissioning easier — the documentation should provide enough information to verify correct fixture installation, transformer selection, circuit connection, cable identification, CCR assignment, control configuration and intensity operation.

Design defines the intended system. Photometry verifies the optical result.

Design for Maintainability

  • Equipment accessibility
  • Cable identification
  • Circuit identification
  • Transformer identification
  • Spare capacity
  • Replacement compatibility
  • Maintenance isolation
  • Test points

The Engineering Cycle

Design for operation. Design for maintenance. Design for the future. A functional design that is difficult to maintain is an incomplete design.

Learn From Others

Common AGL Design Mistakes

Recognising these recurring mistakes early in a project is far cheaper than correcting them after installation.

01

Selecting Independently

Choosing equipment component-by-component rather than as a coordinated system.

02

Ignoring Total Loading

Not establishing the total circuit loading across the full series circuit.

03

Layout / Circuit Mismatch

Not coordinating the electrical circuit with the physical lighting layout.

04

Poor Cable Routing

Insufficient attention to cable routing and identification.

05

Poor Documentation

Weak documentation of transformer and fixture locations.

06

Ignoring the Future

Not allowing for future modifications or expansion.

07

Photometry as an Afterthought

Treating photometry as completely separate from the design process.

08

Generic Calculations

Using generic calculations without checking actual project conditions.

09

Uncoordinated Deliverables

Failing to coordinate drawings, schedules and the BOQ.

10

No Final Verification

Not verifying the final installed configuration against the design.

The Big Picture

The Complete AGL Engineering Cycle

An AGL system should be designed as a complete system, not as a collection of individual products — the CCR, series circuit, cable, isolation transformers, connectors, fixtures, control system, monitoring system and airport layout must work together from design through operation.

Design
Build
Test
Measure
Commission
Monitor
Maintain
Improve

Understand how airport ground lighting systems, visual aids, electrical circuits and control equipment fit together in a typical airport layout.

TERMINALTOWERAPPRWYTWYSTDCCR HOUSELV DISTRIBUTIONAPRON FLOODLIGHTSWINDSOCK (LIT)LOCALISERLANDING DIRECTIONRUNWAYPARALLEL TAXIWAYAPPROACHLIGHTSAPRON123456789SERIES CIRCUITS FROM THE CCR HOUSE (APPROACH, RUNWAY, TAXIWAY, STAND GUIDANCE)LOW-VOLTAGE SUPPLY TO APRON FLOODLIGHTS (NOT A SERIES CIRCUIT)TYPICAL LAYOUT · CONCEPTUAL PLAN VIEW · NOT TO SCALE
Figure 9. Understand how airport ground lighting systems, visual aids, electrical circuits and control equipment fit together in a typical airport layout.
AGL Visual Encyclopedia: What does a complete AGL airport layout look like
Where Design Sits

AGL Engineering Disciplines

AGL engineering sits at the intersection of several disciplines — a successful AGL system requires them to work together.

Airport PlanningElectrical EngineeringLighting EngineeringControl & AutomationInstallation EngineeringPhotometryTesting & CommissioningMaintenance
Test Yourself

Quick Knowledge Check

Q1. What isolates individual AGL fixtures from the high-voltage series circuit?

A. The CCR
B. The primary connector
C. The isolating transformer
D. The earthing conductor

Q2. CCR selection should primarily be based on:

A. The number of lights alone
B. The actual system design, including load, transformers and cable
C. The airport's runway length
D. Manufacturer availability only

Q3. Adding fixtures to an existing series circuit can affect:

A. Circuit load, transformer requirement, CCR capacity and cable performance
B. Only the fixture colour
C. Nothing, provided the fixtures are the same type
D. Only the airport's approach lighting
Explore More

Explore More AGL Engineering

FOUNDATION

AGL Fundamentals

Build your understanding of the complete Airfield Ground Lighting system.

Open AGL Fundamentals →
PERFORMANCE

AGL Photometry

Verify the optical performance of the installed system.

Open AGL Photometry →
STANDARDS

Standards Companion

Understand ICAO, FAA, IEC, IS and other applicable technical references.

Open the Standards Companion →
COMPONENTS

AGL Cables & Connector Engineering

Primary and secondary circuit hardware selection.

Open Cables & Connectors →
COMPONENTS

AGL Isolating Transformers

The fixture interface within the series circuit.

Open Isolating Transformers →
EQUIPMENT

Constant Current Regulators

CCR sizing and series-circuit power supply.

Explore CCR Engineering →
CONTROL

ALCMS

The control and monitoring system layered over the design.

Open ALCMS →
PROCESS

AGL Installation & Commissioning

Turning the design into a field-verified system.

Open Installation & Commissioning →
VERIFICATION

AGL Testing & Inspection

Electrical and photometric verification of the design.

Open Testing & Inspection →

Design It Right. Build It Once.

From airport layout to energized circuit, from electrical calculation to photometric verification — explore the complete AGL design and electrical engineering knowledge base.

AGL Engineering Hub

Explore the AGL Engineering Knowledge Hub

Fundamentals

Standards & Compliance

Runway, Taxiway & Approach Lighting

Surface Movement & Safety

PAPI

Electrical Engineering & Power

Photometry & Testing

Maintenance, Inspection & Safety

Resources, Documentation & Careers

FAQ

Frequently Asked Questions

Q1What is AGL design?

AGL design is the engineering process of converting an airport's operational and lighting requirements into a complete, coordinated airfield lighting system. It covers aerodrome layout, lighting systems, fixture locations, circuit configuration, CCR selection, series-circuit cable, isolating transformers, connectors, control and monitoring, earthing and bonding, electrical loading, installation, and testing and commissioning.

Q2What are the stages of the AGL design process?

The sequence runs from airport layout and operational requirements through lighting system selection, fixture layout, circuit planning, electrical load calculation, CCR selection, transformer and connector selection, cable design, earthing and protection, control and monitoring, drawings and BOQ, installation, testing and commissioning, and finally photometric verification of the installed system.

Q3Why do AGL systems use a series circuit?

The series circuit is designed so that the required current is maintained through the circuit while individual fixtures stay electrically isolated from the high-voltage primary circuit. A constant-current loop runs from the CCR through each isolating transformer and fixture and back to the CCR.

Q4How is a CCR selected for an AGL circuit?

CCR selection should be based on the actual system design rather than simply the number of lights. Factors include required circuit current, number of fixtures, transformer ratings, circuit load, CCR capacity, intensity steps, cable characteristics, circuit length, and control and monitoring requirements.

Q5Why does CCR output voltage rise with every transformer in the loop?

In a constant-current loop the current stays fixed, so the CCR must raise its output voltage to overcome the accumulated impedance of the cable and every transformer on the loop. This is why CCR sizing considers rated output voltage, not just current.

Q6What happens to the design when fixtures are added to a circuit?

A seemingly simple change such as adding fixtures can cascade through the design, affecting circuit load, transformer requirement, CCR capacity, cable performance and control configuration. This is particularly important when adding or replacing fixtures during airport modifications.

Q7What does a voltage drop and circuit performance check involve?

It considers the complete circuit rather than individual components: cable losses, transformer characteristics, circuit loading and CCR operating conditions such as output current, voltage headroom and step behaviour. The aim is that the whole system operates within the required parameters, not merely that each component meets its own rating.

Q8What do earthing, bonding and protection cover in AGL design?

Earthing and bonding cover equipment earthing, metallic structure bonding, transformer and CCR installation, and lightning protection interfaces where applicable. Protection covers overcurrent and surge protection, equipment protection, insulation and earth-fault monitoring, emergency isolation and interlocking. The arrangement must follow the applicable standards, airport requirements and project specifications.

Q9Why is circuit zoning important in AGL design?

Large systems often need multiple circuits or functional zones, and good zoning makes troubleshooting and maintenance significantly easier. Zoning considers runway and taxiway sections, approach systems, operational and maintenance requirements, CCR allocation, redundancy and future expansion.

Q10What drawings and schedules make up an AGL design package?

A complete package can include an AGL layout drawing showing equipment locations, a series circuit diagram, a CCR schematic, a transformer schedule and a cable schedule, among other engineering drawings and documentation, each serving a distinct purpose.

Field Insight

Engineering & Expert Notes

Design the Circuit Around Serviceability
Design

Position access points, spare capacity and sectioning so that faults can be isolated and repaired without taking the whole airfield out of service.

Leave Margin in CCR Loading
Loading

A circuit designed exactly to capacity leaves no room for later additions, cable ageing or higher losses. Agree and record the margin policy early.

Voltage Drop and Insulation Are Both Constraints
Cables

Check cable length against the CCR's available output voltage and verify the insulation rating for the primary voltage. A design can fail on either one.

Earthing and Surge Protection Belong in the First Layout
Protection

Adding protection late tends to produce compromises. Integrate earthing, bonding and surge devices into the original drawings and schedules.

Drawings and Schedules Must Agree
Documentation

Mismatches between single-line diagrams, layout drawings and bills of quantities cause site errors. Cross-check them before issue.

Run a Design Review With Operations and Maintenance
Review

People who will run the system often see access, control and spares issues the designer cannot. Invite them before construction starts.

Precision AGL Academy

Understand AGL. Build Your Engineering Skills.

You now understand how AGL systems are designed and electrically engineered — from layout and circuit zoning to CCR sizing, cable calculations and load schedules.

Take the next step with Precision AGL Academy.

Learn AGL Step by Step

Build your knowledge through structured technical learning covering:

AGL Fundamentals Components Electrical Systems Design Photometry Testing Troubleshooting Maintenance

Move from understanding how AGL works to developing the practical knowledge needed to analyse, operate and maintain complete AGL systems.

Understand the system. Build the knowledge. Apply the engineering.