THE AGL ENGINEERING CENTRE by Precision AGL Academy · Fault Diagnosis

Why Airfield Lights Fail Common Causes, Symptoms & Fixes

Work through the likely causes behind runway light outages, flickering, water ingress, damaged inset lights, transformer faults, CCR problems and control-system alarms, and learn how to investigate, verify and close an AGL fault with evidence.

Overview

Why AGL Failures Need a Structured Approach

Airfield Ground Lighting (AGL) failures can originate in the light fixture, secondary connection, isolating transformer, primary series cable, Constant Current Regulator (CCR), control interface or Airfield Lighting Control and Monitoring System (ALCMS).

A failed runway light does not always mean that the fixture itself is defective. The actual cause may be an electrical connection problem, damaged cable, transformer fault, circuit protection operation or control-system issue.

Effective fault diagnosis starts with recording the symptoms, identifying the affected asset and circuit, reviewing available monitoring information and following the approved fault-investigation procedure. Replacing a fixture without identifying the underlying cause may lead to repeated failures, unnecessary expenditure and incomplete corrective action.

This guide explains common AGL failure symptoms, their possible causes, evidence to review and general corrective-action considerations.

Important safety note: AGL systems support aircraft movement and airport operations. Troubleshooting, testing, isolation, repair and return-to-service decisions must be performed by authorized personnel under the airport’s approved safety, access, isolation, maintenance and operational procedures. The possible causes listed below are diagnostic starting points, not confirmation of a fault or instructions for intrusive electrical work.

Topics covered in this guide

Runway lights not workingFlickeringWater ingressInset light damageIsolating transformersCCR & series circuitsALCMS & controlCables & connectorsLED fittingsSymptom reference tableInvestigation processFault report templatePreventing recurrence

Where a fault can start, and what to look at first.

LIGHT NOT WORKING OR ABNORMALA symptom, not a diagnosisFixtureEVIDENCEInspection notesAsset historyEquipment recordsSecondaryconnectionEVIDENCEConnector conditionInspection recordsIsolatingtransformerEVIDENCEIdentification, ratingsTest recordsPrimary cableand jointsEVIDENCECircuit recordsPrior faultsApproved cable testsCCRand supplyEVIDENCEAlarm historyEvent recordsMaintenance logControl(ALCMS)EVIDENCECommand statusFeedbackEvent logsConfirm the cause from evidence, under the approved procedure,before any part is replaced.
Figure 1. Fault tree for a runway light that is not working. Six places a fault can start, with the evidence to review for each. The symptom alone does not identify the cause.
1 · Lights Not Working

Why Are Runway Lights Not Working?

When runway lights stop operating, the first task is to establish the extent of the failure. Determine whether the symptom affects one fitting, several fittings on a circuit or a wider lighting system.

The number and location of affected lights can help narrow the investigation, but the failure pattern alone does not establish the root cause.

Common causes of runway light failure

Possible causeTypical area to investigateEvidence to review
Fixture failureIndividual light fittingInspection observations, asset history and relevant equipment records
Secondary connection faultFixture connection and associated wiringConnector condition and approved inspection records
Isolating transformer faultTransformer and its connectionsTransformer identification, ratings and available test records
Primary cable faultSeries-circuit cable and jointsCircuit records, prior fault reports and approved cable-test results
CCR protection operationCCR and circuit power equipmentAlarm history, operating indications and maintenance records
Supply or internal CCR problemCCR power and internal equipmentAvailable event records and authorized inspection findings
Control command problemLocal or remote control interfaceCommand status, feedback, event logs and operating records
Multiple equipment defectsAffected lighting circuit or installation areaFailure distribution, asset history and inspection evidence

Individual light failure versus multiple light failure

When one light is not working

A local fixture fault, secondary connection issue, isolating transformer fault or another associated equipment problem may be involved. The cause must be confirmed using the approved investigation method.

When several lights on the same circuit are affected

The investigation may need to include the CCR, circuit condition, primary cable, connections, protection indications and relevant control functions.

When several unrelated systems are affected

Review any common equipment, control interface, supply arrangement or event that could explain the symptoms, while checking each affected system according to its approved procedure.

Recommended investigation record

Record the following before concluding the fault investigation:

Affected runway, taxiway, approach system or other installationExact fixture or equipment identification, where knownCircuit number and associated CCR, where applicableTime the failure was observed and reportedWhether the fault is continuous, intermittent or newly detectedAvailable CCR alarms and control-system indicationsRecent maintenance, replacement or modification historyInspection and test records relevant to the suspected fault
Do not replace every non-operating fitting automatically. Establish the likely failure area and record the evidence that supports the diagnosis.

Three ways a series loop can fail, and what each one looks like.

SERIES LOOP · WHERE DOES THE CURRENT GO? ISOLATE & LOCK OUT BEFORE TOUCHING CABLE ENDS A OPEN CIRCUIT T1 T2 T3 CCR PATH NONE · LOOP BROKEN LAMPS ALL OUT TESTER OVER-RANGE (OL) B SHORT CIRCUIT T1 T2 T3 CCR PATH SHORTCUT, REST SKIPPED LAMPS BEYOND SHORT OUT TESTER FAR BELOW BASELINE C EARTH FAULT T1 T2 T3 CCR PATH LOOP INTACT + LEAK LAMPS STAY ON INSUL. LOW TO EARTH A SECOND EARTH FAULT ELSEWHERE BEHAVES LIKE B SCHEMATIC · LOOP SHORTENED · NOT TO SCALE
Figure 2. Open circuit, short circuit and earth fault in a series loop. One failed light does not always mean a failed fixture.
AGL Visual Encyclopedia: Series-circuit fault path Lamp-out behaviour Earth fault
An airman checking a runway light at night after replacing the bulb
Photo 1. An electrician checks a runway light after replacing a bulb. Confirming the light at the fitting is one step; the cause may lie elsewhere on the circuit.Credit: U.S. Air Force photo by Staff Sgt. Stephenie Wade, Bagram Airfield, June 2013. Public domain (US Government work). Source page
2 · Flickering

What Causes Runway Light Flickering?

Runway light flickering or intermittent operation may indicate a problem with the fixture, electrical connections, associated equipment, circuit or control system.

Because similar symptoms can result from different faults, an observation of flickering should be treated as a symptom rather than a definitive diagnosis.

Possible causes of flickering

Possible causeWhat to investigate
Intermittent connectionAvailable connector and connection inspection records
Fixture component problemFixture condition, product history and relevant manufacturer guidance
Isolating transformer issueTransformer identification, condition and approved test results
Cable or joint deteriorationCircuit history, accessible installation condition and prescribed test records
CCR operating issueRecorded output indications, alarms and applicable event history
Control or monitoring issueRelationship between observed lighting behaviour and recorded commands or feedback
Equipment incompatibilityCompatibility of the installed components with the approved circuit design
Environmental damageEvidence of moisture, contamination, impact or deterioration

How to document flickering

Record whether the flickering is observed at one fitting, multiple fittings on the same circuit or multiple systems. Include the time, operating conditions, available equipment indications and any recurring pattern.

Review the information using the airport’s approved troubleshooting process. Do not assume that an apparent change in light output proves a CCR fault or that a control-system alarm proves a field-equipment failure.

Corrective action should follow the confirmed cause and the relevant equipment instructions.

A flicker is logged as an event, then traced to the likely cause.

INTERMITTENT-FAULT TROUBLESHOOTING · RECORD, REPEAT, TRACELIGHTS NORMALFAULT APPEARSTHEN CLEARSAGAINAGAINTIME →LOG EACH EVENT: TIME · WEATHER · BRIGHTNESS STEP · CCR CODE1SYMPTOMFLICKERING LIGHTCause: loose or wetconnection or jointCheck: connectors, joints2SYMPTOMALARM COMES, CLEARSCause: fault that onlyshows in some conditionsCheck: event log, alarm history3SYMPTOMREADINGS WANDERCause: intermittent jointor poor test connectionCheck: test lead, repeat4SYMPTOMWORSE WET OR HOTCause: moisture, corrosion,ageing insulationCheck: IR trend vs baseline5SYMPTOMNORMAL ON ARRIVALCause: fault not presentto be measuredCheck: records, no blind resetTELL ATC · TEST DE-ENERGISED · ISOLATE, LOCK OFF, PROVE DEAD · NEVER SEPARATE A LIVE PRIMARY CONNECTOR
Figure 3. Intermittent-fault troubleshooting map: log each event with time, weather, brightness step and CCR code, then match the symptom to causes and checks.
AGL Visual Encyclopedia: Intermittent-fault troubleshooting Loose connection LED driver, thyristor CCR flicker
3 · Water Ingress

Airport Light Water Ingress

Water ingress can contribute to corrosion, connection problems, insulation deterioration and damage to electrical or optical components.

The significance of water ingress depends on the fixture design, the affected component, the degree of exposure and the manufacturer’s requirements.

Common contributors to water ingress

Damaged or deteriorated sealing componentsCompromised cable entries or connection arrangementsIncorrect assembly or installationPhysical damage to the fitting or enclosureEnvironmental exposure beyond the equipment’s intended conditionsMaintenance or replacement work that does not restore the specified sealing arrangementDrainage or installation conditions inconsistent with the approved design

Inspection and corrective-action considerations

Record the equipment identification and observed condition. Where required, document visible moisture, corrosion, damaged seals, cable-entry concerns and relevant maintenance history.

The corrective-action process should establish the extent of the damage and whether associated electrical components require inspection, testing, replacement or other manufacturer-approved attention.

Cleaning or drying a fitting alone may not resolve the underlying cause. Any repair, reassembly, sealing or verification must follow the equipment instructions and the airport’s approved maintenance procedure.

Three paths water can take into an in-pavement light.

MOISTURE INGRESS · WATER WHERE IT SHOULD NOT BE ISOLATE & PROVE DEAD BEFORE OPENING A CAN OR PIT BASE CAN CROSS-SECTION PAVEMENT TRANSFORMER SUMP DRAIN BLOCKED grout, silt or debris 1 LENS & BODY SEAL 2 PAVEMENT JOINT 3 CABLE ENTRY WATER STANDS AROUND THE TRANSFORMER WHAT WATER DOES FIRST IR FALLS Often well before any fault appears THEN CORROSION & DAMAGE Terminals, optics, driver, LED FINALLY EARTH FAULT / OPEN Flicker, trip or lights out SEEN FOGGED / WET Water or fog inside the lens, wet can MEASURED FALLING IR Reading drops from test to test ON THE CIRCUIT EARTH FAULT Alarm, flicker or fixtures out LOOK FIRST: LENS & GASKETS · CABLE ENTRIES · CONNECTOR SEALS · BLOCKED DRAINS SCHEMATIC · SIMPLIFIED · NOT TO SCALE
Figure 4. Moisture ingress at an in-pavement light: lens and body seal, pavement joint around the can, and cable and duct entry.
AGL Visual Encyclopedia: Moisture ingress Water-ingress condition Water-ingress prevention Sealing system
4 · Inset Lights

Inset Light Damage and Failure

Inset airfield lights are installed within pavement and may experience mechanical loading, impact, contamination and environmental exposure. Their installation condition and compatibility with the approved mounting arrangement are important to reliable operation.

Common causes of inset light damage

Possible causeInspection considerations
Pavement-related loading or impactLook for evidence of damage to the fixture or surrounding pavement
Incorrect installationReview installation records and the approved mounting arrangement
Damaged lens or optical surfaceRecord cracks, contamination or other visible abnormalities
Loose or damaged mounting arrangementReview the prescribed inspection findings and installation details
Water ingressCheck relevant indicators and available sealing or maintenance records
ContaminationRecord deposits or material that may affect the optical surface
Connection or component defectReview relevant connection and equipment records
Inappropriate handlingCheck maintenance and replacement history where available

Why the surrounding pavement matters

A fitting and its surrounding pavement may need to be assessed together. Visible pavement damage, deterioration around the mounting area or evidence of physical impact may be relevant to the investigation.

Replacement decisions should take account of the specified fitting, approved installation details, required optical performance and any necessary pavement work. After corrective work, perform the inspections and acceptance checks required by the approved procedure.

Do not assume that installing a replacement fixture alone resolves the underlying installation or pavement-related cause.

Inset light in section: window, body, flange, base, transformer and cable.

SIDE ELEVATION · CUTAWAY RUNWAY PAVEMENT PAVEMENT STRUCTURE DESIGNED TO BE ROLLED OVER IT 1 LENS & PRISM WINDOW Low-angle optical window, sealed 2 FIXTURE BODY Flush; projects only ~13 mm (typical) 3 TOP FLANGE & BOLTS Secures the fixture to the base 4 LIGHT BASE Shallow can set into the pavement 5 ISOLATION TRANSFORMER Couples the lamp to the series circuit 6 PRIMARY CABLE Series-circuit feed, underground SCHEMATIC CUTAWAY OF A TYPICAL INSET FIXTURE · NOT TO SCALE · PROJECTION EXAGGERATED
Figure 5. Cutaway of an inset runway light set flush in the pavement. The fitting and the surrounding pavement are assessed together.
AGL Visual Encyclopedia: Inset runway light Rubber deposit build-up Structural deterioration
An airman removing the light from a flush edge light at an air base
Photo 2. An airman removes the light unit from a flush edge light. Inset fittings are worked on at the fixture and its base, so record the condition of both.Credit: U.S. Air Force photo by Senior Airman Brittany A. Chase, Misawa Air Base, Aug. 23, 2017. Public domain (US Government work). Source page
5 · Isolating Transformers

What Causes AGL Isolating Transformer Failure?

An airfield lighting isolating transformer forms part of the lighting circuit and must be suitable for its specified electrical and installation conditions.

Transformer-related failures may be associated with insulation deterioration, moisture ingress, physical damage, connection defects or operating conditions outside the equipment’s intended ratings.

Possible transformer failure causes

Possible causeEvidence to review
Insulation deteriorationApplicable electrical test results and maintenance history
Moisture ingressObserved condition, connector details and relevant installation records
Physical damageInspection findings and equipment history
Connector or connection defectConnector compatibility, assembly records and authorized inspection results
Incorrect equipment selectionTransformer rating, circuit schedule and associated fixture requirements
Equipment deteriorationAge, service history, previous faults and manufacturer guidance
Installation problemApproved drawings, installation records and relevant inspection findings
External cable or circuit faultCircuit records and results from the approved investigation process

Transformer fault investigation checklist

Identify & verify

Record the transformer asset identification and location.
Verify the specified transformer rating against approved records.
Record observable physical or environmental damage.
Review associated connector and cable information.
0 / 4 complete

Review & record

Check previous maintenance, replacement and test records.
Review relevant fixture and circuit information.
Record the test procedure and results used in the investigation.
Document the identified cause, corrective action and required verification.
0 / 4 complete
A light that stops operating does not automatically indicate transformer failure. Other circuit components and connections may produce similar symptoms.
Transformer inspection and testing must use the specified methods and appropriate instruments. Do not apply generic electrical test values or procedures to every transformer type.

Five checks on an isolating transformer, from primary to housing.

TRANSFORMER TROUBLESHOOTING · SYMPTOM, CAUSE, CHECKPOTTED HOUSINGP1P2SERIESLOOPS1S2FIXTUREPRIMARYSECONDARY123451 PRIMARY CONTINUITY · 2 SECONDARY CONTINUITY · 3 PRIMARY TO EARTH IR4 PRIMARY TO SECONDARY IR · 5 VISUAL: HOUSING, POTTING, WATERALL LIGHTS OUTPrimary winding open · check 1CCR TRIPS, EARTH FAULTInsulation breakdown · checks 3, 4, 5ONE LIGHT OUT, LOOP COMPLETESecondary side · check 2DIM OR FLICKERING LIGHTSecondary connection · checks 2, 5HOT, DISCOLOURED, SMELLOverload or internal fault · check 5ALWAYSTELL ATC · ISOLATE AND LOCK OFF THE CCR · TEST THE TRANSFORMER DISCONNECTED · AUTHORISED ONLYTest methods and limits come from the transformer manufacturer and the airport’s safe-working rules.
Figure 6. Transformer troubleshooting map: primary and secondary continuity, insulation resistance and a visual check. Carry out tests only under the approved procedure; a light that stops does not automatically mean a failed transformer.
AGL Visual Encyclopedia: Transformer failure modes Transformer troubleshooting Isolation transformer principle
6 · CCR & Series Circuits

CCR Problems and Series Circuit Failures

The Constant Current Regulator (CCR) supplies the required current to the associated AGL series circuit. Its indications, alarms and event records can be useful evidence when investigating a lighting failure.

However, a CCR alarm or shutdown indication does not, by itself, identify the defective component.

Common CCR failure areas

Possible issueEvidence to review
Protection operationAlarm history, recorded event information and applicable protection records
Internal component faultAuthorized maintenance findings and manufacturer guidance
Cooling or ventilation problemEquipment indications and prescribed inspection records
Power supply issueAvailable equipment indications and authorized inspection results
Incorrect configuration or settingsApproved configuration records and relevant event history
Control interface problemCommand, feedback and communication records
Circuit-related faultAffected circuit information and approved investigation results
Recurring equipment problemMaintenance history, fault frequency and prior corrective actions

Series circuit failure investigation

Series-circuit failures may involve the primary cable, cable joints, connectors, isolating transformers, light fittings or associated power and control equipment.

Useful evidence may include

Circuit identification and approved circuit drawingsPattern and location of affected lightsCCR alarm and event recordsPrevious circuit faults and maintenance activitiesAvailable cable, connection and transformer test recordsRecent equipment changes or repairsResults of approved inspection and testing

The investigation should distinguish between a confirmed component fault and a symptom that could have several causes.

Safety note: Do not open energized equipment, disconnect series-circuit components, change CCR settings or perform intrusive tests without the approved isolation and work procedures. Authorized personnel must follow the specified method for the equipment and circuit being investigated.

Six CCR symptoms, each with a first check and a likely area.

CCR TROUBLESHOOTING · SYMPTOM, FIRST CHECK, LIKELY AREASYMPTOMFIRST CHECKLIKELY AREANO DISPLAY, WON'T STARTNothing lit on the CCRSupply, input protection, control powerPOWER INPUTRUNS, NO OUTPUT CURRENTOpen-circuit alarmCircuit side first, then CCR outputCIRCUITTRIPS OR EARTH-FAULT ALARMProtection operatesCircuit insulation, then CCR output stageCIRCUIT / CCRCURRENT WRONG FOR THE STEPReading differs from expectedStep setting, controller, thyristor, measurementCONTROLOVER-TEMPERATURE ALARMCCR running hotCooling, airflow, ambient, load ratingCOOLINGIGNORES REMOTE COMMANDSLocal panel worksSelector, communication, ALCMS linkCONTROL PATHALWAYSREAD THE DISPLAY AND ALARM FIRST · TELL ATC · ISOLATE AND PROVE DEAD BEFORE OPENING THE CABINETThe CCR holds high voltage inside and drives high current into the circuit. Authorised personnel only, using the manufacturer’s procedure.
Figure 7. CCR troubleshooting map. An alarm or trip does not by itself identify the defective component.
AGL Visual Encyclopedia: CCR troubleshooting CCR to series-circuit interface Series-circuit troubleshooting
An airman testing the voltage of a constant current regulator with a multimeter
Photo 3. An electrician tests a constant current regulator with a multimeter. Measuring CCR output is the first step in separating a regulator fault from a circuit fault.Credit: U.S. Air Force photo by Staff Sgt. Nick Wilson, Whiteman AFB, January 2013. Public domain (US Government work). Source page
7 · ALCMS & Control

ALCMS and Control-System Failures

The Airfield Lighting Control and Monitoring System (ALCMS) may provide operator control, status indications, alarms and other approved functions. A failure within the control system can affect the command or indication path, while a field-equipment failure can generate an alarm or status abnormality within the system.

The investigation should distinguish between the reported indication and the actual condition of the lighting equipment.

Possible ALCMS failure causes

Possible causeEvidence to review
Communication lossRecorded communications alarms and interface status
Incorrect configurationApproved configuration records and documented changes
Interface failureRelevant interface status and authorized test records
Faulty status feedbackComparison of recorded indications with approved verification results
Operator command issueRelevant event records and authorized operating information
Power or hardware problemEquipment alarms and maintenance records
Field circuit faultCCR indications, circuit history and approved field inspection results
Integration issueInterface specifications, change records and integration test evidence

ALCMS fault reporting checklist

Capture the indication

Record the reported alarm or abnormal indication.
Identify the affected system, control station and circuit, where known.
Record the time and relevant operational context.
Review available event and communication records.
0 / 4 complete

Verify & close

Identify recent configuration or maintenance changes.
Determine which field equipment is reported as affected.
Record the authorized test or verification results.
Document corrective actions and required functional checks.
0 / 4 complete
Control-system indications should be interpreted according to the approved system documentation. Avoid changing configurations, resetting equipment or bypassing functions without authorization and a defined procedure.

Related Guides

ALCMS guide

Work through the control layers before blaming the field.

ALCMS TROUBLESHOOTING FLOW · WORK THROUGH THE LAYERS1 COMMS ALARM OR STALE STATUS?Screen shows link lostYESCHECK SERVER, NETWORK, CONTROLLERFind the layer that lost contactNETWORK / SERVERNO · NEXT CHECK2 SELECTOR IN LOCAL OR OFF?Check at the CCR panelYESNOT A FAULT: REMOTE IGNOREDTell ATC, restore Remote after workCCR PANELNO · NEXT CHECK3 CCR FAULT OR NO OUTPUT?CCR alarm, no output currentYESCCR OR PROTECTION FAULTAlarm, isolate, repairCCRNO · NEXT CHECK4 CCR OUTPUT OK, LIGHTS WRONG?Current normal, lights darkYESCIRCUIT OR FIXTURES AT FAULTField tests by authorised engineersCIRCUITNO · RE-CHECK STATUS AT THE EQUIPMENT, ESCALATEIN EVERY CASE1 TELL ATC FIRST2 AUTHORISED ENGINEERS ONLY3 CHECK STATUS AT THE EQUIPMENT4 Test after repair · restore Remote · confirm status on the screen · tell ATC control is back
Figure 8. ALCMS troubleshooting flow: tell ATC first, use authorised engineers and confirm status before returning to remote control.
AGL Visual Encyclopedia: ALCMS troubleshooting flow ALCMS failure flow ALCMS event logging
An airman using a regulator to turn on airfield lights at Bagram Airfield
Photo 4. An electrician switches the airfield lights on at the regulator. Each circuit has its own regulator, so control, regulator and circuit must be checked together.Credit: U.S. Air Force photo by Staff Sgt. Stephenie Wade, Bagram Airfield, June 2013. Public domain (US Government work). Source page
8 · Cables & Connectors

Airfield Lighting Cable and Connector Failure Causes

AGL cable and connector faults may arise from physical damage, deteriorated insulation, poor joints, moisture exposure, installation defects or external excavation.

Primary series cables and secondary connections have different functions and should be investigated using the applicable circuit documentation and test methods.

Common cable and connector problems

Possible issueEvidence to review
Physical cable damageInspection findings, installation route information and maintenance history
Insulation deteriorationApplicable test results and condition history
Joint or termination problemJointing and termination records, plus authorized inspection findings
Connector damageConnector identification, condition and assembly records
Water exposureEnvironmental observations and relevant installation details
Excavation or civil works damageSite records, reported incidents and cable-route information
Incorrect component selectionApproved material schedule and compatibility requirements
Undocumented modificationAs-built drawings, work orders and circuit records

Cable fault investigation record

A cable investigation record should include:

Cable identification and circuit referenceCable type and relevant specificationRoute information and known joints or terminationsDescription of the reported symptomRelevant CCR or circuit indicationsTest method and procedure referenceTest instrument identification where requiredActual measured result and units, where applicableAcceptance criterion and document revisionInvestigation findings and corrective-action reference
Use the specified method and acceptance values for the particular cable and circuit. Test voltage, test duration and acceptance limits must not be selected from a generic checklist.

Where a primary cable or connector can fail.

CABLE FAILURE · CONDUCTOR & INSULATION FAULT ISOLATE & PROVE DEAD BEFORE WORKING ON A CABLE BURIED PRIMARY CABLE RUN GROUND CCR OUTPUT ON CABLE DAMAGE EVERY LIGHT OUT LOOP CURRENT CABLE CROSS-SECTION CONDUCTOR INSULATION OUTER JACKET CONDUCTOR BREAK OPEN CIRCUIT Every light out, CCR trips INSULATION BREAKDOWN EARTH FAULT Lights stay on, fault is silent WET OR DAMAGED JACKET DRIFTING IR Insulation resistance falls over time CAUSES: EXCAVATION · CRUSHING · MOISTURE · AGEING · SURGE · POOR INSTALLATION LOOK FIRST: JOINTS & TERMINATIONS · DUCT CROSSINGS · RECENT DIGGING · WET PITS SCHEMATIC · SIMPLIFIED · NOT TO SCALE
Figure 9. Cable failure causes along a series circuit. Use the specified test method and acceptance values for the cable and circuit.
AGL Visual Encyclopedia: Cable failure Cable troubleshooting Connector troubleshooting Cable fault location
9 · LED Fittings

Why LED Airfield Lights Fail

LED airfield lights can experience failures involving the light source, electronic components, power or control interfaces, optical components, connections or environmental protection.

The likely cause depends on the particular product design, installation and operating conditions.

Possible LED light failure causes

Possible causeWhat to review
Electronic component failureManufacturer’s diagnostic guidance and equipment history
Thermal stressInstallation conditions and relevant product requirements
Environmental exposureEvidence of moisture, contamination or physical damage
Connection faultAccessible inspection records and approved test findings
Power-system compatibilityCompatibility information for the installed circuit and equipment
Control-interface issueOperating commands, indications and related event logs
Optical damageLens and other optical inspection findings
Product deteriorationService history and available manufacturer assessment

LED compatibility considerations

An LED fitting should not be assumed compatible with an existing AGL circuit simply because its physical dimensions are suitable.

Before a replacement or retrofit is accepted, verify the required electrical characteristics, approved system compatibility, control interfaces and any specific acceptance tests required by the project.

Potential energy or maintenance savings do not replace the need to demonstrate technical suitability and compliance with the applicable requirements.

Why a compatible-looking LED fitting can still flicker on a CCR.

CCR OUTPUT CURRENT AND LED LIGHT OUTPUT · ILLUSTRATIVE WAVEFORMS 1 · FULL STEP (B5) AMPS LIGHT STEADY LIGHT CURRENT CLOSE TO A SINE WAVE ANY GOOD DRIVER COPES 2 · LOW STEP, DRIVER NOT SMOOTHING AMPS LIGHT LIGHT FOLLOWS THE PULSES FLICKER AND STROBING SHOW WORST AT THE LOWEST STEPS 3 · LOW STEP, DRIVER SMOOTHING AMPS LIGHT STEADY LIGHT AGAIN SAME CURRENT, SAME AVERAGE LIGHT ENERGY STORE CARRIES THE GAPS CCR THYRISTORS FIRE LATE AT LOW STEPS LOOP CURRENT CHOPPED INTO PULSES GAPS BETWEEN THEM TRANSFORMER PASSES THE WAVEFORM TO THE FIXTURE LED DRIVER SMOOTHS OR FOLLOWS THE DESIGN DECIDES LIGHT STEADY, OR FLICKER AND STROBING FLICKER SHOWS FIRST AT THE LOW STEPS · TEST THE REAL FIXTURE ON THE REAL CCR AT EVERY STEP
Figure 10. LED output against CCR current at full and low steps. Physical fit does not prove electrical compatibility.
AGL Visual Encyclopedia: LED driver, thyristor CCR flicker Retrofit and CCR resizing Mixed halogen and LED circuits
Two airmen examining an LED light on a runway
Photo 5. Airmen examine an LED light on a newly completed runway. LED fittings should be checked for circuit compatibility, not only fit.Credit: U.S. Air Force photo by Sonic Johnson, Columbus Air Force Base, Sept. 3, 2013. Public domain (US Government work). Source page
10 · Symptom Reference

Common AGL Fault Symptoms and Their Possible Causes

The following table is a first-level reference for organizing fault investigations. Each symptom may have more than one cause, and the actual cause must be established from evidence.

Observed symptomPossible causesRecommended investigation focus
One runway light not operatingFixture, secondary connection, transformer or associated wiring faultAsset history, local inspection records and approved test results
Several lights affected on a circuitCCR, primary cable, circuit connection or other shared equipment issueCircuit pattern, CCR indications and circuit records
Intermittent light outputConnection, equipment, circuit or control-related issueTiming, affected locations, event records and approved inspection results
Water or moisture evidenceDamaged seals, compromised cable entry or environmental exposureEquipment condition, assembly details and manufacturer requirements
Inset fitting damagedImpact, loading, mounting or pavement-related issueFixture and surrounding pavement inspection
CCR alarm or trip indicationProtection operation, regulator fault or circuit-related issueEvent history and the approved investigation procedure
ALCMS indicates a faultField fault, interface problem, communications issue or inaccurate feedbackAlarm details, event history and authorized verification
Repeated transformer-related reportsTransformer defect, connections, installation conditions or another circuit problemTransformer and circuit history, specifications and test evidence
Cable fault suspectedPhysical damage, joint issue, insulation deterioration or external interferenceRoute records, incident history and approved cable tests
LED fitting failureElectronic, environmental, optical, connection or compatibility issueProduct information, circuit compatibility and manufacturer guidance
This table is not a fault-isolation decision tree. It should be used to structure evidence collection and record the suspected cause for further authorized investigation.

One light out versus many: the pattern points to where to start.

MULTIPLE-FIXTURE FAILURE · SUSPECT THE CIRCUIT, NOT THE FIXTURECCRSHORT: BEYOND IT DARKSHORTCUTCCREVERY 2ND: ONE CIRCUIT OUT1PATTERNEVERY 2ND LIGHT DARKCause: one interleavedcircuit out: open / CCRCheck: CCR alarm, output2PATTERNBEYOND A POINT DARKCause: short circuitbypasses the loopCheck: IR / continuity, split3PATTERNSCATTERED LIGHTS DARKCause: common cause:water, surge, ageingCheck: pits, connectors, each4PATTERNSEVERAL DIM TOGETHERCause: step setting, leakageor heavy loadingCheck: CCR current at step5PATTERNEACH LOCAL FAULTCause: separate fixture-sidefaults, loop completeCheck: secondary, then fixtureTELL ATC · CCR OFF, ISOLATED, LOCKED OUT · PROVE DEAD · THEN SPLIT THE LOOP AND TEST
Figure 11. Multiple-fixture-failure troubleshooting. The pattern narrows the search but does not prove the cause.
AGL Visual Encyclopedia: Multiple-fixture failure Fixture troubleshooting Series-circuit troubleshooting
11 · Investigation Process

A Systematic AGL Fault Investigation Process

A documented fault investigation helps teams identify the cause, avoid unnecessary component replacement and reduce recurring defects.

01

Record the reported symptom. Capture the observation, time, location, affected asset and any available operator or maintenance report. Avoid recording an assumed cause as if it were already confirmed.

02

Establish the failure scope. Identify whether the problem affects one fixture, multiple fittings, one circuit or several systems. Confirm equipment and circuit identities against approved records.

03

Review available indications. Review applicable CCR alarms, control-system status, circuit records and event history. Determine whether the available indications are consistent with the reported symptom.

04

Review previous maintenance. Check work orders, previous failures, equipment replacement history and any recent installation or configuration changes. Repeated faults may indicate an unresolved underlying cause, but the pattern alone is not sufficient to prove one.

05

Define the authorized investigation. Select the inspection or test method using the approved maintenance procedure, equipment instructions, applicable specifications and authorization requirements. Identify any access restrictions, isolation requirements, permits or operational coordination needed before work begins.

06

Record findings. Document observed conditions, tests performed, actual results, relevant instrument details, acceptance criteria and the procedure used.

07

Establish the cause. Separate the confirmed cause from other possible explanations. If the available evidence is inconclusive, record the investigation status and identify the next authorized action.

08

Carry out corrective action. Repair, adjust or replace equipment only under the approved procedure and within the responsible personnel’s authorization.

09

Verify the result. Perform the required post-maintenance tests, inspections or functional checks and record the results against the applicable acceptance criteria.

10

Close the record. Document the root cause where established, corrective work, verification evidence, outstanding items and authorized closure.

A fault should not be considered fully resolved merely because the original symptom is no longer visible. The required verification and closure process must be completed.

Isolate the fault in a fixed order.

FAULT-ISOLATION FLOWCHART · SYMPTOM, TYPE, SECTIONFIRSTTELL ATC · SWITCH OFF AND ISOLATE THE CCR · LOCK OFF · AUTHORISED PERSONNEL ONLYALL LIGHTS OUTCCR open-circuit alarm, no currentOPEN CIRCUITa break in the loopTEST CONTINUITY BY SECTIONFault is where it failsCCR TRIPSEarth-fault or overcurrent alarmEARTH FAULTinsulation to earth is lowTEST INSULATION RESISTANCE BY SECTIONLow reading marks the sectionSOME LIGHTS OUTCCR normal, circuit runningLOCAL FAULTfixture, connector or transformerCHECK THE DEVICE ITSELFLight, secondary connector, transformerNARROW DOWN BY HALF-SPLITTEST: GOOD · SET ASIDEBAD · SPLIT AGAINfault sectionTHEN1 Repair the faulty part2 Retest section and circuit3 Restore, run, confirm status4 Record results, tell ATC
Figure 12. Fault-isolation flowchart: establish scope, then work from the indication to the confirmed cause.
AGL Visual Encyclopedia: Fault-isolation flowchart Corrective maintenance sequence Safe maintenance sequence
An electrical systems craftsman repairing a taxiway edge light
Photo 6. An electrical systems craftsman repairs an inoperable taxiway edge light. Repair follows the documented investigation, under the approved procedure.Credit: U.S. Air Force photo by Staff Sgt. Nick Wilson, Whiteman Air Force Base, Jan. 29, 2013. Public domain (US Government work). Source page
12 · Fault Report Template

AGL Fault Report Template

Use a consistent record format for runway, taxiway, approach lighting, CCR, transformer, cable and control-system faults.

Fault investigation record

FieldDetails
Fault reference
Date and time reported
Airport / location
System / equipment type
Asset ID / circuit number
Reported symptom
Number / location of affected fittings, if applicable
CCR or ALCMS indication
Relevant operating context
Previous fault or maintenance reference
Investigation procedure reference
Tests and inspections performed
Measured results and units, where applicable
Applicable acceptance criterion
Confirmed cause or investigation status
Corrective action taken
Required post-maintenance verification
Verification result
Outstanding items
Responsible person / reviewer
Closure date and approval

Example fault record

The following is an illustrative record structure, not a real incident or a confirmed technical diagnosis.

FieldExample entry
Reported symptomOne lighting fitting reported as not operating
Initial assessmentCause not yet confirmed
Evidence reviewedAsset identification and available maintenance history
InvestigationTo be completed under the approved procedure
Corrective actionTo be determined from investigation findings
VerificationRequired checks to be recorded against applicable criteria
ClosurePending authorized review
This approach keeps observations, diagnosis, corrective action and verification separate and traceable.

From first report to closure, and what is recorded at each stage.

1 REPORTFault referenceDate and timeAsset ID, circuitReported symptom2 INVESTIGATEProcedure referenceTests and inspectionsMeasured resultsAcceptance criterion3 FINDINGSCause or statusCCR or ALCMS indicationPrevious fault reference4 ACT AND VERIFYCorrective actionPost-work verificationVerification result5 CLOSEOutstanding itemsResponsible reviewerClosure date, approvalObservation, diagnosis, corrective action and verification are kept separateso every step stays traceable.
Figure 13. The fault report as five stages. The fields match the template above.
13 · Prevention

Preventing Recurring AGL Failures

Failure prevention depends on correct equipment selection, quality installation, suitable inspection and maintenance practices, reliable records and effective defect closure.

Useful reliability practices

Maintain accurate asset registers and circuit drawingsRecord equipment model, rating and replacement historyPerform scheduled inspections according to approved maintenance requirementsRetain test reports and relevant instrument recordsReview recurring faults rather than treating each incident in isolationCheck compatibility before replacing fixtures, transformers or control equipmentDocument installation changes and update controlled records as requiredInvestigate repeated water ingress, physical damage or connection problemsTrack outstanding defects and verify their closureReview relevant alarms and maintenance trendsUse root-cause analysis where appropriate to the severity and recurrence of the faultUse only approved components, procedures and acceptance criteria

Why root-cause analysis matters

Replacing a failed component may restore function, but it may not address the condition that caused the failure.

For example, if a replacement component fails repeatedly, the investigation may need to consider installation conditions, external damage, component compatibility, electrical conditions or maintenance history. These are hypotheses to investigate—not conclusions to make without evidence.

Engineering objective: Identify the actual cause, implement the appropriate corrective action and retain enough evidence to verify the result.

Prevention is a loop, not a one-off repair.

1 KEEP RECORDSAsset registers, drawings,test reports2 INSPECT AND MAINTAINScheduled, to approvedmaintenance requirements3 SPOT REPEAT FAULTSReview fault frequency,alarms and trends4 ROOT-CAUSE ANALYSISWhere severity orrecurrence warrants it5 FIX, UPDATE RECORDSApproved components;document changes6 VERIFY CLOSURETrack defects andconfirm the resultRepeat faults point to an unresolved cause,so the loop runs again.A replacement that restores function may not address why the part failed.
Figure 14. Loop for preventing recurring failures. Predictive trending can give earlier warning than a fixed alarm.
AGL Visual Encyclopedia: Predictive maintenance Preventive maintenance sequence Condition grading
AGL Engineering Hub

Explore the AGL Engineering Knowledge Hub

Fundamentals

Standards & Compliance

Runway, Taxiway & Approach Lighting

Surface Movement & Safety

PAPI

Electrical Engineering & Power

Photometry & Testing

Maintenance, Inspection & Safety

Resources, Documentation & Careers

FAQ

Frequently Asked Questions

Q1What should be checked first when runway lights fail?

Record the affected location and circuit, establish whether one or multiple lights are affected, and review available CCR and control-system indications. Follow the airport’s approved fault-investigation procedure to identify the cause.

Q2Why do runway lights keep failing?

Repeated failures may be associated with unresolved connection issues, equipment deterioration, environmental exposure, cable or installation problems, compatibility concerns or other system conditions. Review the failure history and evidence before determining the root cause.

Q3Why do airfield lights flicker?

Flickering may result from intermittent connections, equipment faults, circuit-related problems or control and power equipment issues. Establish the extent and timing of the symptom and review available records before selecting an authorized test method.

Q4What causes water ingress in airfield lights?

Possible contributors include damaged seals, compromised cable entries, incorrect assembly, physical damage or environmental conditions outside the equipment’s intended requirements. The corrective action should address the cause and assess any related electrical or optical damage.

Q5What causes isolating transformer failure?

Possible causes include insulation deterioration, moisture ingress, physical damage, connection defects, installation issues or operation outside the intended rating. Verify the actual cause using the applicable approved inspection and test procedures.

Q6Why does the CCR show a fault when some lights are not working?

A CCR indication can arise from protection operation, regulator-related issues or a circuit problem, among other possibilities. Review the recorded alarm and the affected lighting circuit. The indication alone does not prove which component has failed.

Q7Can an AGL fault be repaired while the circuit is energized?

All work must follow the airport-approved electrical safety, isolation, permit and maintenance procedures. Do not undertake intrusive electrical work simply because a lighting circuit appears to be operating normally.

Q8How can AGL failures be reduced?

Maintain accurate asset and circuit records, perform authorized preventive maintenance, use compatible specified equipment, investigate recurring symptoms and document corrective-action verification. Follow the approved programme for the particular airport and equipment.

Q9Does replacing a failed light solve the problem?

It may resolve a confirmed fixture defect, but it may not address an underlying connection, transformer, cable, installation or system problem. The failure cause and required post-maintenance verification should be documented.

Q10Why runway lights are not working: what are the common causes?

When runway lights are not working, common causes include a tripped or faulted CCR, an open circuit, a failed transformer or connector, water ingress, power loss and control problems. Work through the fault methodically from the supply and CCR to the circuit and the individual light.

Q11What causes AGL transformer failure?

AGL transformer failure can be caused by water ingress, insulation breakdown, overheating, mechanical damage, poor connections and surge damage. An isolating transformer fault can lead to an open circuit or an earth fault.

Q12How to document an AGL fault?

To document an AGL fault, record the date, location, circuit, symptoms, readings, suspected cause, action taken, parts used and who verified the repair. Add photographs and refer to the fault report template on this page.

Q13What are airfield lighting failure causes, airfield ground lighting failure causes and airport lighting failure causes?

The main airfield lighting failure causes are electrical (open circuits, insulation faults), environmental (water, heat, corrosion), mechanical (impact, vibration, jet blast), control-related and maintenance-related. Airfield ground lighting failure causes and airport lighting failure causes are the same in principle.

Q14What are runway lighting failure causes and runway edge lights failure causes?

Runway lighting failure causes include circuit faults, damaged fixtures, water ingress and CCR faults. Runway edge lights failure causes typically include lamp or LED failure, broken lenses, connector problems and transformer faults.

Q15What are runway centreline lights failure causes and threshold lights failure causes?

Runway centreline lights failure causes are often mechanical damage from aircraft wheels and water ingress in inset fixtures. Threshold lights failure causes include similar damage, plus aiming and cabling issues.

Q16What are taxiway lighting failure causes and approach lighting failure causes?

Taxiway lighting failure causes include damage from vehicles, water ingress, and cable and connector faults. Approach lighting failure causes include lightning, structural damage, cable faults and failures in remote elevated fixtures.

Q17What are AGL series circuit failure causes?

AGL series circuit failure causes include open circuits from a failed transformer or connector, insulation or earth faults, cable damage and incorrect loading. Series circuits are sensitive to any break in the loop.

Q18What are constant current regulator failure causes?

Constant current regulator failure causes include component failure, overheating, overload, supply problems, surges and control faults. Alarms and CCR trip indications help narrow down the cause.

Q19What are airfield lighting isolation transformer failure causes?

Airfield lighting isolation transformer failure causes include moisture, insulation damage, overheating, connector failure and mechanical stress.

Q20What are airfield lighting cable failure causes?

Airfield lighting cable failure causes include mechanical damage during excavation, insulation breakdown, water ingress at joints, rodent or ground movement damage and age.

Q21What are airfield lighting control system failure causes and ALCMS failure causes?

Airfield lighting control system failure causes include communication faults, power supply failures, software or configuration errors and hardware faults. ALCMS failure causes are similar and may also include network and interface problems.

Related Resources

Related AGL Resources

Explore these related technical pages.

Asset Lifecycle, Reliability Engineering and Failure Management

Reliability concepts, failure records and root-cause investigation.

Open guide

AGL Maintenance in India

Maintenance planning and practical AGL maintenance guidance.

Open guide

AGL Testing and Inspection

Inspection, testing and verification principles.

Open guide

AGL Circuit Fault Analysis Tool

A related resource for organizing circuit fault analysis.

Open guide

AGL Inspection and Audit Checklists

Structured inspection and defect-recording templates.

Open guide

AGL Diagrams and Schematics

Equipment diagrams, circuit information and system layouts.

Open guide
Final Note

Final Note

Airfield lighting failures can have several possible causes, and similar symptoms may arise in different parts of the system. Reliable fault diagnosis depends on identifying the affected equipment, reviewing available records, using approved inspection and test methods, documenting evidence and verifying corrective action.

Use this guide as an educational starting point. The applicable airport procedures, approved engineering documents, manufacturer instructions and authorized maintenance practices take precedence for all operational work.

Technical disclaimer: This page provides general technical information and does not replace approved airport procedures, manufacturer instructions, project specifications or the judgment of authorized personnel.
Explore More

Explore More AGL Engineering Resources

AGL Inspection Checklists

Inspection, maintenance and audit templates.

Open guide

Airport Lighting Maintenance Schedule

Planning routine AGL maintenance.

Open guide

CCR Deep Dive

Constant current regulator operation.

Open guide

AGL Toolkit

Practical tools for AGL engineers.

Open guide
Field Insight

Engineering & Expert Notes

Find the Pattern Before Replacing Parts
Diagnosis

Check whether failures cluster by circuit, location, age or weather. A pattern points to a shared cause such as a cable fault, a drainage problem or a batch issue, not a run of unrelated bad luck.

Water Is the Most Repeated Root Cause
Water Ingress

Poor seals, blocked drainage and damaged connectors let moisture into fixtures, transformers and bases. Fix the entry path as well as the failed component, or the fault will return.

Intermittent Faults Usually Mean a Connection Problem
Connections

Flickering or a light that works on some days is more often a marginal joint, corroded contact or movement in the base than a failed lamp or LED.

A Replaced Transformer Can Hide a Cable Fault
Series Circuit

If a secondary fault is repeated after replacement, test the cable and connector before accepting the transformer as the cause. Measure rather than swap by habit.

Keep a Fault Log That Others Can Learn From
Records

Record symptom, location, cause found and fix applied. After a few months the log shows which parts and areas deserve design changes or more frequent inspection.

Confirm Safe Isolation Before Touching the Circuit
Safety

Series circuits can carry hazardous voltage even when lights look off. Follow the lock-out and test procedure for every fault visit, however minor the job appears.

Precision AGL Academy

Understand AGL. Build Your Engineering Skills.

You now have a structured way to approach AGL failures, from recording the symptom and establishing the scope to reviewing evidence, verifying corrective action and closing the record.

Take the next step with Precision AGL Academy.

Learn AGL Step by Step

Build your knowledge through structured technical learning covering:

AGL Fundamentals Components Electrical Systems Design Photometry Testing Troubleshooting Maintenance

Move from understanding why AGL equipment fails to developing the practical knowledge needed to analyse, operate and maintain complete AGL systems.

Understand the system. Build the knowledge. Apply the engineering.